ELECTRICAL SAFETY REGULATIONS 2024
NORTHERN TERRITORY OF AUSTRALIA
ELECTRICAL SAFETY REGULATIONS 2024
As in force at 28 May 2026
Table of provisions
Part 1 Preliminary matters
1 Title .................................................................................................. 1
2 Commencement .............................................................................. 1
3 Definitions ........................................................................................ 1
4 Meaning of minimum information..................................................... 7
Part 2 Managing risks to health and safety
Division 1 General matters
5 Application of Division ..................................................................... 8
6 Duty to identify hazards ................................................................... 8
7 Hierarchy of control measures ......................................................... 8
8 Maintenance of control measures.................................................... 9
9 Review of control measures ............................................................ 9
10 Safe work practices ....................................................................... 10
11 Multiple duties................................................................................ 10
Division 2 Risk assessments and safe work method
statements
12 Risk assessments and safe work method statements ................... 11
13 Access to risk assessments and safe work method statements .... 12
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 1 Classes of electrical work licences
14 Classes of electrical work licences ................................................ 12
Subdivision 2 Unrestricted electrical work licences
15 Unrestricted electrical mechanic licence ........................................ 13
16 Unrestricted electrical mechanic and fitter licence ......................... 14
17 Term of unrestricted electrical work licences ................................. 14
Subdivision 3 Restricted electrical work licence
18 Restricted electrical work licence................................................... 15
-- 1 of 149 --
Electrical Safety Regulations 2024 ii
19 Endorsements ............................................................................... 15
20 Air-conditioning and refrigeration equipment work
endorsement.................................................................................. 16
21 Disconnect and reconnect work endorsement – basic
electrical equipment ....................................................................... 17
22 Disconnect and reconnect work endorsement – water heaters ..... 17
23 Disconnect and reconnect work endorsement – explosion
protected equipment ...................................................................... 18
24 Disconnect and reconnect work endorsement – self-propelled,
high-voltage earthmoving equipment............................................. 18
25 Domestic appliances and equipment work endorsement .............. 19
26 Electrical cable jointer work endorsement ..................................... 20
27 Electrical fitter work endorsement.................................................. 20
28 Electrical line work endorsement – distribution .............................. 21
29 Electrical line work endorsement – transmission ........................... 21
30 Electronics and communication equipment work endorsement ..... 21
31 Fire protection equipment work endorsement................................ 22
32 Gas equipment work endorsement ................................................ 23
33 Instrumentation and process control equipment work
endorsement.................................................................................. 24
34 Maritime operations work endorsement ......................................... 25
35 Specialised commercial and industrial equipment work
endorsement.................................................................................. 26
36 Water plumbing equipment work endorsement ............................. 27
37 Other electrical work endorsed by Electrical Safety Regulator ...... 27
38 Term of restricted electrical work licence ....................................... 28
Division 2 Electrical contractor licences
39 Eligibility for electrical contractor licence ....................................... 28
40 Nominated person on electrical contractor licence ........................ 29
41 Removal of nominated person ....................................................... 29
42 Term of electrical contractor licence .............................................. 30
Division 3 In-house electrical licences
43 Eligibility for in-house electrical licences........................................ 30
Division 4 Conditions and restrictions
44 Conditions and restrictions on electrical work licence.................... 30
45 Conditions and restrictions on electrical contractor licence ........... 31
46 Advertising by licensed electrical contractor .................................. 31
47 Conditions of in-house electrical licence ........................................ 32
48 Licence not transferable ................................................................ 32
49 Licensee contact details ................................................................ 33
50 Change in body corporate or partnership ...................................... 33
-- 2 of 149 --
Electrical Safety Regulations 2024 iii
Division 5 Apprentices and trainees
51 Levels of supervision ..................................................................... 34
52 Apprentices.................................................................................... 36
53 Trainees......................................................................................... 36
54 Term of trainee permit ................................................................... 37
55 Trainee permit not transferable...................................................... 37
56 Duty of person conducting business or undertaking in relation
to supervision ................................................................................ 37
57 Duty of holder of electrical work licence supervising ..................... 38
58 Offence of failing to supervise apprentice or trainee...................... 39
59 Refusal of work .............................................................................. 39
Division 6 Other matters related to licences and trainee
permits
60 Other eligibility criteria for electrical work licence .......................... 40
61 Colour identification test statement................................................ 40
62 Further assessment ....................................................................... 41
63 Producing licence, trainee permit and other documents ................ 41
64 Return of licence or trainee permit................................................. 41
65 Replacement of licence or trainee permit ...................................... 42
66 Renewal of licence or trainee permit ............................................. 42
Part 4 General electrical safety
Division 1 Electrical equipment and electrical
installations
67 Unsafe electrical equipment .......................................................... 42
68 Cord extension sets and flexible cables ........................................ 43
69 Safety switches.............................................................................. 43
70 Electrical equipment in hostile environment................................... 44
71 Untested electrical equipment in hostile environment.................... 45
Division 2 Electrical work on energised electrical
equipment
72 Application of Division ................................................................... 45
73 Testing to determine whether equipment is energised .................. 45
74 Prohibition of electrical work on energised electrical equipment.... 46
75 Preventing inadvertent energising ................................................. 46
76 Preliminary steps ........................................................................... 47
77 Performing electrical work on energised electrical equipment ....... 47
78 Authorised access only .................................................................. 49
79 Contact with equipment being worked on ...................................... 49
-- 3 of 149 --
Electrical Safety Regulations 2024 iv
Division 3 Safety switches
80 Use of socket outlets in hostile environment.................................. 49
81 Testing of safety switches.............................................................. 50
Division 4 Consumer electrical equipment
82 Approved consumer electrical equipment ...................................... 51
Part 5 Conduct of electrical work
Division 1 Application of Part
83 Application of Part ......................................................................... 52
Division 2 Wiring Rules
84 Exemption for streetlights .............................................................. 52
85 Compliance with Wiring Rules ....................................................... 52
86 Examination and testing ................................................................ 52
87 Compliance with Wiring Rules ....................................................... 53
88 Compliance with current standards ............................................... 53
89 Suitability of testing instruments .................................................... 54
90 Duty to comply with Wiring Rules .................................................. 54
91 Duty of person conducting business or undertaking ...................... 54
Division 3 General electrical work
92 Electrical work involving pools, water features and water tubs ...... 55
93 Duty of person in control to fix defect ............................................ 56
94 Earthing ......................................................................................... 56
95 Duty to preserve insulation of electric line ..................................... 57
96 Duty to ensure safety of disconnected overhead electric line ........ 58
Division 4 Certificates of compliance
97 Contents of certificates of compliance ........................................... 58
Division 5 Misrepresentation
98 Misrepresentations about electrical work ....................................... 59
99 Misrepresentation about contract to perform electrical work ......... 59
100 Misrepresentation about licence .................................................... 60
101 Other misrepresentation ................................................................ 60
Division 6 Other matters
102 Electrical equipment with serious defect ........................................ 60
103 Rescue and resuscitation training.................................................. 61
-- 4 of 149 --
Electrical Safety Regulations 2024 v
Part 6 Conduct of other work
Division 1 Construction work
104 Standards for electrical equipment for construction ....................... 61
105 Electrical equipment for construction ............................................. 62
106 Construction wiring ........................................................................ 62
107 Defence ......................................................................................... 63
Division 2 Manufacturing work
108 Double adaptors and piggyback plugs prohibited .......................... 63
109 Safety switches.............................................................................. 63
110 Specified electrical equipment ....................................................... 63
111 Manufacturing work – safety switch ............................................... 65
Division 3 Service work and office work
112 Specified electrical equipment ....................................................... 66
113 Safety switches – service work and office work ............................. 68
Division 4 Electrical work related to amusement devices,
rides and activities
114 Application of Division ................................................................... 69
115 Double adaptors and piggyback plugs prohibited .......................... 69
116 Specified electrical equipment ....................................................... 70
117 Amusement devices and amusement rides ................................... 71
118 Safety switches.............................................................................. 73
Division 5 Work in proximity to exposed conductors or
electrical equipment
119 Work involving danger of direct contact with live conductors ......... 74
120 Work in proximity to exposed conductors or electrical
equipment ...................................................................................... 74
Division 6 High voltage electrical work
121 Performance of high voltage live line work .................................... 76
122 High voltage live line work management plan................................ 76
123 Work in proximity to exposed high voltage conductors or
electrical equipment ....................................................................... 77
124 Direct contact with exposed high voltage electrical equipment ...... 78
125 Live high voltage line work............................................................. 78
126 Authorisations – high voltage......................................................... 78
127 Regular assessment ...................................................................... 79
-- 5 of 149 --
Electrical Safety Regulations 2024 vi
Division 7 Work in roof spaces
128 Roof spaces de-energised ............................................................. 79
129 Offence related to electrical work in roof spaces ........................... 81
Division 8 Installation of ceiling insulation
130 Training for assessment of electrical risk ....................................... 81
131 Installation standard ...................................................................... 81
132 Energised equipment in ceiling prohibited ..................................... 82
133 Assessment of electrical risk and control measures ...................... 82
134 Electrically conductive ceiling insulation on joists prohibited ......... 82
135 Metal or other conductive fasteners for ceiling insulation
prohibited ....................................................................................... 83
Division 9 Photovoltaic arrays
136 Standards ...................................................................................... 83
137 Enclosure of photovoltaic array ..................................................... 84
138 Power conversion equipment ........................................................ 85
139 Isolators prohibited on roof ............................................................ 85
140 Disconnection points ..................................................................... 86
141 Signage ......................................................................................... 86
Division 10 Energy storage systems
142 Installation of energy storage systems .......................................... 86
143 Smoke alarm – indoors .................................................................. 87
144 Safety – indoor installation............................................................. 87
145 Safety – outside installation ........................................................... 88
146 Storage of combustible materials .................................................. 89
147 Signage – general ......................................................................... 90
148 Fire indicator panels ...................................................................... 91
149 Signage – commercial operations ................................................. 91
150 Registration – commercial operations ........................................... 92
151 Notice of ceasing operation ........................................................... 93
Division 11 Electric vehicles
152 Smoke alarms................................................................................ 93
153 Signage – inside building ............................................................... 94
154 Signage – on land or outside building ............................................ 95
155 Other signage ................................................................................ 96
156 Protection for freestanding electrical connection points for
electric vehicles ............................................................................. 97
-- 6 of 149 --
Electrical Safety Regulations 2024 vii
Part 7 Electricity infrastructure
Division 1 Service lines
157 Duties related to service lines ........................................................ 97
158 Inspection of clamps and apparatus .............................................. 98
159 Structure supporting electric line or equipment.............................. 98
Division 2 Maintenance related to powerlines
160 Trimming of trees near overhead electric line ................................ 99
161 Consultation with owner or occupier before remedial action to
clear vegetation ............................................................................. 99
Division 3 Proximity to powerlines and electricity
infrastructure
Subdivision 1 Proximity to powerlines
162 Proximity to powerlines ................................................................ 100
163 Erection of buildings in proximity to powerlines ........................... 101
164 Prohibition of certain activities in proximity to powerlines ............ 102
165 Register of underground powerlines ............................................ 103
Subdivision 2 Conduct in proximity to electricity
infrastructure
166 Placement of materials in proximity to electricity infrastructure ... 103
167 Placement of materials in proximity to supporting structures ....... 103
168 Placement of materials in proximity to substations ...................... 104
169 Prohibition of burning in proximity to electricity infrastructure ...... 104
170 Protection of underground powerlines ......................................... 105
171 Entangled objects ........................................................................ 105
172 Altering ground levels near electricity infrastructure .................... 106
Subdivision 3 Transportation in proximity to powerlines
173 Transportation ............................................................................. 107
174 Recovery of costs ........................................................................ 108
175 Obstruction of road ...................................................................... 108
176 Interference or damage of road ................................................... 108
177 Removal of danger on road ......................................................... 108
Division 4 Cathodic protection systems
178 Cathodic protection systems........................................................ 108
-- 7 of 149 --
Electrical Safety Regulations 2024 viii
Division 5 Distribution entity improvement notices
179 Giving improvement notice .......................................................... 109
180 Contents of improvement notices ................................................ 110
181 Extension of time for compliance with improvement notices........ 110
182 Compliance with improvement notice .......................................... 110
Division 6 Other matters
183 Changes to safety management and mitigation plan ................... 111
Part 8 Approved safety switches
191 Performing electrical installation work for domestic residences
and residential premises .............................................................. 111
Part 9 Miscellaneous
192 Register of engaged workers ....................................................... 112
193 Record of apprentices and trainees ............................................. 112
194 Appointment of inspectors ........................................................... 112
195 Fees ............................................................................................ 112
196 Display of distribution entity improvement notice ......................... 113
197 Costs of ensuring compliance with direction ................................ 113
198 General offence ........................................................................... 114
199 Register of licences ..................................................................... 114
200 Information sharing ...................................................................... 115
Part 10 Infringement notice offences
201 Infringement notice offence and infringement amount payable ... 117
202 When infringement notice may be given ...................................... 118
203 Contents of infringement notice ................................................... 118
204 Effective date of payment methods ............................................. 119
205 Expiation of offence ..................................................................... 119
206 Withdrawal of infringement notice................................................ 119
207 Effect of Part ................................................................................ 119
Schedule 1 Supervision of apprentices and trainees
Schedule 2 Proximity limits
Schedule 3 Erection of building or structure in
proximity to powerline
Schedule 4 Proximity to powerlines
Schedule 5 Fees and refunds
-- 8 of 149 --
Electrical Safety Regulations 2024 ix
Schedule 6 Infringement notice penalties
ENDNOTES
-- 9 of 149 --
-- 10 of 149 --
NORTHERN TERRITORY OF AUSTRALIA
____________________
As in force at 28 May 2026
____________________
ELECTRICAL SAFETY REGULATIONS 2024
Regulations under the Electrical Safety Act 2022
Part 1 Preliminary matters
1 Title
These Regulations may be cited as the Electrical Safety
Regulations 2024.
2 Commencement
These Regulations commence on the commencement of
section 253 of the Electrical Safety Act 2022.
3 Definitions
In these Regulations:
amusement device means an amusement device as defined in
AS 3533.3 (Amusement Rides And Devices – In-Service
Inspection).
amusement ride means an amusement ride as defined in
AS 3533.3 (Amusement Rides And Devices – In-Service
Inspection).
approved safety switch means a residual current device with or
without integral overcurrent protection that is certified and
registered in the Electrical Equipment Safety System (EESS)
framework.
AS means an Australian Standard published by Standards Australia
International Limited.
AS/NZS means a Joint Australian/New Zealand Standard published
by Standards Australia International Limited.
-- 11 of 149 --
Part 1 Preliminary matters
Electrical Safety Regulations 2024 2
class, in relation to a building or structure, means a building class
as defined in the National Construction Code, published by the
Australian Building Codes Board.
competent, in relation to a person, means the person has acquired
knowledge and skill, through training, qualifications, experience, or
a combination of these, that enables the person to correctly perform
the task required.
construction work means:
(a) construction work as defined in regulation 289 of the Work
Health and Safety (National Uniform Legislation)
Regulations 2011, but does not include work specified in
regulation 114; or
(b) work done in conjunction with construction work mentioned in
paragraph (a).
Example for definition construction work, paragraph (b)
Installation of plumbing in a house under construction.
date of possession, for land, means the date the purchaser or
lessee of the land enters into lawful possession of the land.
de-energise means to disconnect or separate from a source of
supply of electricity.
Note for definition de-energise
To de-energise does not necessarily mean to isolate, earth, discharge or render
out of commission.
direct supervision, see regulation 51(1).
domestic residence means a building or structure, or a part of a
building or structure, that:
(a) is used, or designed to be used, as a single or multiple
dwelling; and
(b) is not used, or designed to be used, for temporary
accommodation.
Examples for definition domestic residence, paragraph (b), of temporary
accommodation
A boarding house or a residence available for online short-term homestays.
-- 12 of 149 --
Part 1 Preliminary matters
Electrical Safety Regulations 2024 3
electric vehicle means a motor vehicle that:
(a) uses an electric motor for propulsion, whether or not it is also
fitted with an internal combustion engine; and
(b) takes and stores energy from an external source of electricity;
and
(c) is not equipped with a fuel cell for converting hydrogen to
electricity; and
(d) does not operate at extra-low voltage.
Note for definition electric vehicle
This includes vehicles that operate with only an electric motor as well as plug-in
hybrid electric vehicles.
endorsement, in relation to a restricted electrical work licence,
means an endorsement on the licence, mentioned in regulation 19,
that determines the scope of electrical work the licensee is entitled
to perform under the licence.
energy storage system includes any of the following:
(a) a battery storage system;
(b) a capacitor energy storage system;
(c) a hybrid energy power system;
(d) a system of hydrogen fuel cells;
(e) a micro grid system;
(f) a standalone power system;
(g) a permanently connected uninterruptable power system;
(h) any other system used to store energy determined by the
Electricity Safety Regulator.
Note definition energy storage system, paragraph (g)
A permanently connected uninterruptible power system does not include a
portable uninterruptible power system.
general purpose socket-outlet means a low voltage socket-outlet
that:
(a) has a rating of 10 A; and
-- 13 of 149 --
Part 1 Preliminary matters
Electrical Safety Regulations 2024 4
(b) is designed to fit a three-pin flat-pin plug that complies with
AS/NZS 3112 (Approval and test specification – plugs and
socket-outlets); and
(c) is used, intended to be used or could at some time reasonably
be expected to be used, for more than one appliance.
general supervision, see regulation 51(2).
hostile environment means an environment in which the normal
use of electrical equipment exposes the equipment to operating
conditions likely to result in damage to the equipment or a reduction
in its expected life span.
Examples for definition hostile environment
Exposure to moisture, heat, vibration, mechanical damage, corrosive chemicals
or dust.
infringement amount, see regulation 201(2).
infringement notice, see regulation 202.
infringement notice offence, see regulation 201(1).
manufacturing work means assembly, disassembly, fabrication,
installation, maintenance, manufacturing, refurbishment or repair,
but does not include the following:
(a) work specified in regulation 114;
(b) construction work.
Examples for definition manufacturing work
Installing the interior fittings of a shop, manufacturing clothes and repairing
leaking pipes.
minimum information, see section 4.
non-combustible barrier means a wall or barrier consisting of any
of the following materials:
(a) brick or masonry;
(b) concrete;
(c) compressed cement sheeting;
-- 14 of 149 --
Part 1 Preliminary matters
Electrical Safety Regulations 2024 5
(d) ceramic or terracotta tiles.
Note for definition non-combustible barrier
Steel cladding, particle board and timber (whether painted or not) do not
constitute a non-combustible barrier.
physically isolated, in relation to electrical equipment, an electrical
installation or an electric line, means the electrical equipment,
electrical installation or electric line, or the part of the equipment,
installation or line on which the electrical work is being performed,
is not and cannot be connected to a source of supply by:
(a) the closure of a switch, fuse-switch, circuit-breaker, contactor,
air-break or other device; or
(b) the replacement or insertion of a fuse or link; or
(c) the connection or reconnection of a wire, cable or conductor to
a part of the installation at which partial supply is available.
Note for definition physically isolated
Physical isolation is disconnection from all sources of supply that renders
energisation impossible without intentional and deliberate action.
piggyback plug means a plug that:
(a) is permanently attached to a cord extension set having a
single means of connection to a low voltage supply; and
(b) has one outlet facility at the rear of the plug.
power conversion equipment means an electrical device that
converts or manipulates one kind of electrical power from a voltage
or current source into another kind of electrical power with respect
to voltage, current and frequency.
proximity means a distance equal to or closer than the proximity
limit C(i) set out in in Schedule 2.
proximity limit means a proximity limit set out in Schedule 2.
purchaser, of land, means the person to whom title to the land is
being transferred under the Land Title Act 2000.
registered training organisation means a training organisation in
the Territory that is registered under the National Vocational
Educational and Training Regulator Act 2011 (Cth).
-- 15 of 149 --
Part 1 Preliminary matters
Electrical Safety Regulations 2024 6
residential premises, see section 4 of the Residential Tenancies
Act 1999.
Note for definition residential premises
Residential premises include a caravan intended for occupation as a place of
residence and a houseboat intended for occupation as a place of residence.
risk assessment, see regulation 12(1).
roof space, of a building, means a space in the building, other than
a habitable room in the space, that is:
(a) immediately under the roof; or
(b) if there is a ceiling under the roof or a part of the roof – the
space between the roof, or that part of the roof, and the
ceiling.
safe work method statement, see regulation 12(2).
safety switch means a residual current device.
service line means an electric line that:
(a) forms part of an electricity network; and
(b) connects consumer terminals to other parts of the electricity
network.
service work means work that is not any of the following:
(a) work specified in regulation 114;
(b) construction work;
(c) manufacturing work;
(d) office work.
Examples for definition service work
Cleaning a motel, cleaning solar panels, cooking in a restaurant, providing health
services at a health facility, selling goods from a shop, teaching at an education
facility and caring for children at a childcare centre.
tenancy agreement, see section 4 of the Residential Tenancies
Act 1999.
Trades Recognition Australia is a business unit within the
Department of Employment and Workplace Relations, Government
of Australia.
-- 16 of 149 --
Part 1 Preliminary matters
Electrical Safety Regulations 2024 7
trainee permit means a trainee permit referred to in section 63 of
the Act.
type 1 safety switch means a residual current device, whether or
not portable, with a rated residual current of not more than 10 mA.
type 2 safety switch means a residual current device, whether or
not portable, with a rated residual current of more than 10 mA but
not more than 30 mA.
Wiring Rules means AS/NZS 3000, as amended from time to time.
4 Meaning of minimum information
The minimum information required for the inspection, testing or
retesting of electrical equipment is:
(a) in all cases:
(i) the date of the inspection, testing or retesting; and
(ii) the day by which the equipment must be reinspected
and retested; and
(b) for a test or retest performed by an individual employed or
engaged by a body corporate – at least one of the following:
(i) the name of the individual;
(ii) the individual's electrical contractor licence number;
(iii) the name of the body corporate;
(iv) the body corporate's electrical contractor licence
number; and
(c) for a test or retest performed by an individual who is not
employed or engaged by a body corporate – at least one of
the following:
(i) the name of the individual;
(ii) the individual's electrical contractor licence number;
(iii) the electrical contractor licence number of the
individual's employer;
(iv) the individual's electrical work licence number.
