TABLE OF PROVISIONS
Regulation Page
1 Objective 1
2 Authorising provisions 1
3 Definitions 2
4 New regulations 119 to 121 inserted 2
119 Farm buildings—definitions 2
120 Farm buildings—fire fighting equipment 3
121 Farm buildings—emergency lighting 6
5 Regulation 1804 amended 6
═══════════════
ENDNOTES 7
-- 1 of 8 --
Authorised by the Chief Parliamentary Counsel
Authorised Version
1
STATUTORY RULES 2014
S.R. No. 173/2014
Building Act 1993
Building Amendment (Farm Buildings) Regulations
2014
The Lieutenant-Governor as the Governor's deputy with the
advice of the Executive Council makes the following
Regulations:
Dated: 21 October 2014
Responsible Minister:
MATTHEW GUY
Minister for Planning
YVETTE CARISBROOKE
Clerk of the Executive Council
1 Objective
The objective of these Regulations is to amend the
Building Regulations 2006 in relation to the
application of the Building Code of Australia to
certain farm buildings.
2 Authorising provisions
These Regulations are made under sections 7, 9,
261 and 262 of, and Schedule 1 to, the Building
Act 1993.
-- 2 of 8 --
S.R. No. 173/2014
Building Amendment (Farm Buildings) Regulations 2014
2
Authorised by the Chief Parliamentary Counsel
3 Definitions
In regulation 105 of the Building Regulations
20061 insert the following definition—
"AS 2419.1 means AS 2419.1—2005 Fire hydrant
installations Part 1: System design,
installation and commissioning, as issued or
published from time to time;".
4 New regulations 119 to 121 inserted
After regulation 118 of the Building Regulations
2006 insert—
'119 Farm buildings—definitions
The BCA Volume One applies as if, in
clause A1.1, after the definition of Fan
motorpower there were inserted—
"Farm building means a building—
(a) that is used for the purpose of
farming; and
(b) that has been classified as a
Class 7b building or a Class 8
building; and
(c) in which the total number of
persons accommodated at any
time does not exceed one person
for each 200m2 of floor area or
part of such area up to a maximum
of 6 persons.
Farming, for the purposes of the definition
of farm building, means agriculture,
cropping, grazing, animal husbandry,
intensive animal keeping, horticultural
growing or dairy farming.".
r. 3
-- 3 of 8 --
S.R. No. 173/2014
Building Amendment (Farm Buildings) Regulations 2014
3
Authorised by the Chief Parliamentary Counsel
120 Farm buildings—fire fighting equipment
(1) Despite anything to the contrary in the BCA,
the BCA Volume One applies as if, after
performance requirement EP1.1 there were
inserted—
"Application:
EP1.1 does not apply to or in relation to a farm
building.".
Note
Performance requirement EP1.1 requires the
installation of a fire hose reel system.
(2) The BCA Volume One applies to farm
buildings as if, in deemed-to-satisfy
provision E1.6—
(a) in paragraph (a), after "Portable fire
extinguishers" there were inserted
", except in farm buildings,";
(b) after paragraph (b) there were
inserted—
"(c) In farm buildings, portable fire
extinguishers must be provided as
follows:
(i) not less than the lesser of—
(A) one extinguisher at or
adjacent to every
required exit door; or
(B) one extinguisher for
each 500m2 of floor
area or part of such an
area; and
(ii) not less than one
extinguisher in each room
containing flammable
materials or electrical
r. 4
-- 4 of 8 --
S.R. No. 173/2014
Building Amendment (Farm Buildings) Regulations 2014
4
Authorised by the Chief Parliamentary Counsel
equipment attached to the
farm building.
Example
A control room.
(d) For the purposes of (c), portable
fire extinguisher means an ABE
powder-type portable fire
extinguisher rated not less than
4A:60B:E in accordance with
AS 2444—2001 Portable fire
extinguishers and fire blankets—
Selection and location, as issued
or published from time to time by
Standards Australia.".
