Building Amendment (Specific Use Bushfire Protected Buildings and Other Matters) Regulations 2016
Authorised by the Chief Parliamentary Counsel
Authorised Version
i
Building Amendment (Specific Use Bushfire
Protected Buildings and Other Matters)
Regulations 2016
S.R. No. 114/2016
TABLE OF PROVISIONS
Regulation Page
1 Objective 1
2 Authorising provisions 1
3 Commencement 2
4 Principal Regulations 2
5 New definitions inserted 2
6 New regulation 114 inserted 2
7 Requirements for permits involving bushfire safety matters 3
8 Requests for information 4
9 Regulation 403 revoked 4
10 Flood areas 4
11 Water supply for fire fighting purposes 4
12 Access for emergency vehicles 4
13 Relevant building surveyor must accept bushfire attack level in
planning scheme or site assessment for planning permit 4
14 Regulation 811(3) and (4) revoked and insertion of new
regulation 812 5
═══════════════
Endnotes 6
-- 1 of 8 --
Authorised by the Chief Parliamentary Counsel
Authorised Version
1
STATUTORY RULES 2016
S.R. No. 114/2016
Building Act 1993
Building Amendment (Specific Use Bushfire
Protected Buildings and Other Matters)
Regulations 2016
The Administrator of the State of Victoria as the Governor's
deputy, with the advice of the Executive Council, makes the
following Regulations:
Dated: 6 September 2016
Responsible Minister:
RICHARD WYNNE
Minister for Planning
ANDREW ROBINSON
Clerk of the Executive Council
1 Objective
The objective of these Regulations is to amend the
Building Regulations 2006—
(a) to provide for further construction
requirements for specific use bushfire
protected buildings; and
(b) to make miscellaneous amendments.
2 Authorising provisions
These Regulations are made under sections 7, 9,
261 and 262 of, and Schedule 1 to, the Building
Act 1993.
-- 2 of 8 --
Building Amendment (Specific Use Bushfire Protected Buildings and Other
Matters) Regulations 2016
S.R. No. 114/2016
Authorised by the Chief Parliamentary Counsel
2
3 Commencement
These Regulations come into operation on
30 September 2016.
4 Principal Regulations
In these Regulations, the Building Regulations
20061 are called the Principal Regulations.
5 New definitions inserted
In regulation 105 of the Principal Regulations
insert the following definitions—
"AS 3959 means AS3959—2009 Construction
of buildings in bushfire-prone areas, as
incorporated for the time being by the BCA;
bushfire attack level has the same meaning as in
AS 3959;
planning scheme means a planning scheme
approved under the Planning and
Environment Act 1987 as in force
from time to time;".
6 New regulation 114 inserted
After regulation 113A of the Principal
Regulations insert—
'114 Specific use bushfire protected
buildings—Construction requirements
(1) The BCA Volume One applies as if
in clause A1.1, after the definition of
Sole-occupancy unit there were inserted—
"Specific use bushfire protected building
means—
(a) a Class 9a or 9c building; or
(b) a building from which a
school within the meaning of
section 1.1.3(1) of the Education
-- 3 of 8 --
Building Amendment (Specific Use Bushfire Protected Buildings and Other
Matters) Regulations 2016
S.R. No. 114/2016
Authorised by the Chief Parliamentary Counsel
3
and Training Reform Act 2006
is operated; or
(c) a building from which an early
childhood centre is operated; or
(d) a Class 4 part of a building
associated with a building referred
to in paragraphs (a) to (c); or
(e) a Class 10a building or deck
associated with a building referred
to in paragraphs (a) to (c).".
(2) The BCA Volume One applies as if in
Part G5—
(a) in the Application at the foot of
clause GP5.1, there were inserted after
paragraph (a)—
"(ab) a specific use bushfire protected
building; or";
(b) in clause G5.1, there were inserted after
paragraph (a)—
"(ab) a specific use bushfire protected
building; or";
(c) in clause G5.2, there were inserted after
paragraph (a)—
"(ab) a specific use bushfire protected
building; or".'.
7 Requirements for permits involving bushfire safety
matters
In regulation 309A(1)(b) of the Principal
Regulations omit "approved under the
Planning and Environment Act 1987
as in force from time to time".
-- 4 of 8 --
Building Amendment (Specific Use Bushfire Protected Buildings and Other
Matters) Regulations 2016
S.R. No. 114/2016
Authorised by the Chief Parliamentary Counsel
4
8 Requests for information
In regulation 326(2)(c) of the Principal
Regulations omit "(within the meaning of
regulation 811(4))".