-- 17 of 149 --
Part 2 Managing risks to health and safety
Division 1 General matters
Electrical Safety Regulations 2024 8
Part 2 Managing risks to health and safety
Division 1 General matters
5 Application of Division
This Division applies to a person conducting a business or
undertaking who has a duty under the Act to:
(a) ensure the business or undertaking is safe from electrical risk;
or
(b) manage electrical risk at a workplace.
6 Duty to identify hazards
The person conducting a business or undertaking must identify
reasonably foreseeable hazards that could give rise to an electrical
safety risk.
7 Hierarchy of control measures
(1) To eliminate or minimise an electrical risk at a workplace, the
person conducting a business or undertaking must, so far as is
reasonably practicable, first do one or more of the following:
(a) substitute, in whole or in part, the hazard giving rise to the risk
with something that gives rise to a lesser risk;
(b) isolate the hazard from any person exposed to it;
(c) implement engineering controls.
(2) If an electrical risk remains after complying with subregulation (1),
the person must minimise the remaining risk by implementing
administrative controls, so far as is reasonably practicable.
(3) If an electrical risk remains after complying with subregulation (2),
the person must finally minimise the remaining risk by providing and
ensuring the use of suitable personal protective equipment, so far
as is reasonably practicable.
Note for regulation 7
A combination of the controls set out in this regulation may be used to minimise
risks if a single control is not sufficient for the purpose.
-- 18 of 149 --
Part 2 Managing risks to health and safety
Division 1 General matters
Electrical Safety Regulations 2024 9
8 Maintenance of control measures
The person conducting a business or undertaking must do all that is
reasonably practicable to ensure any control measure implemented
at the workplace is:
(a) fit for purpose; and
(b) suitable for the nature and duration of the work; and
(c) installed, set up and used correctly.
9 Review of control measures
(1) The person conducting a business or undertaking must review and
revise (if necessary) any control measures implemented at the
workplace to do all that is reasonably practicable to ensure
compliance with regulation 8.
(2) Without limiting subregulation (1), the person conducting a business
or undertaking must review and revise (if necessary) a control
measure in the following circumstances:
(a) the control measure does not control the risk it was
implemented to control so far as is reasonably practicable;
(b) a proposed change at the workplace is likely to give rise to a
new or different electrical risk that the measure may not
effectively control;
(c) a new hazard or electrical risk is identified;
(d) consultation by the person indicates that a review is
necessary;
(e) a review is requested under subregulation (4).
Examples for subregulation (2)(a)
1 The results of monitoring show that the control measure does not control
the electrical risk.
2 A reportable event occurs because of a serious electrical event or a
dangerous electrical event.
(3) Without limiting subregulation (2)(b), a change at the workplace
includes:
(a) a change to the workplace itself or any aspect of the work
environment; or
(b) a change to a system of work, a process or a procedure.
-- 19 of 149 --
Part 2 Managing risks to health and safety
Division 1 General matters
Electrical Safety Regulations 2024 10
(4) A health and safety representative for workers at a workplace,
elected under the Work Health and Safety (National Uniform
Legislation) Act 2011, may request a review of a control measure if
the representative believes on reasonable grounds that:
(a) a circumstance affects or may affect the electrical safety at the
workplace; and
(b) the control measure has not been reviewed in response to the
circumstance.
10 Safe work practices
The person conducting a business or undertaking must ensure the
safety of all persons while electrical work is performed at the
workplace by:
(a) providing suitable protection to workers from any adjacent live
electrical conductors or adjacent live parts of electrical
equipment; and
(b) ensuring workers use insulated tools and equipment when
appropriate; and
(c) ensuring workers use equipment and plant designed and
made in accordance with recognised electricity industry
practice; and
(d) implementing safe work practices.
11 Multiple duties
A duty imposed on a person under a provision of these Regulations
does not limit or affect:
(a) any duty the person has under the Act; or
(b) any duty the person has under the Work Health and Safety
(National Uniform Legislation) Act 2011; or
(c) any other provision of these Regulations, unless expressly
provided otherwise.
-- 20 of 149 --
Part 2 Managing risks to health and safety
Division 2 Risk assessments and safe work method statements
Electrical Safety Regulations 2024 11
Division 2 Risk assessments and safe work method
statements
12 Risk assessments and safe work method statements
(1) A risk assessment, in relation to electrical work, means a written
assessment by a competent person of the electrical risk associated
with the electrical work.
(2) A safe work method statement, in relation to electrical work,
means a written assessment of electrical risk that:
(a) identifies the nature of the electrical work; and
(b) specifies the hazards associated with the electrical work and
the electrical risks associated with those hazards; and
(c) describes the control measures to be implemented to control
the electrical risks; and
(d) describes how those control measures are to be implemented,
monitored and reviewed.
Example of a control measure for subregulation (2)(c)
Preventing public access to the area where the electrical work is being
performed.
(3) Subject to subregulation (4), the person required under these
Regulations to prepare a risk assessment or a safe work method
statement must keep it:
(a) in the case a risk assessment – for at least 28 days after the
electrical work to which it relates is completed; and
(b) in the case a safe work method statement – until the electrical
work to which it relates is completed.
(4) If a serious electrical event or dangerous electrical event occurs in
connection with the work to which the assessment or statement
relates, the person must keep the assessment or statement for at
least 5 years after the event occurs.
Note for subregulation (4)
The terms serious electrical event and dangerous electrical event are defined
in section 3 of the Act.
(5) A person commits an offence if the person contravenes
subregulation (3) or (4).
Maximum penalty: 50 penalty units.
-- 21 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 1 Classes of electrical work licences
Electrical Safety Regulations 2024 12
(6) An offence against subregulation (5) is an offence of strict liability.
13 Access to risk assessments and safe work method statements
(1) A person keeping a risk assessment or safe work method
statement under regulation 12(4) must do all that is reasonably
practicable to ensure a copy of the assessment or statement,
during the period for which the assessment or statement must be
kept, is:
(a) readily accessible to any worker engaged by the person to
perform electrical work to which the assessment or statement
relates; and
(b) available for inspection under the Act.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 1 Classes of electrical work licences
14 Classes of electrical work licences
(1) Electrical work licences are classified into the following classes:
(a) unrestricted electrical work licence;
(b) restricted electrical work licence.
(2) Unrestricted electrical work licences are classified into the following
subclasses:
(a) unrestricted electrical mechanic licence;
(b) unrestricted electrical mechanic and fitter licence.
-- 22 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 2 Unrestricted electrical work licences
Electrical Safety Regulations 2024 13
Subdivision 2 Unrestricted electrical work licences
15 Unrestricted electrical mechanic licence
(1) An unrestricted electrical mechanic licence entitles the licensee to
do or supervise the following electrical work:
(a) installing or changing an electrical installation or electric line;
(b) maintaining and repairing electrical equipment and connecting
electrical equipment to a source of electricity.
(2) To be eligible for an unrestricted electrical mechanic licence, an
applicant must meet the following criteria:
(a) if the applicant was trained in Australia:
(i) completed an apprenticeship under the Training and
Skills Development Act 2016; and
(ii) obtained, during that apprenticeship, at least 12 months
experience in the trade work of an electrical mechanic;
and
(iii) successfully completed a Certificate III in
Electro-technology Electrician, or another course of
instruction for electrical mechanic apprentices approved
by the Electrical Safety Regulator, at a registered
training organisation;
(b) if the applicant was trained outside Australia:
(i) successfully completed a course of instruction and
training, relevant to the Australian context, at a training
organisation accredited in the place outside Australia;
and
(ii) obtained, during that training, at least 12 months
experience in the trade work of an electrical mechanic;
and
(iii) was assessed by Trades Recognition Australia and
issued with an Offshore Technical Skills Record in the
class of 34111 Electrician (General).
-- 23 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 2 Unrestricted electrical work licences
Electrical Safety Regulations 2024 14
16 Unrestricted electrical mechanic and fitter licence
(1) An unrestricted electrical mechanic and fitter licence entitles the
licensee to do or supervise all electrical work.
Examples for subregulation (1)
1 Installing or changing an electrical installation or electric line.
2 Maintaining, repairing and connecting an item of electrical equipment to a
source of electricity.
3 Making, operating, testing or repairing electrical equipment.
(2) To be eligible for an unrestricted electrical mechanic and fitter
licence, an applicant must meet the following criteria:
(a) completed an apprenticeship under the Training and Skills
Development Act 2016;
(b) obtained, during that apprenticeship:
(i) at least 12 months experience in the trade work of an
electrical mechanic; and
(ii) at least 12 months experience in the trade work of an
electrical fitter;
(c) successfully completed the course of instruction for a
Certificate III in Electro-technology Electrician, or another
course of instruction for electrical mechanic apprentices
approved by the Electrical Safety Regulator, at a registered
training organisation.
(3) An unrestricted electrical mechanic licensee is eligible for an
unrestricted electrical mechanic and fitter licence if the licensee:
(a) satisfies the Electrical Safety Regulator, by an examination
conducted or approved by the Electrical Safety Regulator, that
the worker has sufficient knowledge of the trade of electrical
fitter; or
(b) can demonstrate at least 12 months experience in the trade
work of an electrical fitter.
17 Term of unrestricted electrical work licences
An unrestricted electrical mechanic licence and an unrestricted
electrical mechanic and fitter licence may be issued, renewed or
reinstated for a maximum of 5 years.
-- 24 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 15
Subdivision 3 Restricted electrical work licence
18 Restricted electrical work licence
(1) A restricted electrical work licence entitles the licensee to perform
or supervise only the electrical work to which the licensee is entitled
under an endorsement on the licence.
(2) The only eligibility criteria for a restricted electrical work licence are
the eligibility criteria applicable to the endorsement on the licence.
(3) A restricted electrical work licence:
(a) does not entitle the licensee to perform or supervise electrical
installation work, unless expressly provided as being within
the scope of the endorsement on the licence; and
(b) does not entitle the licensee to an electrical work licence of
another class or endorsement; and
(c) must not be considered in deciding whether the licensee is
qualified to obtain or hold an electrical work licence of another
class or endorsement.
19 Endorsements
A restricted electrical work licence may have one or more of the
following endorsements:
(a) air-conditioning and refrigeration equipment work;
(b) disconnect and reconnect work – basic electrical equipment;
(c) disconnect and reconnect work – water heaters;
(d) disconnect and reconnect work – explosion protected
equipment;
(e) disconnect and reconnect work – self-propelled, high-voltage
earthmoving equipment;
(f) domestic appliances and equipment work;
(g) electrical cable jointer work;
(h) electrical fitter work;
(i) electrical line work – distribution;
(j) electrical line work – transmission;
-- 25 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 16
(k) electronics and communication equipment work;
(l) fire protection equipment work;
(m) gas equipment work;
(n) instrumentation and process control equipment work;
(o) maritime operations work;
(p) specialised commercial and industrial equipment work;
(q) water plumbing equipment work;
(r) other electrical work not listed above that is endorsed on the
licence by the Electrical Safety Regulator.
20 Air-conditioning and refrigeration equipment work
endorsement
(1) An air-conditioning and refrigeration equipment work endorsement
entitles the licensee to perform the following electrical work:
(a) disconnecting and reconnecting fixed wired electrical
equipment;
(b) attaching plugs and cords to 250 volts;
(c) attaching plugs and cords to 1 000 volts AC or 1 500 volts DC;
(d) fault finding to determine component failure in equipment to
1 000 volts AC or 1 500 volts DC.
(2) To be eligible for an air-conditioning and refrigeration equipment
work endorsement, an applicant must meet the following criteria:
(a) if the applicant was trained in Australia:
(i) completed an apprenticeship or traineeship in the trade
of a refrigeration mechanic under the Training and Skills
Development Act 2016; and
(ii) obtained, during that apprenticeship or traineeship, at
least 12 months experience in the trade work of an
air-conditioning and refrigeration mechanic; and
(iii) successfully completed the course of instruction for an
air-conditioning and refrigeration mechanic at a
registered training organisation;
-- 26 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 17
(b) if the applicant was trained outside Australia:
(i) successfully completed a course of instruction and
training, relevant to the Australian context, at a training
organisation accredited in the place outside Australia;
and
(ii) obtained, during that training, at least 12 months
experience in the trade work of an air-conditioning and
refrigeration mechanic; and
(iii) was assessed by Trades Recognition Australia and
issued with an Offshore Technical Skills Record in the
class of 342111 Air-conditioning and Refrigeration
Mechanic.
21 Disconnect and reconnect work endorsement – basic electrical
equipment
(1) A disconnect and reconnect work endorsement – basic electrical
equipment entitles the licensee to perform electrical work
disconnecting and reconnecting composite equipment, control
devices and motors.
(2) To be eligible for a disconnect and reconnect work endorsement –
basic electrical equipment, an applicant must meet the following
criteria:
(a) successfully completed a relevant course of instruction for
disconnect and reconnect – electrical equipment connected to
low voltage installation wiring, or its equivalent, at a registered
training organisation;
(b) completed an apprenticeship or traineeship as a diesel fitter /
mechanical fitter;
(c) obtained, during that apprenticeship or traineeship, at least
12 months experience in diesel fitting / mechanical fitting work.
22 Disconnect and reconnect work endorsement – water heaters
(1) A disconnect and reconnect work endorsement – water heaters
entitles the licensee to perform electrical work disconnecting and
reconnecting electric water cylinders, water reticulation systems,
irrigation systems including pumps, oil-fired heating and water
reticulated air-conditioning systems to 1 000 volts AC or
1 500 volts DC.
-- 27 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 18
(2) To be eligible for a disconnect and reconnect work endorsement –
water heaters, an applicant must meet the following criteria:
(a) successfully completed a relevant course of instruction for
disconnect and reconnect – electrical equipment connected to
low voltage installation wiring, or its equivalent, at a registered
training organisation;
(b) completed an apprenticeship or traineeship as a plumber
under the Training and Skills Development Act 2016;
(c) obtained, during that apprenticeship or traineeship, at least
12 months experience in the work of a plumber;
(d) holds a licence or registration issued under the Plumbers and
Drainers Licensing Act 1983.
23 Disconnect and reconnect work endorsement – explosion
protected equipment
(1) A disconnect and reconnect work endorsement – explosion
protected equipment entitles the licensee to perform electrical work
disconnecting and reconnecting appliances and control devices
connected to low voltage installation wiring.
(2) To be eligible for a disconnect and reconnect work endorsement –
explosion protected equipment, an applicant must meet the
following criteria:
(a) successfully completed a relevant course of instruction for
disconnect and reconnect – electrical equipment connected to
low voltage installation wiring, or its equivalent, at a registered
training organisation;
(b) successfully completed a relevant course of instruction for
electrical equipment in hazardous areas, or its equivalent, at a
registered training organisation;
(c) demonstrate at least 12 months work experience relevant to
disconnect and reconnect work for electrical equipment in
explosion protected areas;
(d) demonstrate a need to disconnect and reconnect electrical
equipment in explosion protected areas.
24 Disconnect and reconnect work endorsement – self-propelled,
high-voltage earthmoving equipment
(1) A disconnect and reconnect work endorsement – self-propelled,
high-voltage earthmoving equipment entitles the licensee to
-- 28 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 19
perform electrical work disconnecting and reconnecting electric
propulsion components of engine driven, self-propelled earth
moving equipment vehicles operating up to 3 300 V.
(2) To be eligible for a disconnect and reconnect work endorsement –
self-propelled, high-voltage earthmoving equipment, an applicant
must meet the following criteria:
(a) successfully completed a relevant course of instruction for
disconnect and reconnect – electrical equipment connected to
high voltage installation wiring, or its equivalent, at a
registered training organisation;
(b) completed an apprenticeship or traineeship as a heavy vehicle
fitter / mechanic under the Training and Skills Development
Act 2016;
(c) demonstrate at least 12 months experience as a diesel fitter /
mechanical fitter.
25 Domestic appliances and equipment work endorsement
(1) A domestic appliances and equipment work endorsement entitles
the licensee to perform the following electrical work:
(a) disconnecting and reconnecting fixed wired cooking
appliances to 250 volts;
(b) fault finding to determine component failure in appliances
connected both by plug and cord and fixed wiring up to
250 volts.
(2) To be eligible for a domestic appliances and equipment work
endorsement, an applicant must meet the following criteria:
(a) completed a traineeship in the trade of domestic appliance
service technician under the Training and Skills Development
Act 2016;
(b) obtained, during that traineeship, at least 6 months experience
in the trade work of domestic appliance service;
(c) successfully completed a relevant course of instruction for
domestic appliance service at a registered training
organisation;
(d) completed a training course approved by the Electrical Safety
Regulator for domestic appliances and equipment work.
-- 29 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 20
(3) An applicant who does not meet the criteria in subregulation (2), is
eligible for the domestic appliances and equipment work
endorsement if the worker satisfies the Electrical Safety Regulator
that the applicant has sufficient knowledge of the trade of domestic
appliance service by:
(a) demonstrating at least 12 months experience in the trade work
of appliance repair; and
(b) if the Electrical Safety Regulator approves an examination for
domestic appliances and equipment work – successfully
passing that examination.
26 Electrical cable jointer work endorsement
(1) An electrical cable jointer work endorsement entitles the licensee to
perform electrical work installing, jointing and terminating covered
cables.
(2) To be eligible for an electrical cable jointer work endorsement, an
applicant must meet the following criteria:
(a) completed an apprenticeship or traineeship in the trade of
electric cable jointer under the Training and Skills
Development Act 2016;
(b) obtained, during that apprenticeship or traineeship, at least
12 months experience in electric cable jointing work;
(c) successfully completed a relevant course of instruction for
laying, cable jointing and terminating of underground
polymeric cables at a registered training organisation.
27 Electrical fitter work endorsement
(1) An electrical fitter work endorsement entitles the licensee to
perform electrical work making, operating, testing or repairing
electrical equipment.
(2) To be eligible for an electrical fitter work endorsement, an applicant
must meet the following criteria:
(a) completed an apprenticeship or traineeship in the trade of
electrical fitter under the Training and Skills Development
Act 2016;
(b) obtained, during that apprenticeship or traineeship, at least
12 months experience in the trade work of an electrical fitter;
-- 30 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 21
(c) successfully completed the course of instruction for electrical
fitter worker at a registered training organisation.
28 Electrical line work endorsement – distribution
(1) An electrical line work endorsement – distribution entitles the
licensee to perform electrical work installing, testing or repairing
electric lines that are restricted to distribution only.
(2) To be eligible for an electrical line work endorsement – distribution,
an applicant must meet the following criteria:
(a) completed an apprenticeship or traineeship in a relevant trade
under the Training and Skills Development Act 2016;
(b) obtained, during that apprenticeship or traineeship, at least
12 months experience in the associated trade work;
(c) successfully completed a relevant course of instruction for
electrical line worker at a registered training organisation.
29 Electrical line work endorsement – transmission
(1) An electrical line work endorsement – transmission entitles the
licensee to perform electrical work installing, testing or repairing
electric lines that are restricted to transmission only.
(2) To be eligible for an electrical line work endorsement –
transmission, an applicant must meet the following criteria:
(a) completed an apprenticeship or traineeship in a relevant trade
under the Training and Skills Development Act 2016;
(b) obtained, during that apprenticeship or traineeship, at least
12 months experience in the associated trade work;
(c) successfully completed a relevant course of instruction for
electrical line worker at a registered training organisation.
30 Electronics and communication equipment work endorsement
(1) An electronics and communication equipment work endorsement
entitles the licensee to perform the following electrical work:
(a) attaching flexible cords and plugs to electrical equipment to
250 volts;
(b) attaching flexible cords and plugs to electrical equipment to
1 000 volts AC or 1 500 volts DC;
-- 31 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 22
(c) attaching flexible cables and plugs to electrical equipment
connected to high voltage.
(2) To be eligible for an electronics and communication equipment
work endorsement, an applicant must meet the following criteria:
(a) if the applicant was trained in Australia:
(i) completed an apprenticeship or traineeship in the trade
of electronics and communication technician under the
Training and Skills Development Act 2016; and
(ii) obtained, during that apprenticeship or traineeship, at
least 12 months experience in the trade of electronics
and communication technician; and
(iii) successfully completed the course of instruction for
electronics and communication at a registered training
organisation;
(b) if the applicant was trained outside Australia:
(i) successfully completed a course of instruction and
training, relevant to the Australian context, at a training
organisation accredited in the place outside Australia;
and
(ii) obtained, during that training, at least 12 months
experience in the trade work of an electronics and
communication technician; and
(iii) was assessed by Trades Recognition Australia and
issued with an Offshore Technical Skills Record in the
class of 342313 Electronics and Communication
Technician.
31 Fire protection equipment work endorsement
(1) A fire protection equipment work endorsement entitles the licensee
to perform electrical work installing, testing and inspecting electrical
equipment for fire protection.
-- 32 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 23
(2) To avoid doubt, a fire protection equipment work endorsement does
not entitle the licensee to perform or supervise electrical installation
work.
(3) To be eligible for a fire protection equipment work endorsement, an
applicant must meet the following criteria:
(a) if the applicant was trained in Australia:
(i) completed an apprenticeship or traineeship in the trade
of fire protection under the Training and Skills
Development Act 2016; and
(ii) obtained, during that apprenticeship or traineeship, at
least 12 months experience in the trade work of a fire
protection equipment technician; and
(iii) successfully completed a relevant course of instruction
for fire protection equipment technician at a registered
training organisation; and
(iv) completed a training course approved by the Electrical
Safety Regulator for a fire protection equipment work
endorsement;
(b) if the applicant trained outside Australia:
(i) successfully completed a relevant course of instruction
for fire protection equipment technician at a training
organisation accredited in the place outside Australia;
and
(ii) obtained, during that training, at least 12 months
experience in the trade work of a fire protection
equipment worker; and
(iii) was assessed by Trades Recognition Australia and
issued with an Offshore Technical Skills Record in the
class of 399918 Fire Protection Equipment.