(3) Despite anything to the contrary in the BCA,
performance requirement EP1.3 of the BCA
Volume One does not apply to a farm
building in relation to which—
(a) a water supply for firefighting purposes
that complies with subregulation (4) is
available or provided on the allotment
on which the farm building is located;
and
(b) the minimum capacity of that water
supply is 144 000 litres; and
(c) subject to subregulation (5)(c), the
water supply is located within
60 metres of the farm building; and
(d) the water supply is situated so as to
enable emergency services vehicles
access to within 4 metres of the water
supply.
Note
Performance requirement EP1.3 requires the provision
of a fire hydrant system.
r. 4
-- 5 of 8 --
S.R. No. 173/2014
Building Amendment (Farm Buildings) Regulations 2014
5
Authorised by the Chief Parliamentary Counsel
(4) For the purposes of subregulation (3)(a), the
water supply must consist of one or more of
the following—
(a) a water storage tank or tanks;
(b) a dam;
(c) a reservoir;
(d) a river;
(e) a lake;
(f) seawater.
(5) If the whole or any part of the water supply
is contained in a water storage tank—
(a) the water storage tank must be fitted
with at least one large bore suction
connection; and
(b) each large bore suction connection
must be located so as to enable
emergency services vehicles access to
within 4 metres of the large bore
suction connection; and
(c) the water storage tank must be located
not less than 10 metres from the farm
building.
(6) In subregulation (5)—
large bore suction connection means a large
bore suction connection within the
meaning of AS 2419.1.
r. 4
-- 6 of 8 --
S.R. No. 173/2014
Building Amendment (Farm Buildings) Regulations 2014
6
Authorised by the Chief Parliamentary Counsel
121 Farm buildings—emergency lighting
Despite anything to the contrary in the BCA,
the BCA Volume One applies as if, after
performance requirement EP4.1, there were
inserted—
"Application:
EP4.1 does not apply to—
(a) a farm building that has no artificial
lighting; or
(b) a farm building with artificial lighting
where, if that lighting fails, automatic power
to supply lighting to the building is provided
by a fuel-driven back-up generator.".
Note
Performance requirement EP4.1 requires the provision
of illumination for safe evacuation in an emergency.'.
5 Regulation 1804 amended
For the heading to regulation 1804 of the Building
Regulations 2006 substitute—
"Exemption for Class 10 buildings on farm
land".
═══════════════
r. 5
-- 7 of 8 --
S.R. No. 173/2014
Building Amendment (Farm Buildings) Regulations 2014
7
Authorised by the Chief Parliamentary Counsel
ENDNOTES
1 Reg. 3: S.R. No. 68/2006. Reprint No. 2 as at 25 October 2011. Reprinted to
S.R. No. 92/2011. Subsequently amended by S.R. Nos 73/2011, 63/2012,
80/2013, 97/2013, 161/2013, 37/2014, 51/2014, 104/2014 and 109/2014.
——
Table of Applied, Adopted or Incorporated Matter
The following table of applied, adopted or incorporated matter is included in
accordance with the requirements of regulation 5 of the Subordinate Legislation
Regulations 2014.
In this table—
BCA Volume One means Volume One of the National Construction Code
Series including any variations or additions in the Appendix Victoria set out
in the Appendices to that Volume;
Statutory rule
provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 4, which
inserts new
regulation 120(2) of
the Building
Regulations 2006
AS 2444—2001 Portable fire
extinguishers and fire
blankets - Selection and
location, published by
Standards Australia on
9 November 2001, as
incorporated by the BCA
Volume One
The whole
Regulation 4, which
inserts new
regulation 120(6) of
the Building
Regulations 2006
AS 2419.1—2005 Fire
hydrant installations, Part 1:
System design, installation
and commissioning, published
by Standards Australia on
26 November 2005,
incorporating Amendment
No. 1 published June 2007
The whole
Endnotes
-- 8 of 8 --