9 Regulation 403 revoked
Regulation 403 of the Principal Regulations is
revoked.
10 Flood areas
In regulation 802(2)(b) of the Principal
Regulations omit "under the Planning and
Environment Act 1987".
11 Water supply for fire fighting purposes
(1) In regulation 808(1)(b) of the Principal
Regulations omit "approved under the
Planning and Environment Act 1987
as in force from time to time".
(2) For regulation 808(8)(a) of the Principal
Regulations substitute—
"(a) the bushfire attack level of the allotment is
determined as LOW or 12·5 in accordance
with AS 3959; and".
12 Access for emergency vehicles
In regulation 809(1)(b) of the Principal
Regulations omit "approved under the
Planning and Environment Act 1987 as
in force from time to time".
13 Relevant building surveyor must accept bushfire
attack level in planning scheme or site assessment
for planning permit
In the heading to regulation 811 of the Principal
Regulations, for "assessment" substitute
"in planning scheme or site assessment for
planning permit".
-- 5 of 8 --
Building Amendment (Specific Use Bushfire Protected Buildings and Other
Matters) Regulations 2016
S.R. No. 114/2016
Authorised by the Chief Parliamentary Counsel
5
14 Regulation 811(3) and (4) revoked and insertion of
new regulation 812
For regulation 811(3) and (4) of the Principal
Regulations substitute—
"812 Relevant building surveyor must accept
bushfire attack level of 12·5
(1) Despite anything to the contrary in the BCA,
if—
(a) a building is to be constructed in a
designated bushfire prone area; and
(b) the bushfire attack level for the site is—
(i) determined as LOW by the
relevant building surveyor; or
(ii) accepted by the relevant
building surveyor as LOW
under regulation 811—
the relevant building surveyor must accept
that the bushfire attack level is 12·5 when
determining the construction requirements
that are applicable to the building.
(2) In this regulation, building means—
(a) a Class 1, 2 or 3 building; or
(b) a Class 10a building or deck that is
associated with a Class 1, 2 or 3
building; or
(c) a specific use bushfire protected
building.
Note
Regulation 114 inserts a definition of Specific
use bushfire protected building into the
BCA Volume One.".
═══════════════
-- 6 of 8 --
Endnotes
Building Amendment (Specific Use Bushfire Protected Buildings and Other
Matters) Regulations 2016
S.R. No. 114/2016
Authorised by the Chief Parliamentary Counsel
6
Endnotes
1 Reg. 4: S.R. No. 68/2006. Reprint No. 3 as at 11 December 2014.
Reprinted to S.R. No. 197/2014. Subsequently amended by
S.R. Nos 8/2015, 21/2015, 70/2015, 134/2015, 152/2015, 157/2015,
21/2016, 33/2016, 49/2016 and 63/2016 and extended in operation by
S.R. No. 4/2016.
——
Table of Applied, Adopted or Incorporated Matter
The following table of applied, adopted or incorporated matter is included in
accordance with the requirements of regulation 5 of the Subordinate Legislation
Regulations 2014.
In this table—
BCA means the Building Code of Australia comprising—
(a) Volume One of the National Construction Code Series including any
variations or additions in the Appendix Victoria set out in the
Appendices to that Volume; and
(b) Volume Two of the National Construction Code Series including
any Victoria additions set out in Appendix A of that Volume;
BCA Volume One means Volume One of the National Construction Code
Series including any variations or additions in the Appendix Victoria set out
in the Appendices to that Volume;
National Construction Code Series means the National Construction Code
Series published by the Australian Building Codes Board as amended or remade
from time to time.
-- 7 of 8 --
Endnotes
Building Amendment (Specific Use Bushfire Protected Buildings and Other
Matters) Regulations 2016
S.R. No. 114/2016
Authorised by the Chief Parliamentary Counsel
7
Statutory rule
provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 5 which
inserts the definition
of AS 3959 in
regulation 105 of the
Building Regulations
2006
AS 3959—2009 Construction
of buildings in bushfire-prone
areas, published by Standards
Australia on 10 March 2009,
reissued incorporating
Amendments No. 1
(November 2009), No. 2
(February 2011) and No. 3
(November 2011), as
incorporated by the BCA
The whole
Regulation 6 which
inserts regulation 114
in the Building
Regulations 2006
BCA Volume One,
published February 2016
by the Australian Building
Codes Board
Clause A1.1
and Part G5