32 Gas equipment work endorsement
(1) A gas equipment work endorsement entitles the licensee to perform
the following electrical work:
(a) disconnecting and reconnecting type A or B gas equipment or
components, including fault finding to 1 000 volts AC or
1 500 volts DC;
(b) attaching plugs and cords to 250 volts;
-- 33 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 24
(c) fault finding to determine component failure in type A or B gas
equipment to 1 000 volts AC or 1 500 volts DC.
(2) To be eligible for a gas equipment work endorsement, an applicant
must meet the following criteria:
(a) completed an apprenticeship or traineeship in the trade of gas
fitting under the Training and Skills Development Act 2016;
(b) obtained, during that apprenticeship or traineeship, at least
12 months experience in the trade work of gas fitting;
(c) successfully completed a relevant course of instruction for gas
fitting at a registered training organisation;
(d) holds a gas fitter certificate issued under the Dangerous
Goods Regulations 1985;
(e) if the Electrical Safety Regulator approves a training course
for a gas equipment work endorsement – successfully
completed that course.
33 Instrumentation and process control equipment work
endorsement
(1) An instrumentation and process control equipment work
endorsement entitles the licensee to perform the following electrical
work:
(a) disconnecting and reconnecting process control devices
(PCDs);
(b) repairing and replacing plugs and cords to 250 volts AC on
PCDs;
(c) repairing and replacing plugs and cords to 1 000 volts AC or
1 500 volts DC on PCDs;
(d) locating and repairing faults in PCDs to 1 000 volts AC or
1 500 volts DC;
(e) if trained in a recognised associated trade – modifying PCDs.
-- 34 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 25
(2) To be eligible for an instrumentation and process control equipment
work endorsement, an applicant must meet the following criteria:
(a) if the applicant was trained in Australia:
(i) completed an apprenticeship or traineeship in the trade
of instrumentation and process control under the
Training and Skills Development Act 2016; and
(ii) obtained, during that apprenticeship or traineeship, at
least 12 months experience in the trade work of an
instrumentation and process control technician; and
(iii) successfully completed the course of instruction for an
instrumentation and process control technician at a
registered training organisation;
(b) if the applicant was trained outside Australia:
(i) successfully completed a course of instruction and
training, relevant to the Australian context, at a training
organisation accredited in the place outside Australia;
and
(ii) obtained, during that training, at least 12 months
experience in the trade work of an electronic instrument
trades worker; and
(iii) was assessed by Trades Recognition Australia and
issued with an Offshore Technical Skills Record in the
class of 342314 Electronic Instrument Trades Worker
(General).
34 Maritime operations work endorsement
(1) A maritime operations work endorsement entitles the licensee to
perform electrical work maintaining and repairing electrical
equipment on maritime vessels.
(2) To be eligible for a maritime operations work endorsement, an
applicant must meet the following criteria:
(a) completed an apprenticeship or traineeship in the trade of
maritime operations under the Training and Skills
Development Act 2016;
(b) obtained, during that apprenticeship or traineeship, at least
12 months experience in the work of a marine engine driver;
-- 35 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 26
(c) completed a Certificate III in Maritime Operations or a training
course approved by the Electrical Safety Regulator for
maritime operations.
35 Specialised commercial and industrial equipment work
endorsement
(1) A specialised commercial and industrial equipment work
endorsement entitles the licensee to perform the following electrical
work:
(a) disconnecting and reconnecting commercial and industrial
equipment to 1 000 volts AC or 1 500 volts DC;
(b) attaching plugs and cords to 250 volts;
(c) attaching plugs and cords to 1 000 volts AC or 1 500 volts DC;
(d) fault finding to determine component failure in commercial and
industrial equipment to 1 000 volts AC or 1 500 volts DC.
(2) To be eligible for a specialised commercial and industrial equipment
work endorsement, an applicant must meet the following criteria:
(a) completed a traineeship in the trade of industrial service
technician under the Training and Skills Development
Act 2016;
(b) obtained, during that traineeship, at least 6 months experience
in the trade work of commercial and industrial equipment
service;
(c) successfully completed a relevant course of instruction for
industrial automation and control at a registered training
organisation;
(d) completed a training course approved by the Electrical Safety
Regulator for commercial and industrial equipment work.
(3) An applicant who does not meet the criteria in subregulation (2), is
eligible for a specialised commercial and industrial equipment work
endorsement if the worker satisfies the Electrical Safety Regulator
that the applicant has sufficient knowledge of the trade of industrial
service technician by:
(a) demonstrating at least 12 months experience in the trade work
of industrial service; and
-- 36 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 1 Electrical work licences
Subdivision 3 Restricted electrical work licence
Electrical Safety Regulations 2024 27
(b) passing an examination for specialised commercial and
industrial equipment work conducted or approved by the
Electrical Safety Regulator; and
(c) satisfies the Electrical Safety Regulator, by an examination
conducted or approved by the Electrical Safety Regulator, that
the worker has sufficient knowledge of the trade of industrial
service technician.
36 Water plumbing equipment work endorsement
(1) A water plumbing equipment work endorsement entitles the
licensee to perform electrical work disconnecting and reconnecting
electric water cylinders, water reticulation systems, irrigation
systems including pumps and oil fired heating and water reticulated
air-conditioning systems to 1 000 volts AC or 1 500 volts DC.
(2) To be eligible for a water plumbing equipment work endorsement,
an applicant must meet the following criteria:
(a) completed an apprenticeship or traineeship in the trade of
plumbing under the Training and Skills Development Act 2016;
(b) obtained, during that apprenticeship or traineeship, at least
12 months experience in the work of a plumber;
(c) successfully completed a relevant course of instruction for
plumbing at a registered training organisation;
(d) holds a licence or registration issued under the Plumbers and
Drainers Licensing Act 1983;
(e) if the Electrical Safety Regulator approves a training course
for a water plumbing equipment endorsement – successfully
completed that course.
37 Other electrical work endorsed by Electrical Safety Regulator
(1) The Electrical Safety Regulator may endorse a restricted electrical
work licence for other electrical work specified by the Electrical
Safety Regulator that is not otherwise provided for in these
Regulations.
(2) An endorsement for electrical work specified under
subregulation (1) entitles the licensee to perform the electrical work
specified in the endorsement.
(3) The Electrical Safety Regulator must publish any electrical work
specified under subregulation (1) on the Electrical Safety
Regulator's website.
-- 37 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 2 Electrical contractor licences
Electrical Safety Regulations 2024 28
(4) To be eligible for an endorsement for electrical work specified under
subregulation (1), an applicant must meet the following criteria:
(a) successfully completed any training requirements specified by
the Electrical Safety Regulator for the endorsement;
(b) obtained, during that training, experience in the required field
as specified by the Electrical Safety Regulator for the
endorsement;
(c) hold any other licence or registration required by the Electrical
Safety Regulator.
38 Term of restricted electrical work licence
A restricted electrical work licence (with any endorsement) may be
issued, renewed or reinstated for a maximum of 5 years.
Division 2 Electrical contractor licences
39 Eligibility for electrical contractor licence
For section 55(2) of the Act, the following criteria are prescribed:
(a) the applicant holds, or at least one owner, partner or
employee of the applicant holds, an unrestricted electrical
work licence and has held it for at least 2 years;
(b) the applicant demonstrates that the electrical work to be
performed under the licence will be performed by;
(i) the holder of an electrical work licence; or
(ii) a person under the supervision of the holder of an
electrical work licence;
(c) the person who holds the unrestricted electrical work licence
under paragraph (a) has successfully completed the units of
competency (contractor course) approved by the Electrical
Safety Regulator;
(d) the applicant holds at least $5 000 000 of public and products
liability insurance for liability arising from personal injury or
property damage from the electrical work performed under the
licence.
-- 38 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 2 Electrical contractor licences
Electrical Safety Regulations 2024 29
40 Nominated person on electrical contractor licence
(1) The Electrical Safety Regulator must endorse an electrical
contractor licence with the name of at least one owner, partner or
employee (nominated person) who:
(a) has successfully completed, the units of competency
(contractor course) approved by the Electrical Safety
Regulator; and
(b) holds an unrestricted electrical work licence and has held it for
at least 2 years.
(2) An electrical contractor licensee may have more than
one nominated person.
(3) A person must not be a nominated person for more than
one electrical contractor licensee.
(4) An electrical contractor licensee must not change the licensee's
nominated person without the approval of the Electrical Safety
Regulator.
41 Removal of nominated person
(1) An electrical contractor licensee must notify the Electrical Safety
Regulator if a person whose name is endorsed on an electrical
contractor licence under regulation 40(1) as a nominated person
ceases to:
(a) hold an unrestricted electrical work licence; or
(b) be an owner, partner or employee of the electrical contractor.
(2) Notification under subregulation (1) must be made within 30 days
after the event occurs.
(3) After receiving the notice under subregulation (1), the Electrical
Safety Regulator must remove the name of the nominated person
from the endorsement on the electrical contractor licence.
(4) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
-- 39 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 4 Conditions and restrictions
Electrical Safety Regulations 2024 30
42 Term of electrical contractor licence
An electrical contractor licence may be issued, renewed or
reinstated for a maximum of 3 years.
Division 3 In-house electrical licences
43 Eligibility for in-house electrical licences
For section 55(2) of the Act, the following criteria are prescribed:
(a) the applicant, or at least one owner, partner or employee of
the applicant, holds an unrestricted electrical work licence and
has held it for at least 2 years;
(b) the person who holds the unrestricted electrical work licence
under paragraph (a) demonstrates having practical experience
for at least 2 years under that licence;
(c) the person who holds the unrestricted electrical work licence
under paragraph (a) has successfully completed, the units of
competency (contractor course) approved by the Electrical
Safety Regulator.
Division 4 Conditions and restrictions
44 Conditions and restrictions on electrical work licence
For section 50(4) of the Act, the following conditions and restrictions
are prescribed:
(a) the licensee must not enter into a contract for electrical work,
unless the licensee is an electrical contractor licensee or an
in-house electrical licensee;
(b) the licensee must not perform electrical installation work,
unless the licensee holds:
(i) an unrestricted electrical work licence; or
(ii) a restricted electrical work licence with an endorsement
authorising electrical installation work;
(c) in the case of a licensee who is unable to pass a colour
identification test – the licensee must wear corrective lenses
while performing electrical work if required to do so by the
Electrical Safety Regulator;
-- 40 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 4 Conditions and restrictions
Electrical Safety Regulations 2024 31
(d) the licensee must not perform any electrical work unless it is
performed:
(i) as an employee of an electrical contractor licensee or an
in-house electrical licensee; or
(ii) for the purpose of wiring the premises or capital
equipment of the licensee or the electrical contractor
licensee or in-house electrical licensee employing the
licensee; or
(iii) without compensation;
(e) any condition or restriction imposed by the Electrical Safety
Regulator under section 59 of the Act;
(f) if the Electrical Safety Regulator approves a continuing
professional development program – compliance with the
requirements of that program.
45 Conditions and restrictions on electrical contractor licence
For section 51(4) of the Act, the following conditions and restrictions
are prescribed:
(a) any electrical work performed under the licence must be
performed by the holder of an electrical work licence;
(b) the licensee must not allow an electrical worker who is unable
to pass a colour identification test to perform electrical work
without wearing corrective lenses if the worker is required to
do so by the Electrical Safety Regulator;
(c) the licensee must maintain at least $5 000 000 of public and
products liability insurance for liability arising from personal
injury or property damage from the electrical work performed
under the licence;
(d) any condition or restriction imposed by the Electrical Safety
Regulator under section 59 of the Act;
(e) the licensee must not perform any electrical work without
having a nominated person endorsed on the licence in
accordance with regulation 40.
46 Advertising by licensed electrical contractor
(1) This regulation applies in relation to conduct that occurs on or after
1 July 2026.
-- 41 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 4 Conditions and restrictions
Electrical Safety Regulations 2024 32
(2) The holder of an electrical contractor licence who advertises the
holder's business must ensure the advertisement:
(a) states the name under which the holder is licensed or the
holder's registered business name; and
(b) states that the holder is licensed under the Act and the
identifying number of the holder's electrical contractor licence.
(3) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
(5) In this regulation:
advertising does not include identifying the name or business of
the licensee on the following:
(a) an employee's uniform;
(b) the licensee's vehicle;
(c) the licensee's buildings or structures.
47 Conditions of in-house electrical licence
For section 52(3) of the Act, the following conditions are prescribed:
(a) any electrical work performed under the licence must be
performed by an employee who holds an electrical work
licence;
(b) the licensee must not perform any electrical installation work
under the licence unless the licensee employs the holder of an
unrestricted electrical work licence;
(c) the licensee must not offer to perform or perform electrical
work to the public;
(d) the licensee must not carry on the business or undertaking of
an electrical contractor.
48 Licence not transferable
A licence is not transferable by the licensee.
-- 42 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 4 Conditions and restrictions
Electrical Safety Regulations 2024 33
49 Licensee contact details
(1) A licensee must, without delay, give the Electrical Safety Regulator
written notice of any change in the licensee's postal address, email
address and telephone number.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 5 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
50 Change in body corporate or partnership
(1) A licensee that is a body corporate or a partnership must, without
delay, give the Electrical Safety Regulator written notice of any
change in:
(a) the name of the body corporate or partnership; or
(b) if the body corporate or partnership carries on business under
a name other than its name – the name under which it carries
on business; or
(c) in the case of a partnership – the membership of the
partnership.
(2) The notice must be accompanied by the electrical contractor
licence and may be accompanied by an application in the approved
form about how the Electrical Safety Regulator is to act under
subregulation (5).
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 20 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
(5) After receiving the notice and considering any accompanying
application, the Electrical Safety Regulator must:
(a) endorse the licence with information about the change of
name or business name and reissue it to the body corporate
or partnership; or
(b) cancel the licence and issue a new licence; or
(c) cancel the licence.
-- 43 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 5 Apprentices and trainees
Electrical Safety Regulations 2024 34
(6) A new licence may be issued to a partnership with a change in its
membership only if the Electrical Safety Regulator is satisfied that:
(a) the entire business of electrical contracting work carried on by
the partnership in the Territory before the membership change
is to be carried on by the partnership after the new licence is
issued; and
(b) the partnership complies with the eligibility requirements for
the issue of the licence.
(7) To avoid doubt, a licence reissued with an endorsement of the
change of the name or business name of the body corporate or
partnership has, subject to the endorsement, continuing effect as
the original electrical contractor licence.
(8) A new licence issued by the Electrical Safety Regulator under this
regulation must be endorsed with a memorandum stating the
reasons for the issue of the new licence.
(9) If the licence is cancelled under subregulation (5)(c), the Electrical
Safety Regulator must give the body corporate or partnership a
decision notice for the decision to cancel.
Division 5 Apprentices and trainees
51 Levels of supervision
(1) For sections 9(2)(f), 62(4)(a) and 63(4)(a) of the Act, direct
supervision, in relation to an apprentice or trainee, means that:
(a) the holder of an electrical work licence is, as far as reasonably
practicable, present in the immediate work area of the
apprentice or trainee at all times while the electrical work is
being performed; and
(b) the holder of an electrical work licence can observe the
apprentice or trainee and their work; and
(c) the apprentice or trainee and the holder of an electrical work
licence are able to communicate directly; and
(d) while the electrical work is being performed by the apprentice
or trainee, the holder of an electrical work licence:
(i) provides instruction and demonstrates the correct
procedures for performing the work; and
(ii) monitors the work; and
-- 44 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 5 Apprentices and trainees
Electrical Safety Regulations 2024 35
(iii) provides guidance; and
(iv) checks, as required, that the work complies with the Act
and these Regulations; and
(e) when the electrical work is completed by the apprentice or
trainee, the holder of an electrical work licence checks and
tests the work to ensure the work is safe from electrical risk
and complies with the Act and these Regulations.
(2) For sections 62(4)(b) and 63(4)(b) of the Act, general supervision,
in relation to an apprentice or trainee, means:
(a) in the case of work specified in Schedule 1 performed by an
apprentice or trainee with a specified amount of experience
that requires general supervision (level 1) – the holder of an
electrical work licence:
(i) is present at the place where the electrical work is being
performed, at all times while the work is being
performed; and
(ii) while the electrical work is being performed:
(A) provides instruction and direction, as required; and
(B) is readily available to provide advice and guidance;
and
(C) periodically monitors the work; and
(D) checks, as required, that the work complies with
the Act and these Regulations; and
(iii) when the electrical work is complete, checks and tests
the work to ensure the work is safe and complies with
the Act and these Regulations; and
(b) in the case of work specified in Schedule 1 performed by an
apprentice or trainee with a specified amount of experience
that requires general supervision (level 2) – the holder of an
electrical work licence:
(i) visits the apprentice or trainee at the place where the
electrical work is being carried out, at least once a day;
and
(ii) before the electrical work commences, provides
instruction and direction, as required, regarding the
electrical work; and
-- 45 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 5 Apprentices and trainees
Electrical Safety Regulations 2024 36
(iii) while the electrical work is being performed:
(A) is readily available or contactable to provide advice
and guidance; and
(B) checks, as appropriate, that the work complies with
the Act and these Regulations; and
(iv) when the electrical work is complete, checks and tests
the work to ensure the work is safe and complies with
the Act and these Regulations.
52 Apprentices
For section 62(4)(b) of the Act, prescribed work is electrical work
that is:
(a) performed on electrical equipment, an electrical installation or
an electric line that is physically isolated; and
(b) specified in Schedule 1 as requiring general supervision; and
(c) performed while the apprentice is under the general
supervision of the holder of an electrical work licence who is
authorised under the Act and these Regulations to do that
electrical work and competent to ensure electrical work is safe
from electrical risk.
53 Trainees
(1) For section 63(4)(b) of the Act, prescribed work is electrical work
that is:
(a) performed as formal training including:
(i) practical work experience facilitated by a supporting
employer under the supervision of the holder of an
electrical work licence; or
(ii) course work facilitated by a registered training
organisation; and
(b) performed on electrical equipment that is physically isolated;
and
(c) specified in Schedule 1 as requiring general supervision; and
-- 46 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 5 Apprentices and trainees
Electrical Safety Regulations 2024 37
(d) performed while the trainee is under the general supervision of
the holder of an electrical work licence who is authorised
under the Act and these Regulations to do that electrical work
and competent to ensure electrical work is safe from electrical
risk.
(2) To be eligible to be issued a trainee permit, an applicant must
demonstrate the need to perform electrical work as:
(a) practical work experience facilitated by a supporting employer
under the supervision of the holder of an electrical work
licence; or
(b) course work facilitated by a registered training organisation.
54 Term of trainee permit
A trainee permit may be issued, renewed or reinstated for a
maximum of 1 year.
55 Trainee permit not transferable
A trainee permit is not transferable by the trainee.
56 Duty of person conducting business or undertaking in relation
to supervision
(1) A person conducting a business or undertaking that performs
electrical work involving an apprentice or trainee must ensure all
electrical work performed by the apprentice or trainee is supervised
in accordance with this regulation.
(2) A person conducting a business or undertaking that performs
electrical work involving an apprentice or trainee must ensure, as
far as is practicable, that the electrical work of the apprentice or
trainee is supervised by the holder of an electrical work licence
who:
(a) is authorised by their licence to carry out the work without
supervision; and
(b) has successfully completed a course of training approved by
the Electrical Safety Regulator in the supervision of
apprentices and trainees; and
(c) has appropriate technical knowledge of and experience in
performing the electrical work.
-- 47 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 5 Apprentices and trainees
Electrical Safety Regulations 2024 38
(3) For subregulation (2), the person conducting the business or
undertaking must have regard to the following:
(a) the type of electrical work to be performed by the apprentice
or trainee, especially whether the work will be performed on or
near a part of an electrical installation that is connected to a
supply of electricity;
(b) the location and general circumstances in which the electrical
work is to be performed;
(c) the level of competence of the apprentice or trainee;
(d) the ability of the person who is to provide the supervision to
provide appropriate supervision.
(4) For subregulation (2), the person conducting the business or
undertaking must ensure, as far as is practicable, that:
(a) the person supervising the apprentice or trainee:
(i) understands their responsibilities under regulation 57;
and
(ii) complies with regulation 57; and
(b) the apprentice or trainee does not carry out electrical work on
or near an energised part of an electrical installation; and
(c) the apprentice or trainee knows who is supervising them.
57 Duty of holder of electrical work licence supervising
(1) The holder of an electrical work licence supervising an apprentice
or a trainee must determine the appropriate level of supervision in
accordance with Schedule 1 for the various tasks to be performed
by the apprentice or trainee, having regard to the following:
(a) the type of electrical work to be performed by the apprentice
or trainee, particularly whether the work will be performed on
or near a part of an electrical installation that is connected to a
supply of electricity;
(b) the location and general circumstances in which the electrical
work is to be performed;
(c) the level of experience and competence of the apprentice or
trainee.
-- 48 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 5 Apprentices and trainees
Electrical Safety Regulations 2024 39
(2) The holder of an electrical work licence supervising the apprentice
or trainee must provide appropriate supervision of the electrical
work of the apprentice or trainee in accordance with
subregulation (3).
(3) The holder of an electrical work licence supervising the apprentice
or trainee must ensure, as far as is practicable, that:
(a) the holder does not supervise the electrical work:
(i) in the case of direct supervision – of more than
one apprentice or trainee at a time; and
(ii) in the case of general supervision (level 1) – of more
than 3 apprentices or trainees at a time; and
(iii) in the case of general supervision (level 2) – of more
than 5 apprentices or trainees at a time; and
(b) the apprentice or trainee does not carry out electrical work on
or near an energised part of an electrical installation; and
(c) the apprentice or trainee knows who is supervising them; and
(d) the apprentice or trainee knows the level of supervision that
applies to the performance of their electrical work; and
(e) the apprentice or trainee understands that they are not to take
instructions in relation to electrical work from anyone other
than the holder of an electrical work licence supervising them.
58 Offence of failing to supervise apprentice or trainee
(1) A person commits an offence if the person contravenes
regulation 56 or 57.
Maximum penalty: 50 penalty units.
(2) An offence against subregulation (1) is an offence of strict liability.
59 Refusal of work
An apprentice or trainee may refuse to perform any electrical work
if, having regard to the supervision under which it is being
performed, the apprentice or trainee reasonably considers that:
(a) the apprentice or trainee is not competent to carry out the
electrical work; or
(b) performing the electrical work would create an electrical risk.
-- 49 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 6 Other matters related to licences and trainee permits
Electrical Safety Regulations 2024 40
Division 6 Other matters related to licences and trainee
permits
60 Other eligibility criteria for electrical work licence
(1) For section 55(2) of the Act, other prescribed eligibility criteria are
set out in this regulation.
(2) The applicant must be adequately able to understand, and read and
write in, the English language without the aid of an interpreter.
(3) The applicant must be trained in, and be competent to carry out,
resuscitation on an individual who has stopped breathing or is
unconscious because of electric shock.
(4) If the Electrical Safety Regulator approves a training course in the
supervision of apprentices and trainees, the applicant must
successfully complete that training course.
(5) For an application for a licence with any electrical line work
endorsement, the applicant must be trained in, and be competent to
carry out, resuscitation and low voltage rescue at a pole top or
transmission tower on an individual who has stopped breathing or is
unconscious because of electric shock.
(6) The applicant must satisfy the Electrical Safety Regulator that the
applicant is suitable to hold the licence if, at any time, the applicant:
(a) was subject to disciplinary action under a law regulating the
activities of electrical workers; or
(b) failed to perform a duty under a law about electrical work.
(7) If required by the Electrical Safety Regulator, the applicant must
provide information to satisfy the Electrical Safety Regulator that
the applicant is a fit and proper person to hold an electrical work
licence.
61 Colour identification test statement
For sections 55(3)(b) and 62(2)(b) of the Act, prescribed information
includes a statement of the results the applicant obtained in a
colour identification test.
-- 50 of 149 --
Part 3 Licences, apprenticeships and trainees
Division 6 Other matters related to licences and trainee permits
Electrical Safety Regulations 2024 41
62 Further assessment
For section 57(1)(a) of the Act, an assessment of the applicant's
competency to perform electrical work may include the following:
(a) one or more examinations or tests conducted by:
(i) the Electrical Safety Regulator; or
(ii) an examiner approved by the Electrical Safety
Regulator; or
(iii) a registered training organisation;
(b) an assessment of the applicant's performance during a course
of instruction.
63 Producing licence, trainee permit and other documents
(1) A person supervising or performing electrical work must, on the
request of an inspector or an authorised officer performing a
function or exercising a power under the Electricity Reform
Act 2000:
(a) state whether the person is licensed to supervise or perform
the electrical work; and
(b) produce, as soon as reasonably practicable, the person's
licence or trainee permit and any other document required to
be kept by the person under the Act.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
64 Return of licence or trainee permit
(1) The Electrical Safety Regulator may, by written notice, require the
holder of a licence or trainee permit, or another person who has
control of the licence or permit, to return the licence or permit to the
Electrical Safety Regulator if the licence or permit:
(a) is cancelled or suspended; or
(b) has expired; or
(c) must be varied.
-- 51 of 149 --
Part 4 General electrical safety
Division 1 Electrical equipment and electrical installations
Electrical Safety Regulations 2024 42
(2) A person who receives a notice under subregulation (1) must return
the licence or trainee permit as soon as practicable.
(3) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 20 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
65 Replacement of licence or trainee permit
The Electrical Safety Regulator may issue a replacement for a
licence or trainee permit that is lost, damaged or destroyed.
66 Renewal of licence or trainee permit
(1) The eligibility criteria applicable to an application for a licence or
trainee permit apply to an application to renew the licence or permit.
(2) A licence or trainee permit must not be renewed if the person
applying to renew the licence or permit would not be eligible for the
licence or permit.
Part 4 General electrical safety
Division 1 Electrical equipment and electrical installations
67 Unsafe electrical equipment
(1) A person conducting a business or undertaking at a workplace must
do all that is reasonably practicable to ensure any unsafe electrical
equipment at the workplace:
(a) is disconnected or isolated from its electricity supply; and
(b) once disconnected or isolated:
(i) is not reconnected until it is repaired or tested and found
to be safe; or
(ii) is replaced or permanently removed from use.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
-- 52 of 149 --
Part 4 General electrical safety
Division 1 Electrical equipment and electrical installations
Electrical Safety Regulations 2024 43
68 Cord extension sets and flexible cables
(1) A person conducting a business or undertaking at a workplace must
do all that is reasonably practicable to ensure any cord extension
set or flexible cable at the workplace is:
(a) located where it is not likely to suffer damage, including
damage by liquid; and
(b) protected against damage.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
69 Safety switches
(1) A person conducting a business or undertaking at a workplace must
not use, or allow to be used, a safety switch unless it complies with
AS/NZS 3760 (In-service safety inspection and testing of electrical
equipment and RCDs) when tested.
(2) A person conducting a business or undertaking at a workplace must
ensure each safety switch, other than a portable safety switch, at
the workplace is:
(a) tested by a competent person in accordance with
AS/NZS 3760 immediately after it is connected; and
(b) tested at the intervals stated in AS/NZS 3760 in accordance
with that standard.
(3) A person conducting a business or undertaking at a workplace must
ensure each portable safety switch the person has at the workplace
is:
(a) tested by pushing the test button on the safety switch
immediately after it is connected; and
(b) tested at the intervals stated in AS/NZS 3760 in accordance
with that standard.
(4) If a safety switch is not working properly, the person conducting the
business or undertaking must ensure:
(a) a durable tag is immediately attached to the safety switch that
warns people not to use the safety switch; and
-- 53 of 149 --
Part 4 General electrical safety
Division 1 Electrical equipment and electrical installations
Electrical Safety Regulations 2024 44
(b) the safety switch is immediately withdrawn from use.
(5) A person commits an offence if the person contravenes
subregulation (1), (2), (3) or (4).
Maximum penalty: 15 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
70 Electrical equipment in hostile environment
(1) A person conducting a business or undertaking at a workplace must
do all that is reasonably practicable to ensure electrical equipment
at the workplace is regularly inspected and tested by a competent
person if the electrical equipment is:
(a) supplied with electricity through an electrical socket outlet; and
(b) used in a hostile environment.
(2) The person conducting the business or undertaking must do all that
is reasonably practicable to ensure electrical equipment that is new
and unused at the workplace is inspected for obvious damage
before it is used.
(3) The person conducting the business or undertaking must do all that
is reasonably practicable to ensure a record of any testing
performed under subregulation (1) is kept in accordance with
subregulation (4) until the electrical equipment is:
(a) next tested; or
(b) permanently removed from the workplace or disposed of.
(4) The record of testing must specify the following:
(a) the name of the person who performed the testing;
(b) the date of the testing;
(c) the outcome of the testing;
(d) the date on which subsequent testing must be performed.
(5) The record in subregulation (4) may be in the form of a tag attached
to the electrical equipment tested.
(6) A person commits an offence if the person contravenes
subregulation (1), (2) or (3).
Maximum penalty: 50 penalty units.
-- 54 of 149 --
Part 4 General electrical safety
Division 2 Electrical work on energised electrical equipment
Electrical Safety Regulations 2024 45
(7) An offence against subregulation (6) is an offence of strict liability.
71 Untested electrical equipment in hostile environment
(1) A person conducting a business or undertaking at a workplace must
ensure, so far as is reasonably practicable, that electrical
equipment is not used in a hostile environment if the equipment is
not inspected and tested under regulation 70.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
Division 2 Electrical work on energised electrical equipment
72 Application of Division
(1) Subject to subregulation (2), this Division applies to a person
conducting a business or undertaking that performs electrical work
on electrical equipment.
(2) This Division does not apply in relation to electrical work performed
by or on behalf of a distribution entity on electrical equipment,
including a powerline controlled or operated by the entity to
transform, transmit or supply electricity.
73 Testing to determine whether equipment is energised
(1) Before electrical work is performed on electrical equipment, the
person must do all that is reasonably practicable to ensure the
electrical equipment is tested by a competent person to determine
whether or not it is energised.
(2) The person must do all that is reasonably practicable to ensure:
(a) each exposed part is treated as energised until it is isolated
and determined not to be energised; and
(b) each high-voltage exposed part is earthed after being
de-energised.
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
-- 55 of 149 --
Part 4 General electrical safety
Division 2 Electrical work on energised electrical equipment
Electrical Safety Regulations 2024 46
74 Prohibition of electrical work on energised electrical
equipment
(1) The person must do all that is reasonably practicable to ensure the
electrical work is not performed while the electrical equipment is
energised unless:
(a) it is necessary for the purposes of health or safety that the
electrical work be performed while the equipment is energised;
or
(b) it is necessary for the equipment to be energised for the work
to be performed properly; or
(c) it is necessary for the purposes of testing the equipment under
regulation 73; or
(d) there is no reasonable alternative means of performing the
work.
Examples for subregulation (1)(a)
1 Some life-saving equipment must remain energised and operating while
electrical work is performed.
2 Traffic lights may need to remain energised and operating while electrical
work is performed.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
75 Preventing inadvertent energising
(1) While electrical equipment is not energised, the person must do all
that is reasonably practicable to ensure the equipment is not
inadvertently energised while the work is being performed.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
-- 56 of 149 --
Part 4 General electrical safety
Division 2 Electrical work on energised electrical equipment
Electrical Safety Regulations 2024 47
76 Preliminary steps
(1) Before electrical work is performed, other than electric line work,
the person must do all that is reasonably practicable to ensure:
(a) the person consults with the person with management or
control of the workplace; and
(b) a risk assessment is conducted in relation to the proposed
electrical work and records the results of the assessment; and
(c) the area where the electrical work is to be performed is clear
of obstructions to allow easy access and exit by the worker
who will perform the electrical work; and
(d) the point at which the electrical equipment can be
disconnected or isolated from its electricity supply is:
(i) clearly marked or labelled; and
(ii) clear of obstructions so as to allow easy access and exit
by the worker who will perform the electrical work; and
(iii) capable of being used quickly.
(2) Electrical work on energised electrical equipment is exempt from
subregulation (1)(d) if:
(a) the work is performed on the supply side of the main switch on
the main switchboard for the equipment; and
(b) the point at which the equipment can be disconnected from its
electricity supply is not reasonably accessible from the
workplace.
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
77 Performing electrical work on energised electrical equipment
(1) If the electrical equipment is energised, the person must do all that
is reasonably practicable to ensure the work is performed:
(a) by a competent person who has tools, testing equipment and
personal protective equipment that:
(i) are suitable for the work; and
-- 57 of 149 --
Part 4 General electrical safety
Division 2 Electrical work on energised electrical equipment
Electrical Safety Regulations 2024 48
(ii) are appropriately rated for the work; and
(iii) were properly tested; and
(iv) are maintained in good working order; and
(b) in accordance with a safe work method statement prepared in
advance; and
(c) subject to subregulation (4), with a safety observer present.
(2) For subregulation (1)(a), the person must do all that is reasonably
practicable to ensure the worker who carries out the electrical work
uses the tools, testing equipment and personal protective
equipment properly.
(3) For subregulation (1)(c) the safety observer must:
(a) be competent to implement control measures in an
emergency; and
(b) be competent to rescue and resuscitate the worker who is
performing the work, if necessary; and
(c) have been assessed in the previous 12 months as competent
to rescue and resuscitate a person.
(4) A safety observer is not required under subregulation (1)(c) if:
(a) the electrical work consists only of testing; and
(b) a risk assessment is conducted under regulation 76(1)(b) that
shows that there is no serious risk associated with the
proposed work.
Example for subregulation (4)(a)
The testing of the polarity of an installed outlet.
(5) A person commits an offence if the person contravenes
subregulation (1), (2) or (3).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
(7) In this regulation:
safety observer means a person who observes the safe
performance of electrical work on energised electrical equipment.
-- 58 of 149 --
Part 4 General electrical safety
Division 3 Safety switches
Electrical Safety Regulations 2024 49
78 Authorised access only
(1) If electrical equipment is energised, the person must do all that is
reasonably practicable to ensure only persons authorised by the
person enter the immediate area in which electrical work is being
performed.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
79 Contact with equipment being worked on
(1) If electrical equipment is energised, any person performing
electrical work must do all that is reasonably practicable to ensure
all persons are prevented from creating an electrical risk by
inadvertently making contact with an exposed energised
component of the equipment while the electrical work is being
performed.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
Division 3 Safety switches
80 Use of socket outlets in hostile environment
(1) This regulation applies to the following:
(a) electrical equipment used in an environment in which the
normal use of electrical equipment exposes the equipment to
a hostile environment;
(b) electrical equipment moved between different locations in
circumstances where damage to the equipment or to a flexible
electricity supply cord is reasonably likely;
(c) electrical equipment frequently moved during its normal use;
-- 59 of 149 --
Part 4 General electrical safety
Division 3 Safety switches
Electrical Safety Regulations 2024 50
(d) electrical equipment forming part of, or is used in connection
with, an amusement device.
Examples for subregulation (1)(a)
Exposure to moisture, heat, vibration, mechanical damage, corrosive chemicals
or dust.
(2) A person conducting a business or undertaking at a workplace must
do all that is reasonably practicable to ensure any electrical risk
associated with the supply of electricity to the electrical equipment
through a socket outlet at the workplace is minimised by the use of
an appropriate safety switch.
(3) For subregulation (2), the safety switch must have a tripping current
that does not exceed 30 mA if the electricity supplied to the
equipment through a socket outlet does not exceed 20 A.
(4) Electrical equipment is exempt from subregulation (2) if the supply
of electricity to the electrical equipment:
(a) does not exceed 50 volts AC; or
(b) is direct current; or
(c) is provided through an isolating transformer that provides at
least an equivalent level of protection to a safety switch; or
(d) is provided from a non-earthed socket outlet supplied by an
isolated winding portable generator that provides at least an
equivalent level of protection to a safety switch.
(5) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
81 Testing of safety switches
(1) A person with management or control of a workplace must do all
that is reasonably practicable to ensure safety switches used at the
workplace are tested regularly by a competent person and are
operating effectively in accordance with AS/NZS 3760 (In-service
safety inspection and testing of electrical equipment and RCDs).
-- 60 of 149 --
Part 4 General electrical safety
Division 4 Consumer electrical equipment
Electrical Safety Regulations 2024 51
(2) The person must keep a record of all testing of safety switches,
other than any testing conducted daily, until the earlier of the
following:
(a) the day the device is next tested;
(b) the day the device is permanently removed from use.
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
Division 4 Consumer electrical equipment
82 Approved consumer electrical equipment
For section 70(1)(c) of the Act, the following laws are prescribed:
(a) Electricity Act 1945 (WA);
(b) Electrical Safety Act 1998 (Vic);
(c) Electrical Safety Act 2002 (Qld);
(d) Electricity Safety Act 2022 (Tas);
(e) Energy Products (Safety and Efficiency) Act 2000 (SA);
(f) Electricity Safety Act 1971 (ACT);
(g) Electricity Act 1992 (NZ);
(h) Gas and Electricity (Consumer Safety) Act 2017 (NSW);
Note for regulation 82
Section 52 of the Interpretation Act 1978 provides that a reference to a law in
Australia includes any subsequent or successor law corresponding to the law
mentioned in this regulation.
-- 61 of 149 --
Part 5 Conduct of electrical work
Division 2 Wiring Rules
Electrical Safety Regulations 2024 52
Part 5 Conduct of electrical work
Division 1 Application of Part
83 Application of Part
This Part does not apply in relation to electrical work performed by
or on behalf of a distribution entity on electrical equipment,
including a powerline controlled or operated by the entity to
transform, transmit or supply electricity.
Division 2 Wiring Rules
84 Exemption for streetlights
The Wiring Rules do not apply in relation to streetlights.
85 Compliance with Wiring Rules
(1) A person performing electrical work must perform the work in
accordance with the Wiring Rules.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
86 Examination and testing
(1) A person who performs electrical work on an electrical installation
must examine and test the installation to determine if it complies
with the requirements of:
(a) the Wiring Rules and any standard applicable by or under the
Wiring Rules; and
(b) any other requirements specified by the operator of the
transmission or distribution network to which the installation is
or will be connected.
(2) The person must perform the examination and testing under
subregulation (1) in accordance with the following:
(a) the Wiring Rules and any standard applicable by or under the
Wiring Rules;
-- 62 of 149 --
Part 5 Conduct of electrical work
Division 2 Wiring Rules
Electrical Safety Regulations 2024 53
(b) any other requirements specified by the operator of the
transmission or distribution network to which the installation is,
or will be, connected.
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
87 Compliance with Wiring Rules
(1) The person in control of an electrical installation must do all that is
reasonably practicable to ensure any structure supporting an
electric line or item of electrical equipment forming part of the
electrical installation complies with:
(a) the Wiring Rules; and
(b) any direction the Electrical Safety Regulator gives for ensuring
the electrical safety of the installation; and
(c) any other requirement specified by the operator of the
transmission or distribution network to which the installation is,
or will be, connected.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
(4) If there is any inconsistency between the Wiring Rules and a
direction of the Electrical Safety Regulator, the direction prevails to
the extent of the inconsistency.
88 Compliance with current standards
A person performing electrical work on electrical equipment, an
electrical installation or electrical infrastructure must ensure the
work complies with the Wiring Rules.
Note for regulation 88
The Wiring Rules require compliance with the standard that is applicable at the
time of the electrical work.
-- 63 of 149 --
Part 5 Conduct of electrical work
Division 2 Wiring Rules
Electrical Safety Regulations 2024 54
89 Suitability of testing instruments
If tests are required to be performed on electricity infrastructure, an
electrical installation or other equipment under the Act or these
Regulations:
(a) the testing instruments used must be designed for and
capable of correctly performing the required tests; and
(b) each testing instrument must be tested and calibrated, in
accordance with the manufacturer's specifications and site
requirements, to ensure it is in proper working order; and
(c) the records of tests performed on testing instruments must be
kept for at least 2 years.
90 Duty to comply with Wiring Rules
(1) A person who performs electrical work on an electrical installation
must do all that is reasonably practicable to ensure the electrical
installation, to the extent it is affected by the electrical work,
complies with:
(a) the Wiring Rules; and
(b) in the case of an electrical installation used for construction
work – the Wiring Rules and AS/NZS 3012 (Electrical
installations – Construction and demolition sites); and
(c) any other requirement specified by the operator of the
transmission or distribution network to which the installation is,
or will be, connected.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
91 Duty of person conducting business or undertaking
(1) A person conducting a business or undertaking that performs
electrical work on an electrical installation must do all that is
reasonably practicable to ensure the electrical installation, to the
extent it is affected by the electrical work, complies with:
(a) the Wiring Rules; and
-- 64 of 149 --
Part 5 Conduct of electrical work
Division 3 General electrical work
Electrical Safety Regulations 2024 55
(b) in the case of an electrical installation used for construction
work – the Wiring Rules and AS/NZS 3012 (Electrical
installations – Construction and demolition sites); and
(c) any other requirement specified by the operator of the
transmission or distribution network to which the installation is,
or will be, connected.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
Division 3 General electrical work
92 Electrical work involving pools, water features and water tubs
(1) Subject to subregulation (2), this regulation applies to electrical
work on any electrical equipment that:
(a) is in, or surrounds the water container of, a swimming pool,
paddling pool, spa facility, water feature or water tub; and
(b) is either:
(i) used for controlling, generating, supplying, transforming
or transmitting electricity at extra low voltage; or
(ii) operated by electricity at extra low voltage.
(2) The following work is exempt from subregulation (1):
(a) the plugging in of a pre-packaged water feature; or
(b) replacing a component part of the equipment if the equipment
is designed so that the component may be readily and safely
replaced by a person without electrical knowledge or skill.
(3) A person must not perform electrical work on the equipment unless:
(a) the person is a licensed electrical worker; and
(b) the work on the equipment is authorised under the person's
licence; and
(c) the equipment complies with the Wiring Rules, to the extent
the equipment is affected by the work.
-- 65 of 149 --
Part 5 Conduct of electrical work
Division 3 General electrical work
Electrical Safety Regulations 2024 56
(4) A person conducting a business or undertaking that performs work
on the equipment must do all that is reasonably practicable to
ensure its workers comply with subregulation (3).
(5) A person commits an offence if the person contravenes
subregulation (3) or (4).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
93 Duty of person in control to fix defect
(1) If an inspector or distribution entity gives written notice to the
person in control of electrical equipment of any defect affecting the
electrical safety of the electrical equipment, the person in control
must ensure the defect is fixed.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
94 Earthing
(1) A person in control of a low voltage electrical installation that
receives electricity distributed by a distribution entity must do all
that is reasonably practicable to ensure the earthing for the
installation complies with the requirements for an earthing and
protection system that applies to the distribution entity under this
regulation.
(2) The works of a distribution entity must incorporate an earthing and
protection system, in accordance with the Wiring Rules and any
requirement specified by the operator of the transmission or
distribution network to which the installation is, or will be,
connected, that is capable of ensuring the following:
(a) reliable passage of fault current;
(b) reliable passage of single wire earth return load currents to
ground or source;
(c) reliable operation of circuit protection devices;
(d) safe step, touch and transfer potentials for all electrical
equipment;
-- 66 of 149 --
Part 5 Conduct of electrical work
Division 3 General electrical work
Electrical Safety Regulations 2024 57
(e) appropriate coordination with the earthing and protection
systems of any other distribution entity;
(f) protection against likely mechanical damage, inadvertent
interference and chemical deterioration;
(g) mechanical stability and integrity of connections.
(3) Without limiting subregulation (2), the earthing and protection
system referred to in that subregulation must comply with the
following requirements:
(a) if the multiple earth neutral system of earthing is used – the
neutral conductor of the system must be effectively earthed;
(b) each non-current carrying exposed conductive part of an
electric line or generating plant must be effectively earthed;
(c) each non-current carrying exposed conductive part of a
substation must be effectively earthed;
(d) the system must be tested as soon as practicable after its
installation to prove its effectiveness;
(e) any high voltage electric line must be protected by a suitable
fuse, circuit breaker or equivalent device.
(4) Earthing is not required under subregulation (3)(b) or (c) if the
distribution entity considers that earthing is not appropriate for
safety reasons in accordance with a recognised industry practice.
(5) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
95 Duty to preserve insulation of electric line
(1) The person in control of an electrical installation must maintain, to a
reasonable extent, the integrity of the insulation of any electric line,
or connection to an electric line, that is part of the electrical
installation:
(a) if it is an overhead electric line – near the point of attachment
of the electric line to any structure; and
-- 67 of 149 --
Part 5 Conduct of electrical work
Division 4 Certificates of compliance
Electrical Safety Regulations 2024 58
(b) whether or not it is an overhead electric line – near roofs or
structures where it is likely that any person could come into
contact with the insulated wires or connectors of the line.
Examples for subregulation (1)(b)
A painter or plumber.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
96 Duty to ensure safety of disconnected overhead electric line
(1) The person in control of an overhead electric line must do all that is
reasonably practicable to ensure any line that is permanently
disconnected from its electricity supply is:
(a) dismantled as soon as practicable after disconnection; or
(b) maintained to be electrically safe and mechanically safe.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
Division 4 Certificates of compliance
97 Contents of certificates of compliance
For section 41(2)(b) of the Act, the following information is
prescribed:
(a) the name and contact details of the person for whom the work
was conducted or performed;
(b) the details of the electrical work performed;
(c) the day the electrical work was performed;
(d) the name and licence number of the person completing the
certificate;
(e) if applicable – the number of the electrical contractor licence
under which the electrical work was performed;
-- 68 of 149 --
Part 5 Conduct of electrical work
Division 5 Misrepresentation
Electrical Safety Regulations 2024 59
(f) any defects or non-compliance noticed that were not rectified;
(g) any other information required in the approved form.
Division 5 Misrepresentation
98 Misrepresentations about electrical work
(1) A person who is not authorised to do so under a licence must not
represent that the person, or any other person who is not
authorised to do so under a licence, may lawfully:
(a) connect to a source of electricity an item of electrical
equipment that may only lawfully be connected to a source of
electricity by the holder of an electrical work licence; or
(b) do electrical work that may only be performed by the holder of
an electrical work licence.
(2) A person conducting a business or undertaking must do all that is
reasonably practicable to ensure the person's workers do not
contravene subregulation (1).
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
99 Misrepresentation about contract to perform electrical work
(1) A person must not represent that the person, or any other person,
who is not authorised to do so under a licence, may contract to
perform electrical work that may only lawfully be performed by the
holder of an electrical contractor licence.
(2) A person conducting a business or undertaking must do all that is
reasonably practicable to ensure the person's workers do not
contravene subregulation (1).
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 100 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
-- 69 of 149 --
Part 5 Conduct of electrical work
Division 6 Other matters
Electrical Safety Regulations 2024 60
100 Misrepresentation about licence
(1) A person must not represent that the person, or any other person,
has a licence or is authorised to do work under a licence if they do
not have the licence or are not authorised to do that work under a
licence.
(2) A person conducting a business or undertaking must do all that is
reasonably practicable to ensure the person's workers do not
contravene subregulation (1).
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
101 Other misrepresentation
(1) A person must not represent that the person or any other person is:
(a) endorsed, approved or authorised by the Electrical Safety
Regulator to undertake electrical work other than as a
licensee, apprentice or trainee; or
(b) recommended by the Electrical Safety Regulator or any
Agency.
(2) A person conducting a business or undertaking must do all that is
reasonably practicable to ensure the person's workers do not
contravene subregulation (1).
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
Division 6 Other matters
102 Electrical equipment with serious defect
(1) An electrical worker must not connect electrical equipment to a
source of electricity if the electrical equipment has a defect that
presents an electrical risk.
-- 70 of 149 --
Part 6 Conduct of other work
Division 1 Construction work
Electrical Safety Regulations 2024 61
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
103 Rescue and resuscitation training
(1) Any person required to perform, or help in performing, electrical
work must be suitably trained in rescue and resuscitation in
accordance with standard practices in the electricity industry.
(2) A person conducting a business or undertaking that performs
electrical work must ensure any electrical worker who performs that
work is competent in rescue and resuscitation in accordance with
standard practices in the electricity industry.
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
(5) It is a defence to a prosecution for an offence against
subregulation (3) if the electrical worker's licence prohibits the
worker from performing work that requires competency in rescue
and resuscitation.
Part 6 Conduct of other work
Division 1 Construction work
104 Standards for electrical equipment for construction
(1) Subregulation (2) applies to:
(a) a person conducting a business or undertaking at a workplace
where construction work is performed; and
(b) a person conducting a business or undertaking that performs
construction work.
(2) Subject to these Regulations, the person must do all that is
reasonably practicable to ensure all electrical equipment used to
perform construction work complies with the requirements of the
Wiring Rules and AS/NZS 3012 (Electrical installations –
Construction and demolition sites).
-- 71 of 149 --
Part 6 Conduct of other work
Division 1 Construction work
Electrical Safety Regulations 2024 62
(3) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
105 Electrical equipment for construction
(1) A person conducting a business or undertaking that performs
construction work must do all that is reasonably practicable to
ensure electrical equipment used for the performance of the work
complies with AS/NZS 3012 (Electrical installations – Construction
and demolition sites).
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
106 Construction wiring
(1) A person with management or control of a workplace where
construction work is being performed must do all that is reasonably
practicable to ensure all construction wiring at the workplace
complies with the requirements of the Wiring Rules and any other
applicable requirements in AS/NZS 3012 (Electrical installations –
Construction and demolition sites).
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
(4) In this regulation:
construction wiring means temporary electrical wiring by which
electricity is supplied by an electricity entity for use in and during
construction work.
-- 72 of 149 --
Part 6 Conduct of other work
Division 2 Manufacturing work
Electrical Safety Regulations 2024 63
107 Defence
It is a defence to a prosecution for an offence against a provision of
this Division for contravening a requirement of this Division if the
defendant complied with a provision in AS/NZS 3012 (Electrical
installations – Construction and demolition sites) that deals with the
same matter as the requirement.
Division 2 Manufacturing work
108 Double adaptors and piggyback plugs prohibited
(1) A person conducting a business or undertaking that performs
manufacturing work must not use a double adaptor or piggyback
plug.
(2) A person conducting a business or undertaking that performs
manufacturing work must do all that is reasonably practicable to
ensure workers performing the work do not use a double adaptor or
piggyback plug.
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
109 Safety switches
(1) A person conducting a business or undertaking that performs
manufacturing work must not use, or allow to be used, a safety
switch unless it complies with AS/NZS 3760 (In-service safety
inspection and testing of electrical equipment) when tested.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 15 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
110 Specified electrical equipment
(1) This regulation applies to the following electrical equipment:
(a) a cord extension set with a current rating of not more than
20 A;
-- 73 of 149 --
Part 6 Conduct of other work
Division 2 Manufacturing work
Electrical Safety Regulations 2024 64
(b) an electrical portable outlet device with a current rating of not
more than 20 A;
(c) electrical equipment, other than a portable safety switch, that:
(i) has a current rating of not more than 20 A; and
(ii) is connected by a flexible cord and plug to low voltage
supply; and
(iii) is moved during its normal use for the purpose of its use.
Examples for subregulation (1)(b) and (c)
1 A handheld grinder plugged into a socket-outlet.
2 A handheld electric drill plugged into a socket-outlet that is used for drilling
holes in steelwork in a light engineering workshop.
(2) Subject to subregulation (3), a person conducting a business or
undertaking that performs manufacturing work must do all that is
reasonably practicable to ensure the electrical equipment specified
in subregulation (1) is not used to perform the work unless the
equipment:
(a) is inspected and tested by a competent person:
(i) in the case of equipment that is double insulated – at
least once every year; or
(ii) otherwise – at least once every 6 months; and
(b) is connected to:
(i) in the case of a socket-outlet in a permanent workplace
under the control of the person conducting the business
or undertaking – a type 1 safety switch or type 2 safety
switch that is not portable; or
(ii) otherwise – a type 1 safety switch or a type 2 safety
switch.
Example for subregulation (2)(b)(ii)
The premises of a customer visited by the worker.
(3) Subregulation (2)(b) does not apply to a socket-outlet that is:
(a) more than 2.3 m above the floor; and
(b) provided for the purpose of supplying electricity to a luminaire
or to electrical equipment with a power rating of not more than
150 W.
-- 74 of 149 --
Part 6 Conduct of other work
Division 2 Manufacturing work
Electrical Safety Regulations 2024 65
(4) If after inspecting and testing the electrical equipment under
subregulation (2)(a), a competent person decides the equipment is
safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure the competent
person immediately attaches a durable tag to the equipment that
shows the minimum information for the equipment.
(5) If after inspecting and testing the electrical equipment under
subregulation (2)(a), a competent person decides the equipment is
not safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure:
(a) the competent person immediately attaches a durable tag to
the equipment that warns people not to use the equipment;
and
(b) the equipment is immediately withdrawn from use.
(6) A person conducting a business or undertaking that performs
manufacturing work must do all that is reasonably practicable to
ensure a tag is not attached to specified electrical equipment under
subregulation (4) unless:
(a) the equipment is new; or
(b) both of the following apply to the equipment and tag
respectively:
(i) the equipment was inspected and tested by a competent
person;
(ii) the tag was attached by the competent person.
(7) A person commits an offence if the person contravenes
subregulation (2), (4), (5) or (6).
Maximum penalty: 15 penalty units.
(8) An offence against subregulation (7) is an offence of strict liability.
111 Manufacturing work – safety switch
(1) This regulation applies to a business or undertaking that performs
manufacturing work on or after 1 July 2026.
-- 75 of 149 --
Part 6 Conduct of other work
Division 3 Service work and office work
Electrical Safety Regulations 2024 66
(2) A person conducting a business or undertaking that performs
manufacturing work must have a type 1 safety switch, or type 2
safety switch, that is not portable, installed for the socket-outlet if
the socket-outlet:
(a) has a current rating of not more than 20 A; and
(b) is not more than 2.3 m above the floor.
(3) A person conducting a business or undertaking that performs
manufacturing work must ensure each safety switch, other than a
portable safety switch, at the workplace:
(a) is tested by a competent person under AS/NZS 3760
(In-service safety inspection and testing of electrical
equipment) immediately after it is connected; and
(b) is tested under, and at the intervals stated in, AS/NZS 3760.
(4) A person commits an offence if the person contravenes
subregulation (2) or (3).
Maximum penalty: 15 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
(6) A person conducting a business or undertaking is exempt from
complying with subregulations (2) and (3) if:
(a) the person is not in control of the electrical equipment for the
installation of the safety switch; and
(b) the person is unable to obtain permission from the person in
control of the electrical equipment for the installation of the
safety switch.
Division 3 Service work and office work
112 Specified electrical equipment
(1) This regulation applies to the following electrical equipment:
(a) a cord extension set with a current rating of not more than
20 A;
(b) an electrical portable outlet device with a current rating of not
more than 20 A;
-- 76 of 149 --
Part 6 Conduct of other work
Division 3 Service work and office work
Electrical Safety Regulations 2024 67
(c) electrical equipment, other than a portable safety switch, that:
(i) has a current rating of not more than 20 A; and
(ii) is connected by a flexible cord and plug to low voltage
supply; and
(iii) is moved during its normal use for the purpose of its use.
(2) A person conducting a business or undertaking that performs
service work or office work must do all that is reasonably
practicable to ensure the electrical equipment is not used unless:
(a) it is inspected and tested by a competent person:
(i) if the equipment is used only for office work – at least
once every 5 years; or
(ii) otherwise – at least once every year; or
(b) it is connected to a type 1 safety switch or a type 2 safety
switch.
Examples of electrical equipment used to perform service work, for
subregulation (2)
1 A portable vacuum cleaner used in a hotel.
2 A handheld blow dryer used in a hairdressing salon.
Example of electrical equipment used to perform office work, for subregulation (2)
A power board or extension lead used to supply power to office equipment.
(3) If after inspecting and testing the electrical equipment under
subregulation (2)(a), a competent person decides the equipment is
safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure the competent
person attaches a durable tag to the equipment that shows the
minimum information for the equipment.
(4) If after inspecting and testing the electrical equipment under
subregulation (2)(a), a competent person decides the equipment is
not safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure:
(a) the competent person immediately attaches a durable tag to
the equipment that warns people not to use the equipment;
and
-- 77 of 149 --
Part 6 Conduct of other work
Division 3 Service work and office work
Electrical Safety Regulations 2024 68
(b) the equipment is immediately withdrawn from use.
(5) The person conducting the business or undertaking must do all that
is reasonably practicable to ensure a tag is not attached to
specified electrical equipment under subregulation (3) unless:
(a) the equipment is new; or
(b) both of the following apply:
(i) the equipment was inspected and tested by a competent
person;
(ii) the tag was attached by the competent person.
(6) A person commits an offence if the person contravenes
subregulation (2), (3), (4) or (5).
Maximum penalty: 15 penalty units.
(7) An offence against subregulation (6) is an offence of strict liability.
113 Safety switches – service work and office work
(1) A person conducting a business or undertaking that performs
service work or office work must not use, or allow to be used, a
safety switch unless it complies with AS/NZS 3760 (In-service
safety inspection and testing of electrical equipment) when tested.
(2) A person conducting a business or undertaking that performs
service work or office work must ensure each safety switch, other
than a portable safety switch, at the workplace:
(a) is tested by a competent person under AS/NZS 3760
immediately after it is connected; and
(b) is tested under, and at the intervals stated in, AS/NZS 3760.
(3) A person conducting a business or undertaking that performs
service work or office work must do all that is reasonably
practicable to ensure each portable safety switch at the workplace:
(a) is tested by pushing the test button on the safety switch
immediately after it is connected; and
(b) is tested under, and at the intervals stated in, AS/NZS 3760.
-- 78 of 149 --
Part 6 Conduct of other work
Division 4 Electrical work related to amusement devices, rides and activities
Electrical Safety Regulations 2024 69
(4) If a safety switch is not working properly, the person conducting the
business or undertaking must do all that is reasonably practicable
to ensure:
(a) a durable tag is immediately attached to the safety switch that
warns people not to use the safety switch; and
(b) the safety switch is immediately withdrawn from use.
(5) A person commits an offence if the person contravenes
subregulation (1), (2), (3) or (4).
Maximum penalty: 15 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
Division 4 Electrical work related to amusement devices,
rides and activities
114 Application of Division
This Division applies to electrical work to assemble, operate or
disassemble any of the following on the site on which it is used,
intended to be used or was used:
(a) an amusement device or amusement ride;
(b) a thing used to provide amusement activities, including side
show activities, associated with:
(i) carnivals, fairs or shows; or
(ii) amusement arcades or similar places;
(c) a thing used to provide entertainment or advertising activities,
in temporary sites, associated with shows, fairs or carnivals.
Example of side show activities for paragraph (b)
Providing hamburgers or fairy floss in a side show.
115 Double adaptors and piggyback plugs prohibited
(1) A person conducting a business or undertaking that performs the
electrical work must not use a double adaptor or piggyback plug.
(2) A person conducting a business or undertaking that performs the
electrical work must do all that is reasonably practicable to ensure
workers performing work for the person do not use a double
adaptor or piggyback plug.
-- 79 of 149 --
Part 6 Conduct of other work
Division 4 Electrical work related to amusement devices, rides and activities
Electrical Safety Regulations 2024 70
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 15 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
116 Specified electrical equipment
(1) This regulation applies to the following electrical equipment:
(a) a cord extension set with a current rating of not more than
20 A;
(b) an electrical portable outlet device with a current rating of not
more than 20 A;
(c) electrical equipment, other than a portable safety switch, that:
(i) has a current rating of not more than 20 A; and
(ii) is connected by a flexible cord and plug to low voltage
supply.
(2) A person conducting a business or undertaking that performs the
electrical work must do all that is reasonably practicable to ensure
electrical equipment is not used unless:
(a) it is inspected and tested by a competent person:
(i) if the equipment is double insulated – at least once every
year; or
(ii) if the equipment is not double insulated – at least once
every 6 months; and
(b) it is connected to a type 1 safety switch or type 2 safety
switch.
(3) If after inspecting and testing the electrical equipment under
subregulation (2)(a), a competent person decides the equipment is
safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure the competent
person immediately attaches a durable tag to the equipment that
shows the minimum information for the equipment.
-- 80 of 149 --
Part 6 Conduct of other work
Division 4 Electrical work related to amusement devices, rides and activities
Electrical Safety Regulations 2024 71
(4) If after inspecting and testing the electrical equipment under
subregulation (2)(a), a competent person decides the equipment is
not safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure:
(a) the competent person immediately attaches a durable tag to
the equipment that warns people not to use the equipment;
and
(b) the equipment is immediately withdrawn from use.
(5) The person conducting the business or undertaking must do all that
is reasonably practicable to ensure a tag is not attached to
specified electrical equipment under subregulation (3) unless:
(a) the equipment is new; or
(b) both of the following apply:
(i) the equipment was inspected and tested by a competent
person;
(ii) the tag was attached by a competent person.
(6) A person commits an offence if the person contravenes
subregulation (2), (3), (4) or (5).
Maximum penalty: 50 penalty units.
(7) An offence against subregulation (6) is an offence of strict liability.
117 Amusement devices and amusement rides
(1) A person conducting a business or undertaking that performs the
electrical work must do all that is reasonably practicable to ensure
any part of an amusement device or amusement ride that is
connected to the electricity supply by a plug is not used unless:
(a) it is inspected and tested by a competent person:
(i) each time it is assembled on the site where it is intended
to be used; and
(ii) in any event – at least once every 6 months; and
(b) for a device or ride with a current rating of not more than
20 A – it is connected to a type 1 safety switch or type 2 safety
switch.
-- 81 of 149 --
Part 6 Conduct of other work
Division 4 Electrical work related to amusement devices, rides and activities
Electrical Safety Regulations 2024 72
(2) For an inspection and test under subregulation (1)(a), the
competent person must:
(a) determine the safety of earthing, insulation and connections;
and
(b) determine whether any safety switch complies with
AS/NZS 3760 (In-service safety inspection and testing of
electrical equipment) when tested; and
(c) make a visual examination to decide the safety of the items of
electrical equipment of the device or ride, including cabling,
plugs, sockets, light fittings, enclosures and motors.
(3) If after inspecting and testing the electrical equipment under
subregulation (1)(a), a competent person decides the equipment is
safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure the competent
person immediately makes a written record of:
(a) details of the test; and
(b) the minimum information for the equipment.
(4) If after inspecting and testing the electrical equipment under
subregulation (1)(a), a competent person decides the equipment is
not safe to use, the person conducting the business or undertaking
must do all that is reasonably practicable to ensure:
(a) the competent person immediately:
(i) attaches a durable, conspicuous sign to the equipment
that warns people not to use the equipment; and
(ii) makes a written record of details of the test; and
(b) the equipment is immediately withdrawn from use.
(5) The person conducting the business or undertaking must do all that
is reasonably practicable to ensure a written record of the day by
which the equipment must be reinspected and retested is not made
with the authority of the person unless the equipment was
inspected and tested by a competent person.
(6) A person commits an offence if the person contravenes
subregulation (1), (3), (4) or (5).
Maximum penalty: 15 penalty units.
(7) An offence against subregulation (6) is an offence of strict liability.
-- 82 of 149 --
Part 6 Conduct of other work
Division 4 Electrical work related to amusement devices, rides and activities
Electrical Safety Regulations 2024 73
118 Safety switches
(1) A person conducting a business or undertaking that performs
electrical work must not use, or allow to be used, a safety switch
unless it complies with AS/NZS 3760 (In-service safety inspection
and testing of electrical equipment) when tested.
(2) The person conducting a business or undertaking must do all that is
reasonably practicable to ensure each safety switch, other than a
portable safety switch, at the workplace:
(a) is tested by a competent person in accordance with
AS/NZS 3760 immediately after it is connected; and
(b) is tested in accordance with, and at the intervals stated in,
AS/NZS 3760.
(3) The person conducting a business or undertaking must do all that is
reasonably practicable to ensure each portable safety switch at the
workplace:
(a) is tested by pushing the test button on the safety switch
immediately after it is connected; and
(b) is tested in accordance with, and at the intervals stated in,
AS/NZS 3760.
(4) If a safety switch is not working properly, the person conducting a
business or undertaking must do all that is reasonably practicable
to ensure:
(a) a durable tag is immediately attached to the safety switch that
warns people not to use the safety switch; and
(b) the safety switch is immediately withdrawn from use.
(5) A person commits an offence if the person contravenes
subregulation (1), (2), (3) or (4).
Maximum penalty: 15 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
-- 83 of 149 --
Part 6 Conduct of other work
Division 5 Work in proximity to exposed conductors or electrical equipment
Electrical Safety Regulations 2024 74
Division 5 Work in proximity to exposed conductors or
electrical equipment
119 Work involving danger of direct contact with live conductors
(1) A person performing any work involving a danger of accidental
direct contact with exposed live conductors or exposed live parts of
electrical equipment must:
(a) be competent and qualified to carry out the work; and
(b) carry out the work with a competent assistant suitably trained
in the following, except where the contrary is shown by
reference to generally accepted industry practices or the
particular circumstances of the case:
(i) the work;
(ii) resuscitation;
(iii) releasing persons from live electrical apparatus;
(iv) rescuing persons from poles, structures, elevated work
platforms or confined spaces.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
120 Work in proximity to exposed conductors or electrical
equipment
(1) A person performing any work or positioning equipment in proximity
to exposed conductors or exposed parts of electrical equipment
must comply with this regulation.
(2) The work must not be performed closer than the proximity limits set
out in Schedule 2.
(3) The work must be performed by a person who:
(a) is suitably trained and qualified for such work beyond the
proximity limits set out in this regulation for that person; or
(b) is instructed in the identification of high and low voltage
conductors and the safety aspects of work near live
powerlines beyond the proximity limits.
-- 84 of 149 --
Part 6 Conduct of other work
Division 5 Work in proximity to exposed conductors or electrical equipment
Electrical Safety Regulations 2024 75
(4) Except where the contrary is shown by reference to generally
accepted industry practices or the particular circumstances of the
case, the person must carry out the work with a competent
assistant who is suitably trained:
(a) in the work; and
(b) in resuscitation; and
(c) in releasing persons from live electrical apparatus; and
(d) if appropriate – in rescuing persons from poles, structures,
elevated work platforms or confined spaces.
(5) Despite subregulation (3), electrical work may be performed closer
than the proximity limits if:
(a) suitable barriers or earthed metal shields are installed
between the person performing the work and the conductors
or electrical equipment; or
(b) the work consists only of testing equipment that is designed so
that the approach limits cannot be complied with; or
(c) the work consists of earthing the conductors or equipment and
is performed after the exposed conductors are isolated and
proved to be de-energised.
(6) When calculating proximity for this regulation:
(a) a person includes any article of clothing worn by the person,
and any conductive object the person is handling; and
(b) a person does not include any object that alone or with
another object:
(i) is an extension of the person; and
(ii) is insulated and tested to be safe for use on and near
the exposed conductor or exposed part of electrical
equipment; and
(c) a machine includes anything the machine is handling, other
than:
(i) a person; or
(ii) a handheld object a person is handling; and
(d) a vehicle or vessel includes anything the vehicle or vessel is
carrying or otherwise handling.
-- 85 of 149 --
Part 6 Conduct of other work
Division 6 High voltage electrical work
Electrical Safety Regulations 2024 76
(7) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(8) An offence against subregulation (7) is an offence of strict liability.
Division 6 High voltage electrical work
121 Performance of high voltage live line work
(1) A person must not perform high voltage live line work on electrical
equipment unless:
(a) the person and work are authorised under regulation 126(1);
and
(b) the work is performed under a high voltage live line work
management plan in accordance with regulation 122.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
122 High voltage live line work management plan
(1) A person in control of electrical equipment must prepare a high
voltage live line work management plan in accordance with this
regulation before performing high voltage live line work.
(2) The high voltage live line work management plan must include
procedures developed in accordance with each of the following
standards:
(a) AS 5804.1 (High-voltage live working – General);
(b) AS 5804.2 (High-voltage live working – Glove and barrier
work);
(c) AS 5804.3 (High-voltage live working – Stick work);
(d) AS 5804.4 (High-voltage live working – Bare hand work).
-- 86 of 149 --
Part 6 Conduct of other work
Division 6 High voltage electrical work
Electrical Safety Regulations 2024 77
(3) The high voltage live line work management plan must be
developed in conjunction with each of the following:
(a) representatives of workers who are to perform high voltage
live line work under the plan;
(b) if the high voltage live line work involves the works of an
electricity entity – the electricity entity;
(c) other persons who might reasonably be expected to have an
interest in the performance of the high voltage live line work.
(4) The high voltage live line work management plan must be approved
by:
(a) an electrical engineer who has professional expertise in the
performance of high voltage live line work; or
(b) a person with expertise that, in the opinion of the person in
control of the electrical equipment, is equivalent to the
expertise mentioned in paragraph (a).
(5) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
123 Work in proximity to exposed high voltage conductors or
electrical equipment
(1) A person performing work or positioning equipment in proximity to
exposed high voltage conductors or exposed parts of high voltage
electrical equipment must ensure the work is authorised in writing
by the operator of the electricity infrastructure or electrical
installation affected under regulation 126.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
-- 87 of 149 --
Part 6 Conduct of other work
Division 6 High voltage electrical work
Electrical Safety Regulations 2024 78
124 Direct contact with exposed high voltage electrical equipment
(1) A person must not perform work by direct contact with exposed
high voltage conductors or exposed parts of high voltage electrical
equipment unless the exposed high voltage conductors or exposed
parts of high voltage electrical equipment are:
(a) shown by testing to be isolated from all sources of electricity
supply; and
(b) earthed.
(2) If the conductor or equipment cannot be directly contacted to prove
isolation from all sources of electricity supply, it is sufficient for
compliance with subregulation (1) if:
(a) written instructions are given for the isolation of the conductor
or equipment from all sources of electricity supply; and
(b) the conductor or equipment is earthed by a lockable earthing
switch designed to be safely operated if the high voltage
conductor or equipment is not isolated from all sources of
supply.
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
125 Live high voltage line work
(1) A person must not perform work on exposed live high voltage
conductors or exposed live parts of high voltage electrical
equipment unless authorised under regulation 126(2).
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
126 Authorisations – high voltage
(1) A person in control of electrical equipment may, in writing,authorise
a person to perform high voltage live line work in relation to the
electrical equipment.
-- 88 of 149 --
Part 6 Conduct of other work
Division 7 Work in roof spaces
Electrical Safety Regulations 2024 79
(2) An operator of electricity infrastructure or an electrical installation
may, in writing, authorise a person to perform electrical work on
exposed live high voltage conductors or exposed live parts of high
voltage electrical equipment.
(3) An authorisation may only be issued if the person issuing it is
satisfied that the person to be authorised:
(a) successfully completed a course of training provided by a
training provider approved by the Electrical Safety Regulator;
and
(b) is assessed by the training provider as competent to perform
work on exposed live high voltage conductors or exposed live
parts of high voltage electrical equipment.
(4) The authorisation must state the voltage of the equipment or
powerlines on which the work is performed.
127 Regular assessment
(1) A person who authorises a person under regulation 126(1) or (2) to
perform high voltage live line work on more than one occasion must
do all that is reasonably practicable to ensure the person is
regularly assessed in accordance with that regulation while
authorised.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
Division 7 Work in roof spaces
128 Roof spaces de-energised
(1) This regulation applies to work performed in a roof space of a
Class 1 building, Class 2 building or Class 10 building.
(2) A person with management or control of the workplace must ensure
the building's electrical installation is de-energised by a competent
person.
(3) A person must not perform work in a roof space of a building unless
the building's electrical installation is de-energised by a competent
person.
-- 89 of 149 --
Part 6 Conduct of other work
Division 7 Work in roof spaces
Electrical Safety Regulations 2024 80
(4) If the roof space of a building in which electrical work is performed
is divided into separate parts that prevent a person from moving
from one part of the roof space to another part, and each part
relates to a separate dwelling, the requirement to de-energise the
building's electrical installation under subregulations (2) and (3) only
applies to the part of the roof space in which the work is to be
performed.
(5) Subregulations (2) and (3) do not apply to electrical work performed
by a competent person to test, service or commission an appliance
or other equipment in, or accessible by means of, the roof space, to
the extent necessary to energise the appliance or equipment, if:
(a) it is necessary to energise the appliance or equipment for the
purposes of testing, servicing or commissioning the appliance
or equipment; and
(b) a written risk assessment is conducted or a safe work method
statement for the work is prepared; and
(c) the competent person is satisfied that any electrical risk
identified by the assessment or statement is or can be
reduced as low as reasonably practicable and the work can be
carried out safely.
Examples of an appliance or equipment for subregulation (5)
A gas appliance, air conditioner or antenna.
(6) Subregulations (2) and (3) do not require the de-energising of the
following:
(a) service apparatus that is part of a building's electrical
installation;
(b) a supply cable that is part of a building's electrical installation
if:
(i) the cable is from a solar power system, wind turbine
or battery; and
(ii) it is not reasonably practicable to de-energise the
cable;
(c) any other part of the building's electrical installation if it is not
reasonably practicable to de-energise that part.
(7) In this regulation:
service apparatus means any works, apparatus or system,
including any part of the works, apparatus or system and any other
-- 90 of 149 --
Part 6 Conduct of other work
Division 8 Installation of ceiling insulation
Electrical Safety Regulations 2024 81
equipment or plant used in conjunction with the works, apparatus or
system that are capable of being used, or are intended to be used,
for the purpose of conveying, measuring or controlling electricity
supplied from any electric network to the position on any premises
at which delivery of the electricity is, is capable of being, or is
intended to be, made to the consumer.
129 Offence related to electrical work in roof spaces
(1) A person commits an offence if the person contravenes
regulation 128.
Maximum penalty: 50 penalty units.
(2) An offence against subregulation (1) is an offence of strict liability.
Division 8 Installation of ceiling insulation
130 Training for assessment of electrical risk
(1) A person conducting a business or undertaking that installs ceiling
insulation in a building must do all that is reasonably practicable to
ensure the person and any other persons employed or engaged by
the person are trained in performing an assessment of the electrical
risk from the installation of ceiling insulation.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 15 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
131 Installation standard
(1) A person conducting a business or undertaking that installs ceiling
insulation in a building must ensure the installation complies with
the following:
(a) the Wiring Rules;
(b) AS/NZS 1680 (Interior and workplace lighting);
(c) AS/NZS 2293 (Emergency escape lighting and exit signs for
buildings);
(d) the National Construction Code.
Note for subregulation (1)(a)
The Wiring Rules deal with recessed luminaires and auxiliary equipment.
-- 91 of 149 --
Part 6 Conduct of other work
Division 8 Installation of ceiling insulation
Electrical Safety Regulations 2024 82
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 15 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
132 Energised equipment in ceiling prohibited
(1) A person conducting a business or undertaking that installs ceiling
insulation in domestic residence must ensure any electrical
equipment in the ceiling is not energised before starting the
installation.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
133 Assessment of electrical risk and control measures
(1) A person conducting a business or undertaking that installs ceiling
insulation in a building other than a domestic residence must,
before starting the installation:
(a) prepare a safe work method statement of the electrical risk for
the work; and
(b) implement any control measures necessary to eliminate or
minimise electrical risk.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 20 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
134 Electrically conductive ceiling insulation on joists prohibited
(1) A person conducting a business or undertaking that installs ceiling
insulation must ensure ceiling insulation that is readily able to
conduct electricity is not installed on any joists in the ceiling of a
building.
Note for subregulation (1)
The insulation can be installed against the roof where it is unlikely to come into
contact with a source of electricity.
-- 92 of 149 --
Part 6 Conduct of other work
Division 9 Photovoltaic arrays
Electrical Safety Regulations 2024 83
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
135 Metal or other conductive fasteners for ceiling insulation
prohibited
(1) A person conducting a business or undertaking installing ceiling
insulation must do all that is reasonably practicable to ensure
ceiling insulation is not fastened with metal or any other form of
conductive fastener.
(2) A worker installing ceiling insulation must not fasten ceiling
insulation with metal or any other form of conductive fastener.
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
Division 9 Photovoltaic arrays
136 Standards
(1) A person performing electrical work involving a photovoltaic array
must perform the work in accordance with this regulation.
(2) The electrical work must comply with the following:
(a) the Wiring Rules;
(b) AS/NZS 5033 (Installation and safety requirements for
photovoltaic (PV) arrays);
(c) AS/NZS 4777.1 (Grid connection of energy systems via
inverters);
(d) AS/NZS 1170.2 (Structural design actions Part 2: Wind
actions);
(e) any requirements of the network operator applicable to
photovoltaic arrays;
-- 93 of 149 --
Part 6 Conduct of other work
Division 9 Photovoltaic arrays
Electrical Safety Regulations 2024 84
(f) any requirements for construction applicable in high wind
areas under the Building Code as adopted under the Building
Regulations 1993.
Note for subregulation (2)(f)
The Building Code sets out high wind areas and refers to Wind Region C
(cyclonic) as defined in AS/NZ 1170.2.
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
137 Enclosure of photovoltaic array
(1) This regulation applies in relation to the ownership or installation of
photovoltaic arrays on and after 1 July 2026.
(2) Subject to subregulation (3), any photovoltaic array that is free
standing and is less than 2.5 m from the ground surface must be
enclosed in a manner that prevents:
(a) unauthorised access to the array; and
(b) damage to the array caused by animals.
(3) The photovoltaic array is not required to be enclosed if:
(a) a written risk assessment is undertaken by a competent
person; and
(b) the risk assessment shows a low risk of unauthorised access
and a low risk of damage to the photovoltaic array.
(4) A person commits an offence if the person:
(a) owns or installs a photovoltaic array that is free standing and
is less than 2.5 m from the ground surface; and
(b) does not enclose the photovoltaic array in accordance with
subregulation (2).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
-- 94 of 149 --
Part 6 Conduct of other work
Division 9 Photovoltaic arrays
Electrical Safety Regulations 2024 85
138 Power conversion equipment
(1) A person performing electrical work involving power conversion
equipment for a photovoltaic array must ensure the equipment is
safely located and marked in accordance with this regulation.
(2) The power conversion equipment must be kept at least 30 cm away
from any combustible materials or substances.
(3) A non-combustible barrier must be installed on any wall that:
(a) is within 30 cm of the power conversion equipment; and
(b) separates the power conversion equipment from a room in a
domestic residence that is used for normal living activities; and
(c) is not already a non-combustible barrier or does not consist of
a metallic material of a minimum thickness of 0.2 mm.
Note for subregulation (3)(c)
Steel cladding, sheet metal (aluminium, steel, tin and zinc) are acceptable
metallic materials.
(4) For subregulation (3), the barrier must:
(a) extend vertically at least 30 cm above and below the power
conversion equipment; and
(b) extend horizontally at least 30 cm wider than the width of the
power conversion equipment.
(5) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
139 Isolators prohibited on roof
(1) A person must not install an isolator for a rooftop photovoltaic array
on the roof of a class 1 building.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
-- 95 of 149 --
Part 6 Conduct of other work
Division 10 Energy storage systems
Electrical Safety Regulations 2024 86
140 Disconnection points
(1) A person must, as far as reasonably practicable, install all
disconnection points for a rooftop photovoltaic array within 1.25 m
of the rooftop access point.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
141 Signage
(1) A person installing power conversion equipment for a photovoltaic
array located indoors in a building used for commercial purposes
must mark the location of the equipment in accordance with this
regulation.
(2) The location of the power conversion equipment must be marked:
(a) at the main switchboard; and
(b) at the sub-board; and
(c) on the fire indicator panel block plan (where applicable).
(3) For subregulation (1), the wording of either of the following is
sufficient:
INVERTER LOCATIONS INVERTER LOCATION
Battery: ___________ or __________________
Solar: ____________ __________________
(4) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 5 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
Division 10 Energy storage systems
142 Installation of energy storage systems
(1) A person performing electrical work involving an energy storage
system must:
(a) perform a risk assessment prior to commencing the work; and
-- 96 of 149 --
Part 6 Conduct of other work
Division 10 Energy storage systems
Electrical Safety Regulations 2024 87
(b) ensure the work complies with:
(i) the Wiring Rules; and
(ii) AS/NZS 5139 (Electrical installations – Safety of battery
systems for use with power conversion equipment).
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
143 Smoke alarm – indoors
(1) This regulation applies in relation to any installation of an energy
storage system located inside a domestic residence and under the
same roof as a habitable room that occurs on or after 1 July 2026.
(2) A person performing the installation must ensure a smoke alarm is
installed in accordance with this regulation.
(3) The smoke alarm must be:
(a) located above or close to the energy storage system in any
place where the energy storage system is located; and
(b) integrated with any other smoke alarms in the building in
which the energy storage system is located.
(4) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
144 Safety – indoor installation
(1) A person performing electrical work installing an energy storage
system located inside domestic residence and under the same roof
as a habitable room must ensure the energy storage system is
safely located, marked and shielded in accordance with this
regulation.
(2) The energy storage system must be located at least 60 cm away
from any combustible materials or substances.
-- 97 of 149 --
Part 6 Conduct of other work
Division 10 Energy storage systems
Electrical Safety Regulations 2024 88
(3) A line at least 50 mm in width must be marked in prominent and
permanent paint on the floor at least 60 cm from the edges of the
energy storage system.
(4) A non-combustible barrier must be installed on any wall that:
(a) is within 30 cm of the energy storage system; and
(b) separates the energy storage system from a habitable room in
the domestic residence; and
(c) is not already a non-combustible barrier.
(5) The non-combustible barrier must:
(a) extend vertically from:
(i) the floor to the ceiling or a point 1.20 m above the
energy storage system; or
(ii) if the energy storage system is installed more than
60 cm above the floor – at least 60 cm below the energy
storage system to the ceiling or a point 1.2 m above the
energy storage system; and
(b) extend horizontally at least 60 cm wider than the width of the
energy storage system; and
(c) if the ceiling is less than 1.2 m above the energy storage
system – extend across the ceiling from the wall covering an
area at least 60 cm beyond the front and sides of the energy
storage system.
(6) For subregulation (5), any floor joists or floor of an elevated building
above the energy storage system are taken to be part of the ceiling.
(7) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(8) An offence against subregulation (7) is an offence of strict liability.
145 Safety – outside installation
(1) A person performing electrical work installing an energy storage
system located outside a building must ensure the energy storage
system is safely located, marked and shielded in accordance with
this regulation.
-- 98 of 149 --
Part 6 Conduct of other work
Division 10 Energy storage systems
Electrical Safety Regulations 2024 89
(2) The energy storage system must be located at least 60 cm away
from any combustible materials or substances.
(3) A line at least 50 mm in width must, so far as is reasonably
practicable, be marked in prominent and permanent paint on the
ground at least 60 cm from the edges of the energy storage system.
(4) A non-combustible barrier must be installed on any wall that:
(a) is within 30 cm of the energy storage system; and
(b) separates the energy storage system from a habitable room in
the building; and
(c) is not already a non-combustible barrier.
(5) The non-combustible barrier must:
(a) extend vertically from the ground to a point 90 cm above the
energy storage system; and
(b) extend horizontally at least 60 cm wider than the width of the
energy storage system.
(6) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(7) An offence against subregulation (6) is an offence of strict liability.
146 Storage of combustible materials
(1) A person must not store or keep any combustible materials or
substances:
(a) within 60 cm from the edges of the energy storage system; or
(b) within the space above the area within 60 cm from the edges
of the energy storage system.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
(4) For subregulation (1), combustible materials includes foliage and
other vegetation.
-- 99 of 149 --
Part 6 Conduct of other work
Division 10 Energy storage systems
Electrical Safety Regulations 2024 90
147 Signage – general
(1) This regulation applies in relation to any installation of an energy
storage system that occurs on or after 1 July 2026.
(2) A person installing an energy storage system must install a durable,
conspicuous sign in accordance with this regulation.
(3) The sign must be located as follows:
(a) on the outside of the building, other than a class 1 building;
(b) in the case of a building used for commercial purposes:
(i) at the main switchboard; and
(ii) at the sub-board; and
(iii) on the fire indicator panel block plan (where applicable).
(4) The signage on the outside of the building must:
(a) be reflective; and
(b) in the case of a chemical battery – include the battery
chemistry or the United Nations Number of the battery
chemistry; and
(c) consist of one of the following logos in which the white letters
"ES" are at least 10 cm in height on a green background:
.
Note for subregulation (4)
The following is a list of some of the energy storage system chemistry numbers:
UN number Chemical type
2794 Flooded lead acid
2795 Nickel cadmium
2800 Valve regulated lead acid
3090 Lithium metal
3292 Sodium
3480 Lithium ion (including ion polymer)
-- 100 of 149 --
Part 6 Conduct of other work
Division 10 Energy storage systems
Electrical Safety Regulations 2024 91
3496 Nickel-metal hydride
(5) The signage referred to in subregulation (3)(b) must consist of one
of the logos mentioned in subregulation (4)(c) in which the white
letters “ES” are legible and in a size appropriate for the location.
(6) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 5 penalty unit.
(7) An offence against subregulation (6) is an offence of strict liability.
148 Fire indicator panels
(1) A person installing an energy storage system in a building with a
fire indicator panel must ensure the location of the energy storage
system is marked prominently on the fire indicator panel block plans
for the building.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 5 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
149 Signage – commercial operations
(1) A person conducting a business or undertaking who charges
batteries with lithium chemistry in or around a building must install a
durable, conspicuous sign in accordance with this regulation if the
batteries:
(a) are used as part of a commercial operation; and
(b) charge at 60 Ah or more; and
(c) are used to power equipment used in the commercial
operation.
Examples for subregulation (1)(a)
Lawnmowing or gardening businesses that use battery operated equipment.
(2) The signage must:
(a) be placed on the outside of the building; and
(b) be reflective; and
-- 101 of 149 --
Part 6 Conduct of other work
Division 10 Energy storage systems
Electrical Safety Regulations 2024 92
(c) include the battery chemistry or the United Nations Number of
the battery chemistry; and
(d) consist of one of the following logos in which the letters "ES"
are at least 10 cm in height:
.
Note for subregulation (2)
The following is a list of energy storage system chemistry numbers:
UN number Chemical type
3090, 3091 Lithium metal
3480, 3481 Lithium ion (including ion polymer)
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 5 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
150 Registration – commercial operations
(1) The owner of a commercial operation must register the operation in
accordance with this regulation if:
(a) the owner uses an energy storage system as part of the
commercial operation; and
(b) the energy storage system uses lithium chemistry; and
(c) the energy storage system charges at 60 Ah or more at any
time.
(2) Registration under this regulation must be lodged in the form
approved by, and manner determined by, the Electrical Safety
Regulator within 30 days after the operation begins using the
energy storage system.
(3) The following information must be included in the registration:
(a) the address of the building and the place within the building
where the energy storage system is located;
-- 102 of 149 --
Part 6 Conduct of other work
Division 11 Electric vehicles
Electrical Safety Regulations 2024 93
(b) the contact details of the owner or occupier of the building.
(4) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
151 Notice of ceasing operation
(1) The owner of a commercial operation registered under
regulation 150 must give written notice to the Electrical Safety
Regulator if the owner ceases using the energy storage system.
(2) The notice must be lodged in the form approved by, and manner
determined by, the Electrical Safety Regulator within 30 days after
the operation ceases using the energy storage system.
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
Division 11 Electric vehicles
152 Smoke alarms
(1) This regulation applies in relation to any installation inside a
building of an electrical connection point for an electric vehicle that
occurs on or after 1 July 2026.
(2) Subject to subregulation (3), the following persons must ensure a
smoke alarm is installed in accordance with this regulation:
(a) a person performing electrical work involving the installation
inside the building of an electrical connection point for an
electric vehicle;
(b) the owner of the building inside of which an electrical
connection point for an electric vehicle is installed.
Note for subregulation (2)
An electrical connection point for an electric vehicle is a power supply device that
supplies electrical power for recharging plug-in electric vehicles. It is not a
general purpose socket or outlet.
-- 103 of 149 --
Part 6 Conduct of other work
Division 11 Electric vehicles
Electrical Safety Regulations 2024 94
(3) No smoke alarm is required to be installed in a building if:
(a) the building is used for commercial purposes; and
(b) the building is equipped with a fire suppression system above
all electrical connection points for electric vehicles; and
(c) a written risk assessment was undertaken by a competent
person; and
(d) the risk assessment shows that smoke alarms would not
minimise the risk more than the fire suppression system.
(4) The smoke alarm must be:
(a) located on the ceiling above any electrical connection point;
and
(b) integrated with any other smoke alarms in the building inside
of which the electrical connection point is installed.
(5) If there are multiple electrical connection points for electric vehicles
in proximity to each other, one smoke alarm may be installed for
every 2 electrical connection points.
(6) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 50 penalty units.
(7) An offence against subregulation (6) is an offence of strict liability.
153 Signage – inside building
(1) This regulation applies in relation to any installation inside a
building, other than a class 1 or class 10 building, of an electrical
connection point for an electric vehicle that occurs on or after
1 July 2026.
(2) The following persons must install a durable, conspicuous sign in
accordance with this regulation:
(a) a person performing electrical work involving the installation
inside the building of an electrical connection point for an
electric vehicle;
(b) the owner of the building inside of which an electrical
connection point for an electric vehicle is installed.
-- 104 of 149 --
Part 6 Conduct of other work
Division 11 Electric vehicles
Electrical Safety Regulations 2024 95
(3) The sign must be reflective and consist of the following logo in
which the white letters "EV" are at least 10 cm in height on a blue
background:
.
(4) The sign must be located:
(a) at every vehicle entrance to the building; and
(b) in proximity to any place where an electrical connection point
for an electric vehicle is installed.
(5) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 5 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
154 Signage – on land or outside building
(1) This regulation applies in relation to any installation of an electrical
connection point for an electric vehicle on land or outside a building
that occurs on or after 1 July 2026.
(2) The following persons must install a durable, conspicuous sign in
accordance with this regulation:
(a) a person performing electrical work involving the installation
on land or outside a building of an electrical connection point
for an electric vehicle;
(b) the owner of the land or building outside of which an electrical
connection point for an electric vehicle is installed.
(3) The sign must be reflective and consist of the following logo in
which the white letters "EV" are at least 10 cm in height on a blue
background:
.
-- 105 of 149 --
Part 6 Conduct of other work
Division 11 Electric vehicles
Electrical Safety Regulations 2024 96
(4) The sign must be located in proximity to any place where an
electrical connection point for an electric vehicle is installed.
(5) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
155 Other signage
(1) This regulation applies in relation to an installation inside a building
of an electrical connection point for an electric vehicle that occurs
on or after 1 July 2026.
(2) A person installing an electrical connection point for charging an
electric vehicle must:
(a) install a durable, conspicuous sign on the main switchboard
and meter box of the building in accordance with
subregulation (3); and
(b) in the case of commercial building with a fire indicator panel –
ensure the location of the electrical connection point for an
electric vehicle is marked prominently on the fire indicator
panel block plans for the building.
(3) The sign must be reflective and consist of the following logo in
which the white letters "EV" are at least 5 mm in height on a blue
background:
.
(4) A person commits an offence if:
(a) the person contravenes subregulation (2); and
(b) the conduct occurs on or after 1 July 2026.
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
-- 106 of 149 --
Part 7 Electricity infrastructure
Division 1 Service lines
Electrical Safety Regulations 2024 97
156 Protection for freestanding electrical connection points for
electric vehicles
(1) This regulation applies in relation to any installation of a
freestanding electrical connection point for an electric vehicle that
occurs on or after 1 July 2026.
(2) The following persons must ensure any freestanding electrical
connection point for an electric vehicle is protected from damage
and electrical risk in accordance with subregulation (3):
(a) a person performing electrical work involving the installation of
a freestanding electrical connection point for an electric
vehicle;
(b) the owner of the building where a freestanding electrical
connection point for an electric vehicle is installed.
(3) The freestanding electrical connection point must:
(a) be protected from damage by a vehicle and safe from
electrical risk by a physical barrier; and
(b) in the event of damage – be safe from electrical risk.
(4) A person commits an offence if the person contravenes
subregulation (2).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
Part 7 Electricity infrastructure
Division 1 Service lines
157 Duties related to service lines
(1) Subject to subregulation (2), the person in control of electricity
infrastructure that is connected to an electricity network by a service
line must provide and maintain:
(a) in the case of an overhead service line – the apparatus used
to attach the service line to the electrical infrastructure; or
-- 107 of 149 --
Part 7 Electricity infrastructure
Division 1 Service lines
Electrical Safety Regulations 2024 98
(b) in the case of an underground service line – the entrance,
support, protection and termination of the service line.
Examples of apparatus for subregulation (1)(a)
A service riser bracket and timber backing for the distribution entity's ‘J' hook.
(2) Subregulation (1) does not require the person in control of the
electricity infrastructure to provide or maintain the insulation of any
apparatus, whether or not the apparatus was provided by the
person.
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
158 Inspection of clamps and apparatus
(1) A distribution entity must, at reasonable regularity, inspect and
maintain the insulation of the clamp or apparatus supplied by the
person in control of the electricity infrastructure for the purposes of
any joint needed for consumer terminals.
(2) A distribution entity commits an offence if the entity contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
159 Structure supporting electric line or equipment
(1) The person in control of electricity infrastructure must ensure any
structure supporting an electric line or item of electrical equipment
forming part of the electricity infrastructure complies with the
requirements of:
(a) the Wiring Rules; and
(b) any direction the Electrical Safety Regulator gives to ensure
electrical safety.
(2) If there is an inconsistency between the Wiring Rules and a
direction of the Electrical Safety Regulator, the direction prevails to
the extent of the inconsistency.
-- 108 of 149 --
Part 7 Electricity infrastructure
Division 2 Maintenance related to powerlines
Electrical Safety Regulations 2024 99
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
Division 2 Maintenance related to powerlines
160 Trimming of trees near overhead electric line
(1) The person in control of an overhead electric line, other than one
owned by an electricity entity, must do all that is reasonably
practicable to ensure trees and other vegetation are trimmed, and
other reasonable measures are taken, to keep the line electrically
safe.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 40 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
161 Consultation with owner or occupier before remedial action to
clear vegetation
(1) For the purposes of section 90 of the Act, an electricity officer on
behalf of an electricity entity may give written notice to the owner or
occupier of land at least 14 days before entering the land if the
owner or occupier fails to comply with section 89(5) of the Act.
(2) The notice must state the following:
(a) the reason for, and the date and time of, the proposed entry;
(b) the nature of the work to be performed in clearing vegetation
from the land;
(c) the arrangements to make good any damage caused or the
terms of any compensation to be paid for damage caused;
(d) the owner's or occupier's right of review under
subregulation (3).
(3) An owner or occupier of land who receives a notice under this
regulation may have the following reviewed by NTCAT:
(a) the proposed arrangements to make good any damage
caused;
-- 109 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 1 Proximity to powerlines
Electrical Safety Regulations 2024 100
(b) the proposed terms of any compensation to be paid for
damage caused;
(c) any action taken to make good any damage caused;
(d) any compensation paid for damage caused.
Division 3 Proximity to powerlines and electricity
infrastructure
Subdivision 1 Proximity to powerlines
162 Proximity to powerlines
(1) Subject to subregulation (3), a person conducting a business or
undertaking at a workplace must ensure, so far as is reasonably
practicable, that no person, plant or thing at the workplace comes
closer to an overhead or underground powerline than proximity
limit A, B, C(i) or C(ii) set out in Schedule 2 opposite the powerline
with the voltage specified in that Schedule.
(2) For Schedule 2, the proximity limits apply as follows:
(a) proximity limit A applies to a person suitably qualified and
trained to work in proximity to exposed high and low voltage
conductors or exposed parts of high and low voltage electrical
equipment;
(b) proximity limit B applies to a person who has been instructed
in the identification of high and low voltage overhead
conductors and the safety aspects of work near live
powerlines;
(c) proximity limit C(i) applies to a person using power operated
tools;
(d) proximity limit C(ii) applies to a person using manually
operated tools.
(3) If it is not reasonably practicable to comply with subregulation (1),
the person conducting the business or undertaking must do all that
is reasonably practicable to ensure:
(a) a risk assessment is conducted for the proposed electrical
work; and
(b) control measures implemented are consistent with:
(i) the risk assessment; and
-- 110 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 1 Proximity to powerlines
Electrical Safety Regulations 2024 101
(ii) if an electricity entity is responsible for the electric line –
any reasonable requirements of the entity made under
section 93 of the Act.
(4) A person commits an offence if the person contravenes
subregulation (1) or (3).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
163 Erection of buildings in proximity to powerlines
(1) For section 91(1) of the Act, the prescribed safety requirements are
set out in this regulation.
(2) A building or structure must not be erected under a powerline
constructed to operate at any voltage.
(3) A building or structure must not be erected above or below an
underground powerline.
(4) A building or structure must not be erected within the following
distances of an underground powerline as measured from vertical
planes extending above and below each outer edge of the
conductor comprising the powerline or, in the case of a powerline
that consists of more than one conductor, each outer edge of each
outer conductor:
(a) 2 m for an underground powerline designed to operate at a
voltage of 11 kV or less;
(b) 3 m for any other underground powerline.
(5) A building or structure must not be erected where the distance
between the building or structure and the position to which a
conductor in a powerline might swing or sag is less than the
distance set out in Table 1 in Schedule 3.
(6) This regulation does not apply to the following structures and power
lines:
(a) a fence that is less than 2 m in height;
(b) a powerline installed specifically to supply electricity to the
building or structure by the operator of the transmission or
distribution network from which the electricity is being
supplied.
-- 111 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 1 Proximity to powerlines
Electrical Safety Regulations 2024 102
164 Prohibition of certain activities in proximity to powerlines
(1) A person must not engage in any conduct prohibited by
subregulations (2) to (5) without the written authority of the
distribution entity.
(2) Material must not be placed closer to the position to which a
powerline may swing or sag than the distance set out in Table 1 in
Schedule 4.
(3) A machine, vehicle or vessel equipped with an elevating component
or shear legs must not be operated in a way that a part of the
machine, vehicle, vessel or its load is closer to the position to which
a powerline may swing or sag than the distance set out in Table 1
in Schedule 4.
(4) Conductors of circuits or other cable system must not be attached
or kept attached to electricity infrastructure.
(5) Conductors of circuits, or other cable system, must not be erected
or maintained closer to the circuit of a powerline than the distance
set out in Table 3 in Schedule 4.
(6) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(7) An offence against subregulation (6) is an offence of strict liability.
(8) When calculating proximity for this regulation:
(a) a person includes any article of clothing worn by the person,
and any conductive object the person is handling; and
(b) a person does not include any object that alone or with
another object:
(i) is an extension of the person; and
(ii) is insulated and tested to be safe for use on and near
the powerline; and
(c) a machine includes anything the machine is handling, other
than:
(i) a person; or
(ii) a handheld object a person is handling; and
-- 112 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 2 Conduct in proximity to electricity infrastructure
Electrical Safety Regulations 2024 103
(d) a vehicle or vessel includes anything the vehicle or vessel is
carrying or otherwise handling.
165 Register of underground powerlines
(1) A distribution entity must keep a register describing the nature and
location of each underground powerline that is under the control of
the entity.
(2) The operator of an electricity network in an area must be notified by
any distribution entity of the nature and location of any underground
powerline installed in the area by that distribution entity.
(3) The information given by a distribution entity under
subregulation (2) must be recorded in the register kept under
subregulation (1).
(4) A distribution entity must make available the information contained
in the register on request by a member of the public during normal
business hours.
Subdivision 2 Conduct in proximity to electricity infrastructure
166 Placement of materials in proximity to electricity infrastructure
(1) A person must not engage in any conduct prohibited by
subregulation (2) or (3) without the written authority of the operator
of the electricity infrastructure.
(2) Material must not be placed or kept closer to electricity
infrastructure consisting of a supporting or protective structure or
equipment for aerial lines than the distance set out in Table 1 in
Schedule 4.
(3) A circuit or other cable system must not be erected closer to a
structure forming part of electricity infrastructure, other than a
structure supporting the circuit or system, than the distance set out
in Table 4 in Schedule 4.
(4) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
167 Placement of materials in proximity to supporting structures
(1) A person must not, without the written authority of the operator of
the electricity infrastructure, place or maintain any material closer
-- 113 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 2 Conduct in proximity to electricity infrastructure
Electrical Safety Regulations 2024 104
than the relevant distance set out in Table 1 in Schedule 4 to
electricity infrastructure consisting of a supporting or protective
structure or equipment for aerial lines.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
168 Placement of materials in proximity to substations
(1) A person must not, without the written authority of the operator of
the electricity infrastructure:
(a) place or maintain any timber or inflammable material within
3 m in any direction of a wall or fence surrounding a
substation; or
(b) impede access to any door, gate or entrance of a substation
or interfere in any way with the free flow of air through an
opening or fitting used for ventilation in the walls of a
substation; or
(c) place or maintain any material adjacent to a wall or fence of a
substation; or
(d) plant or nurture vegetation near or adjacent to a wall or fence
of a substation, so as to enable unauthorised access to the
substation.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
169 Prohibition of burning in proximity to electricity infrastructure
(1) A person must not, without the written authority of the operator of
the electricity infrastructure, burn any material in proximity to
electricity infrastructure that creates a risk of damage to the
infrastructure or outages or flashovers.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
-- 114 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 2 Conduct in proximity to electricity infrastructure
Electrical Safety Regulations 2024 105
(3) An offence against subregulation (2) is an offence of strict liability.
170 Protection of underground powerlines
(1) A person must not, without the written authority of the operator of
the electricity infrastructure of which the line forms part:
(a) place or maintain, or cause to be placed or maintained, a
corrosive, abrasive, heavy or deleterious material or
substance above an underground powerline; or
(b) make an opening in the ground surface that may endanger an
underground power line; or
(c) remove, tamper with or cover any underground line marker.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
171 Entangled objects
(1) A person must not, without the authority of the operator of the
electrical infrastructure or electrical installation, pull or interfere with
an object resting on or entangled in the electricity infrastructure or
the electrical installation.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
(4) It is a defence to a prosecution for an offence against
subregulation (2) if the conduct is reasonably necessary to prevent
or reduce injury to a person or property.
-- 115 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 2 Conduct in proximity to electricity infrastructure
Electrical Safety Regulations 2024 106
172 Altering ground levels near electricity infrastructure
(1) A person must not, without the written authority of the operator of
the electricity infrastructure, engage in the following conduct in a
manner that may alter the level of the ground at a place so as to
infringe a permissible clearance distance under these Regulations:
(a) cut away, excavate or remove, or cause to be cut away,
excavated or removed, earth or material supporting electricity
infrastructure so as to endanger the stability of the
infrastructure;
(b) make an excavation deeper than 0.3 m within 3 m of:
(i) a pole structure or stand, not being a tower or tower
structure supporting electricity infrastructure; or
(ii) a pole or bed log to which is affixed a staywire used to
support electricity infrastructure;
(c) make an excavation deeper than 0.5 m within 10 m of a tower
or tower structure supporting electricity infrastructure;
(d) make an excavation deeper than 0.3 m within 0.6 m of a wall,
fence or foundation of a substation;
(e) place material or construct an artificial surface above ground
level:
(i) below an electric line or within the vertical projection of
points to which a conductor of the electric line may sway;
or
(ii) adjacent to electricity infrastructure.
(2) The allowable depth of an excavation under subregulation (1) is
determined by reference to:
(a) if the ground level unaffected by previous works is known –
that level;
(b) if not known – by reference to the current ground level.
(3) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 25 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
-- 116 of 149 --
Part 7 Electricity infrastructure
Division 3 Proximity to powerlines and electricity infrastructure
Subdivision 3 Transportation in proximity to powerlines
Electrical Safety Regulations 2024 107
Subdivision 3 Transportation in proximity to powerlines
173 Transportation
(1) A person who drives a vehicle carrying a load or equipment on the
vehicle or on a trailer attached to the vehicle that exceeds the
height limit established under the Motor Vehicles Act 1949 must
ensure:
(a) the distance between the load being transported and an aerial
line along the route taken is greater than the relevant distance
set out in Table 5 in Schedule 4; and
(b) arrangements approved by the operator of the electricity
infrastructure of which the aerial line is part have been made
before, and are observed during, transportation.
(2) The person must give written notice of the proposal to transport the
load to the operator of the electricity infrastructure at least 3 clear
business days before the commencement of the transportation with
the notice clearly stating the following:
(a) the nature of the vehicle or trailer and the load;
(b) the height and width of the load;
(c) the date and the time of the proposed transportation;
(d) the starting point and finishing point of the transportation;
(e) the proposed route;
(f) the name and contact address of the person;
(g) that the person must pay the reasonable costs that are
incurred by the operator in considering the proposal,
approving the transportation arrangements or facilitating the
transportation;
(h) any other particulars that the operator may in the
circumstances require.
(3) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(4) An offence against subregulation (3) is an offence of strict liability.
-- 117 of 149 --
Part 7 Electricity infrastructure
Division 4 Cathodic protection systems
Electrical Safety Regulations 2024 108
174 Recovery of costs
(1) An operator of electricity infrastructure may charge, in advance, the
reasonable costs referred to in regulation 173(2)(g).
(2) An amount equivalent to the reasonable cost referred to in
regulation 173(2)(g) is a debt due and payable to the operator of
the electricity infrastructure charging it.
175 Obstruction of road
(1) A person must not obstruct a road under the control of an operator
of electricity infrastructure or otherwise do anything to prevent or
impede access to the electricity infrastructure.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
176 Interference or damage of road
(1) A person must not interfere with or damage the surface of a road
made by an operator of electricity infrastructure that is used for the
purposes of works.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 25 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
177 Removal of danger on road
An operator of electricity infrastructure may, without notice any
person, remove any thing that causes or may cause a danger to
people or property using or on a road under the control of the
operator of electricity infrastructure.
Division 4 Cathodic protection systems
178 Cathodic protection systems
(1) The owner or operator of a cathodic protection system must ensure
it does not adversely affect the integrity or safety of any electrical
installation or supply system through corrosion.
-- 118 of 149 --
Part 7 Electricity infrastructure
Division 5 Distribution entity improvement notices
Electrical Safety Regulations 2024 109
(2) The owner or operator of a cathodic protection system that has an
anode immersed in water or a marine environment must, within
90 days before starting to operate the system, perform tests to
ensure the potential difference between any 2 accessible points
spaced 1 m apart in the water or marine environment is not more
than 3 volts when the system is energised.
(3) Subregulations (1) and (2) do not apply to a cathodic protection
system that:
(a) is installed on any floating mobile structure, fishing equipment,
fixed offshore structure (not connected with land above sea
level) or the internal surface of any apparatus, equipment or
structure; or
(b) uses only galvanic anodes.
(4) A person commits an offence if the person contravenes
subregulation (1) or (2).
Maximum penalty: 50 penalty units.
(5) An offence against subregulation (4) is an offence of strict liability.
Division 5 Distribution entity improvement notices
179 Giving improvement notice
(1) A distribution entity may give a person in control of an electrical
installation an improvement notice if the entity believes on
reasonable grounds that the installation is not safe from electrical
risk.
(2) The improvement notice may require the person to:
(a) remedy the electrical risk; or
(b) prevent a likely electrical risk from occurring; or
(c) remedy the things, circumstances or conduct causing the
electrical risk or likely electrical risk.
(3) The person in control of an electrical installation who receives an
improvement notice under this regulation may have it reviewed by
NTCAT.
-- 119 of 149 --
Part 7 Electricity infrastructure
Division 5 Distribution entity improvement notices
Electrical Safety Regulations 2024 110
180 Contents of improvement notices
(1) An improvement notice given under regulation 179 must include the
following:
(a) the grounds on which the notice is being issued;
(b) the provision of the Act or these Regulations that the
distribution entity believes is causing the electrical risk or likely
electrical risk;
(c) a summary of the facts of the alleged electrical risk or likely
electrical risk;
(d) the specific period within which the remedy or preventive
action is required to be completed;
(e) the person's right of review under regulation 179(3).
(2) The improvement notice may include the measures to be taken to
remedy the electrical risk or likely electrical risk.
(3) The measures required to be taken and the period within which
they are to be completed must be reasonable in the circumstances.
181 Extension of time for compliance with improvement notices
(1) A distribution entity may, by written notice, extend the time to
comply with its improvement notice.
(2) The time may be extended more than once.
(3) No extension may be given after the time to comply has expired.
182 Compliance with improvement notice
(1) A person to whom an improvement notice is given under
regulation 179 must comply with the notice within the period
specified in the notice.
(2) A person commits an offence if the person:
(a) is given an improvement notice; and
(b) does not comply with the notice within the period specified in
the notice or any extension of time made under
regulation 181.
Maximum penalty: 50 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
-- 120 of 149 --
Part 8 Approved safety switches
Electrical Safety Regulations 2024 111
(4) It is a defence to a prosecution for an offence against
subregulation (2) if the defendant did all that was reasonably
practicable to comply with the notice, including engaging a
contractor to perform the work.
(5) The defendant has a legal burden of proof in relation to the defence
under subregulation (4).
Division 6 Other matters
183 Changes to safety management and mitigation plan
(1) An electricity entity with a safety management and mitigation plan
approved by the Electrical Safety Regulator must not make any
change to the plan until the proposed change is:
(a) assessed by a competent and independent third party in
accordance with section 77(4) and (5) of the Act; and
(b) approved by the Electrical Safety Regulator.
(2) The Electrical Safety Regulator may approve a change in a safety
management and mitigation plan submitted by an electricity entity
under subregulation (1) if satisfied that the plan as changed meets
the requirements of section 78(2) of the Act.
(3) The Electrical Safety Regulator must give the electricity entity a
decision notice if it approves or refuses to approve a change to its
safety management and mitigation plan.
Part 8 Approved safety switches
191 Performing electrical installation work for domestic residences
and residential premises
(1) This regulation applies in relation to electrical work on an electrical
installation in a domestic residence or residential premises that
occurs on or after 1 December 2028.
(2) A person must not perform electrical work on the electrical
installation unless:
(a) an approved safety switch is installed; or
(b) if an approved safety switch is not installed:
(i) the work consists of the connection of the residence or
premises to a source of electricity; or
-- 121 of 149 --
Part 9 Miscellaneous
Electrical Safety Regulations 2024 112
(ii) the work must be performed without delay because of an
emergency, to prevent an emergency from happening or
for safety reasons.
(3) A person commits an offence of strict liability if the person
contravenes subregulation (2).
Maximum penalty: 50 penalty units.
Part 9 Miscellaneous
192 Register of engaged workers
For section 53 of the Act, the following information is prescribed:
(a) the person's name;
(b) the number and class of the person's licence;
(c) any endorsements on the person's licence;
(d) any conditions or restrictions on the person's licence;
(e) the day the person's licence expires.
193 Record of apprentices and trainees
(1) For sections 62(3) and 63(3) of the Act, the record must be in an
approved form and contain current information about registered
apprentices and trainees with trainee permits.
(2) An apprentice and trainee must notify the Electrical Safety
Regulator of any change in the apprentice's or trainee's recorded
contact details within 14 days after the change.
194 Appointment of inspectors
For section 141(1)(b) of the Act, holders of unrestricted electrical
work licences are a prescribed class of persons.
195 Fees
(1) The prescribed fees are specified in Schedule 5, Part 1 opposite
the item specified in that Schedule.
(2) The Electrical Safety Regulator may refund or remit a fee or the
administration component of a fee if:
(a) the fee is for an application that is withdrawn; or
-- 122 of 149 --
Part 9 Miscellaneous
Electrical Safety Regulations 2024 113
(b) the fee is for a licence, registration or permit that is returned or
cancelled for reasons other than a disciplinary matter; or
(c) the Electrical Safety Regulator considers that the refund or
remittance is otherwise justified in the circumstances.
(3) The amount of the refund for the administration component of the
fee for an application in relation to a licence that is refused is
specified in Schedule 5, Part 2 opposite the type of application
specified in that Schedule.
(4) The Electrical Safety Regulator may publish information to assist
the public on the refund and remittance of fees.
196 Display of distribution entity improvement notice
(1) A person who receives an improvement notice under
regulation 179(1) must, as soon as possible, display a copy of the
notice in a prominent location at or near the installation specified in
the notice.
(2) A person commits an offence if the person contravenes
subregulation (1).
Maximum penalty: 30 penalty units.
(3) An offence against subregulation (2) is an offence of strict liability.
(4) A person must not remove, destroy, damage or deface a notice
displayed under subregulation (1) while the notice is in force.
(5) A person commits an offence if the person intentionally contravenes
subregulation (4).
Maximum penalty: 30 penalty units.
197 Costs of ensuring compliance with direction
(1) A person to whom a direction is given under section 188 or 198 of
the Act is liable to pay the reasonable costs of any re-inspection or
re-attendance by an inspector for the purpose of ensuring
compliance with the direction.
(2) The amount payable under subregulation (1) is a debt due and
payable to the Electrical Safety Regulator by the person to whom
the direction was given.
-- 123 of 149 --
Part 9 Miscellaneous
Electrical Safety Regulations 2024 114
198 General offence
(1) A person commits an offence if the person contravenes a provision
of these Regulations for which no offence or penalty is expressly
provided.
Maximum penalty: 50 penalty units.
(2) An offence against subregulation (1) is an offence of strict liability.
(3) It is a defence to a prosecution for an offence against
subregulation (1) if the defendant has a reasonable excuse.
199 Register of licences
(1) The Electrical Safety Regulator must keep a register, in the
approved form, containing current information about licences.
(2) The register of electrical licences must include the following
information for each licence:
(a) the full name and address of the licensee;
(b) an identifying number;
(c) when the licence was issued;
(d) details of any renewal. failure to renew and reinstatement of
the licence;
(e) details of any disciplinary action taken against the holder;
(f) any other information the Electrical Safety Regulator considers
appropriate.
Example for subregulation (2)(f)
The endorsements, conditions or restrictions on a licence.
(3) A licensee must notify the Electrical Safety Regulator of any change
in the licensee's contact details, as recorded in the register, within
14 days after the change.
(4) Subregulation (3) does not apply to any change referred to in
regulation 50.
-- 124 of 149 --
Part 9 Miscellaneous
Electrical Safety Regulations 2024 115
(5) The Electrical Safety Regulator may publish some or all of the
information included in the register on the Electrical Safety
Regulator's website.
Note for subregulation (5)
Publishing the information allows consumers to obtain licensing details about a
person performing electrical work.
200 Information sharing
(1) The Electrical Safety Regulator may share information obtained
under these Regulations for the following purposes:
(a) to exercise a power or perform a function or duty under the
following:
(i) the Act;
(ii) the Electricity Reform Act 2000;
(iii) the Work Health and Safety (National Uniform
Legislation) Act 2011;
(b) to reduce, eliminate or respond to an electrical risk;
(c) to prevent and address unlicensed electrical work;
(d) to improve the ability of emergency services to respond to
emergency situations;
(e) to maintain registers and databases of electrical equipment,
electrical installations and electricity infrastructure;
(f) to promote the safe and efficient administration of grant
programs related to electrical safety;
(g) to ensure licensees meet their obligations to consumers of
electrical equipment and electrical services;
(h) to provide information required for the transfer of land or for
the establishment of a tenancy;
(i) to provide information relevant to the prevention, detection, or
the investigation of an offence;
(j) for purposes related to enforcement or compliance with the
Act or these Regulations.
-- 125 of 149 --
Part 9 Miscellaneous
Electrical Safety Regulations 2024 116
(2) For subregulation (1), the information may be shared with the
following:
(a) a law enforcement agency as defined in section 4 of the
Information Act 2002;
(b) the Clean Energy Regulator established by the Clean Energy
Regulator Act 2011 (Cth);
(c) the Registrar-General and Lands Titles Registration and
General Registry Office for the Northern Territory established
under section 4 of the Registration Act 1927;
(d) the Commissioner of Tenancies as defined in section 13 of the
Residential Tenancies Act 1999;
(e) network providers, network operators and network entities,
including the Power and Water Corporation established under
section 4 of the Power and Water Corporation Act 1987;
(f) the Power Retail Corporation established under section 5 the
Power Retail Corporation Act 2014;
(g) the Power Generation Corporation established under section 5
of the Power Generation Act 2014;
(h) the Utilities Commission established under section 5 of the
Utilities Commission Act 2000;
(i) the Agency responsible for the Consumer Affairs and Fair
Trading Act 1990;
(j) any Agency responsible for implementing any program related
to energy storage systems;
(k) any Agency responsible for the following:
(i) the Building Act 1993;
(ii) the Plumbers and Drainers Licensing Act 1983;
(iii) the Swimming Pool Safety Act 2004;
(iv) the Water Supply and Sewerage Services Act 2000;
(v) any other law governing building construction, plumbing
and swimming pool safety;
(l) any Agency or government body responsible for the following:
(i) aboriginal housing;
-- 126 of 149 --
Part 10 Infringement notice offences
Electrical Safety Regulations 2024 117
(ii) government employee housing;
(iii) remote communities and homelands;
(iv) town camps;
(m) local government councils;
(n) any person performing a function corresponding to the
Electrical Safety Regulator in a State, another Territory, the
Commonwealth or New Zealand.
(3) Despite anything to the contrary in the Information Act 2002, the
Electrical Safety Regulator is authorised to share information under
this regulation that would be considered personal and confidential
information under that Act.
(4) A person who receives information shared by the Electrical Safety
Regulator under this regulation must not intentionally disclose that
information to any other person, unless:
(a) the Electrical Safety Regulator requires or authorises the
disclosure; or
(b) the person who supplied the information authorises the
disclosure; or
(c) the disclosure is otherwise authorised or required by law; or
(d) the information is public knowledge.
(5) A person commits an offence if the person contravenes
subregulation (4).
Maximum penalty: 50 penalty units.
(6) An offence against subregulation (5) is an offence of strict liability.
Part 10 Infringement notice offences
201 Infringement notice offence and infringement amount payable
(1) An infringement notice offence is an offence against a provision
specified in Schedule 6.
(2) The infringement amount for an infringement notice offence is the
amount equal to the monetary value of the number of penalty units
specified for the offence in Schedule 6.
-- 127 of 149 --
Part 10 Infringement notice offences
Electrical Safety Regulations 2024 118
202 When infringement notice may be given
An inspector may give an infringement notice to a person if the
inspector believes on reasonable grounds that the person
committed an infringement notice offence.
203 Contents of infringement notice
(1) The infringement notice must specify the following:
(a) the name and address of the person to whom it is issued, if
known;
(b) the date the infringement notice is given to the person;
(c) the date and time of the infringement notice offence and the
place at which the infringement notice offence occurred;
(d) a description of the offence;
(e) the infringement amount payable for the offence;
(f) the enforcement agency to which the prescribed amount is
payable.
(2) The infringement notice must include a statement to the effect of
the following:
(a) the person may expiate the infringement notice offence and
avoid any further action in relation to the offence by paying the
infringement amount to the specified enforcement agency
within 28 days after the notice is given;
(b) the person may elect to have the offence dealt with by a court
by:
(i) completing a statement of election and giving it to the
specified enforcement agency; and
(ii) not paying the infringement amount;
(c) if the Fines and Penalties (Recovery) Act 2001 applies to the
infringement notice offence – enforcement action may be
taken under that Act if the person does nothing in response to
the notice.
(3) The infringement notice must include an appropriate form for
making the statement of election mentioned in
subregulation (2)(b)(i).
-- 128 of 149 --
Part 10 Infringement notice offences
Electrical Safety Regulations 2024 119
204 Effective date of payment methods
(1) Payment of the infringement amount by electronic means takes
effect when the amount is credited to the payee's bank account.
(2) Payment of the infringement amount by cheque takes effect when
the cheque is cleared on first presentation.
205 Expiation of offence
If the infringement amount for the infringement notice offence is
paid in accordance with the infringement notice, the alleged offence
is expiated and no further proceedings can be taken in relation to
the offence.
206 Withdrawal of infringement notice
(1) The Director may withdraw the infringement notice by written notice
given to the person.
(2) The notice must be given:
(a) within 28 days after the infringement notice is given to the
person; and
(b) before payment of the infringement amount.
207 Effect of Part
(1) This Part does not:
(a) prejudice or affect the start or continuation of a proceeding for
an infringement offence unless the offence is expiated; or
(b) limit the penalty that may be imposed by a court for the
offence; or
(c) prevent more than one infringement notice for the same
infringement offence being given to a person; or
(d) require an infringement notice to be given for an infringement
offence; or
(e) affect the liability of a person to be prosecuted in a court for an
infringement notice offence for which an infringement notice
was not given.
(2) If more than one infringement notice for the same offence is given
to a person, the person may expiate the offence by paying the
infringement amount in accordance with any of the notices.
-- 129 of 149 --
Schedule 1 Supervision of apprentices and trainees
Electrical Safety Regulations 2024 120
Schedule 1 Supervision of apprentices and trainees
regulation 57
Table 1 Electrical work
Type of electrical work Type of supervision for amount of experience
0 to 6
months
6 to 12
months
12 to 24
months
24 to 36
months
36 to 48
months
Install cable support and
mechanical protection Direct
Direct /
General
(level 1)
General
(level 1)
General
(level 2)
General
(level 2)
Lay wiring or cabling and terminate
accessories exceeding extra-low
voltage
Direct
Direct or
General
(level 1)
General
(level 1)
General
(level 1)
General
(level 2)
Install apparatus and equipment
exceeding extra-low voltage Direct Direct
Direct or
General
(level 1)
General
(level 1)
General
(level 2)
Maintain, troubleshoot and repair
faults associated with apparatus &
circuits exceeding extra-low
voltage (De-energise)
Direct Direct Direct
Direct or
General
(level 1)
General
(level 2)
Proving de-energisation of LV
Installations and Equipment (Verify
isolation from all sources of supply)
The person supervising is
responsible for proving isolation
before an apprentice with less than
24 months experience commences
the work but the apprentice should
be required to personally reconfirm
de-energisation on every occasion to
instil good working practices.
Direct
Direct or
General
(level 1) 1
Test LV apparatus & circuits (de-
energised) Direct Direct Direct
Direct or
General
(level 1)
General
(level 1) or
General
(level 2) 2
Undertake commissioning
procedures for LV
apparatus and associated circuits
(No access to
exposed LV)
Direct Direct Direct
Direct or
General
(level 1)
General
(level 2)
Testing for LV System integrity and
operability
(Energised LV)
Simulated
at RTO
only
Simulated
at RTO
only
Simulated
at RTO
only
Simulated
at RTO
only
Direct
Install & maintain explosion protect
equipment Direct Direct Direct
Direct or
General
(level 1)
General
(level 1)
Disconnecting and reconnecting
fixed wired
electrical equipment connected to
supply up to
1000 volts AC or 1500 volts DC
The person supervising is
responsible for proving isolation
before apprentice with less than
24 months experience commences
the work but the apprentice should
be required to personally reconfirm
de-energisation on every occasion to
instil good working practices.
Direct
Direct or
General
(level 1) 3
-- 130 of 149 --
Schedule 1 Supervision of apprentices and trainees
Electrical Safety Regulations 2024 121
Attaching flexible cords and plugs
for supply up to
1000 volts AC or 1500 volts DC
Direct Direct
Direct or
General
(level 1)
General
(level 1) or
General
(level 2)
General
(level 2)
Footnotes for Table 1
1 & 3 General (level 1) supervision should be restricted to apprentices who have completed
all relevant training and to jobs where the supervisor has completed a hazard
assessment and ensured the apprentice is competent to undertake the de-
energisation task.
2 General (level 2) supervision is only appropriate after successful completion of the
electrical installation safety testing component of training but all electrical apprentices
are to be competent in testing a full installation at the point of becoming eligible for a
licence
Abbreviations.
• LV means low voltage
• RTO means registered training organisation.
-- 131 of 149 --
Schedule 1 Supervision of apprentices and trainees
Electrical Safety Regulations 2024 122
Table 2 Other related work
Type of work
Type of supervision for amount of experience
0 to 6
months
6 to 12
months
12 to 24
months
24 to 36
months
36 to 48
months
Assembling and installing ELV and
non-electrical hardware or
equipment
Direct Direct or
General
(level 1)
General
(level 1)
General
(level 1)
General
(level 2)
Installing ELV cable support and
mechanical
protection
Direct Direct or
General
(level 1)
General
(level 1)
General
(level 1)
General
(level 2)
Lay ELV wiring or cabling and
terminate ELV
accessories
Direct Direct Direct or
General
(level 1)
General
(level 1)
General
(level 2)
Maintain, troubleshoot and repair
faults associated with ELV
Apparatus & circuits
Direct Direct Direct Direct or
General
(level 1)
General
(level 2)
Undertaking commissioning
procedures of ELV
apparatus and associated circuits
Direct Direct Direct Direct or
General
(level 1)
General
(level 2)
Testing ELV apparatus and circuits Direct Direct Direct Direct or
General
(level 1)
General
(level 2)
Handling non-flammable
refrigerants
Direct Direct General
(level 2)
General
(level 1)
General
(level 2)
Handling flammable refrigerants Direct Direct Direct General
(level 1)
General
(level 2)
Note for Table 2
ELV means extra-low voltage.
-- 132 of 149 --
Schedule 2 Proximity limits
Electrical Safety Regulations 2024 123
Schedule 2 Proximity limits
regulations 120 and 162
Column 1 Column 2 Column 3 Column 4
Voltage of conductor or
equipment Proximity limit A Proximity limit B Proximity limit C
(i) (ii)
Distance in metres
Not more than 1000 V 0 0.3 3.0 1.0
More than 1000 V but less
than 6.6 kV 0.3 0.6 3.0 2.0
6.6 kV or more but not
more than 33 kV 0.6 1.2 3.0 3.0
66 kV 1.0 2.0 4.0 4.0
132 kV 1.8 3.6 5.0 5.0
275 kV 2.5 5.0 6.0 6.0
-- 133 of 149 --
Schedule 3 Erection of building or structure in proximity to powerline
Electrical Safety Regulations 2024 124
Schedule 3 Erection of building or structure in proximity to powerline
regulation 163
Table 1 Proximity limits between powerline and building or structure
Direction Distance measured from nearest conductor (in metres) Distance measured from centre of pole (in metres)
U<1000 V U>1000 V U>1000 V
U<33 kV
U>3 3kV
U<66 kV
U>66 kV
U<132 kV
U>132 kV
U<275 kV
U>275 kV
U<330 kV
U>330 kV
U<500 kV
Insulated Bare Insulated Bare or
covered Bare Bare Bare Bare Bare
Neutral Active
With
earthed
screen
Without
earthed
screen
Single pole other
Vertically above those
parts of a building or
structure normally
accessible to persons (A)
2.7 2.7 3.7 2.7 3.7 4.5 N/A N/A N/A N/A N/A N/A
Vertically above those
parts of a building or
structure not normally
accessible to persons but
on which a person can
stand (B)
0.1 2.7 2.7 0.1 2.7 4.7 N/A N/A N/A N/A N/A N/A
In any other direction
from those parts of a
building or structure
normally accessible to
persons or that is not
normally accessible to
persons but on which a
0.1 0.9 1.5 0.1 1.5 3.1 13.0 15.0 20.0 25.0 30.0 38.0
-- 134 of 149 --
Schedule 3 Erection of building or structure in proximity to powerline
Electrical Safety Regulations 2024 125
person can stand (C)
In any direction from
those parts of a building
or structure not normally
accessible to persons (D)
0.1* 0.3* 0.6* 0.1 0.6 2.5 13.0 15.0 20.0 25.0 30.0 38.0
In any direction from
ground (G) Refer to Table 2 or 3 Refer to Table 2 Refer to Table 2
*This distance may be further reduced to allow for termination at the point of attachment.
-- 135 of 149 --
Schedule 3 Erection of building or structure in proximity to powerline
Electrical Safety Regulations 2024 126
FIGURE 1
1. Figure 1 illustrates the application of Table 1 to a particular structure.
The letters A to D refer to distances A to D as set out in Table 1. The
letter G refers to distance to ground of insulated cables.
2. The proximity limits specified in A and B of Table 1 must be maintained
above a horizontal line extending outward for the distance specified in
C from the outer extremities of those parts of any building or structure
on which a person can stand.
The above illustration applies to a
building if the height of the railing
(or similar) PLUS distance B is
greater than distance A
-- 136 of 149 --
Schedule 3 Erection of building or structure in proximity to powerline
Electrical Safety Regulations 2024 127
Table 2 Proximity limits from ground, lines other than insulated
powerlines
Nominal System Voltage (U) Distance to ground in any other direction
(in metres)
Over the
carriageway of
roads
Over land other
than carriageway
of roads
Over land not
traversable by
vehicles
Bare or insulated conductor or any
other cable U < 1 kV
Insulated conductor with earthed
screen U> 1 kV
5.5 5.5 4.5
Insulated conductor without
earthed screen U > 1 kV 6.0 5.5 4.5
Bare or covered conductor
1 kV < U < 33 kV
33 kV < U < 132 kV
132 kV < U < 275 kV
275 kV < U < 330 kV
330 kV > U < 500 kV
6.7
6.7
7.5
8.0
9.0
5.5
6.7
7.5
8.0
9.0
4.5
5.5
6.0
6.7
7.5
Table 3 Proximity limits for above ground powerlines and other
cable systems
Location of Line Clearance Distance
(in metres)
Over the centre of a road 5.5
Over any other part of a road 4.6
Over a footway or land which is likely to be used by
vehicles 3.0
Elsewhere 2.7
-- 137 of 149 --
Schedule 4 Proximity to powerlines
Electrical Safety Regulations 2024 128
Schedule 4 Proximity to powerlines
regulations 164, 166, 167 and 173
Table 1 Proximity limits between materials and powerlines or supporting structures
Direction of Distance Type and Voltage of Aerial Line (clearance distance in metres)
Other cable systems & powerlines
U< 1 kV
U > 1 kV
U < 33 kV
U > 33 kV
U < 132 kV
U > 132 kV
U < 275 kV
U > 275 kV
U < 330 kV
U > 330 kV
U < 500 kV
Distance between any material (other than
inflammable materials) and aerial lines:
(a) horizontal distance
(b) vertical distance
1.5
3.7
2.1
4.6
3.0
4.6
4.6
6.8
5.5
8.0
6.4
9.8
Distance between inflammable materials
and aerial lines:
(a) horizontal distances
(b) vertical distances
3.0
3.7
3.0
4.6
3.0
6.8
4.6
6.8
5.5
8.0
6.4
9.8
Distance between any material and
supporting structure:
(a) horizontal distances
(b) vertical distances
5.0
N/A
10.0
N/A
15.0
N/A
15.0
N/A
15.0
N/A
15.0
N/A
-- 138 of 149 --
Schedule 4 Proximity to powerlines
Electrical Safety Regulations 2024 129
Table 2 Proximity limits between operation of machine, vehicle or vessel with elevating component or shear
legs and power lines
Type and voltage or aerial
line
U < 1 kV
ABC
U < 1 kV
Bare and covered conductor
U >1 kV
U < 33 kV
U > 33 kV
U < 132 kV
U > 132 kV
U < 275 kV
U > 275 kV
U < 330 kV
U > 275 kV
U < 500 kV
Clearance distance in all
directions in metres 0.5 1.0 1.5 3.0 4.0 6.0 8.0
-- 139 of 149 --
Schedule 4 Proximity to powerlines
Electrical Safety Regulations 2024 130
Table 3 Proximity limits between erection of circuits or other cable
systems and powerlines
Type or Circuit and Voltage Proximity limits (in metres)
Upper Circuit Lower Circuit Attached to a
common
structure
Between Structures
No wind condition Wind condition
LV aerial line Private powerline (LV) and other
cable systems
0.9 Not permitted Not permitted
LV aerial line LV aerial line 0.38 0.6 0.38
Aerial lines
U > 1 kV
U < 33 kV
Private powerline (LV) and other
cable systems 1.8 Not permitted Not permitted
Aerial lines
U > 1 kV
LV aerial line or, Aerial lines <
11 kV
1.2 1.2 0.6
Aerial lines
U > 1 kV
U < 33 kV
LV aerial line or,
Aerial lines < 33 kV 1.2 1.2 0.75
Aerial lines
U > 33 kV
U < 66 kV
Private powerline (LV) and other
cable systems 2.4 Not permitted Not permitted
Aerial lines
U > 33 kV
U < 66 kV
LV aerial line or,
aerial lines < 66 kV 1.8 1.8 1.2
Aerial lines
U > 66 kV
U < 132 kV
Aerial lines < 33 kV
Not permitted Not permitted Not permitted
Aerial lines
U > 132 kV
Aerial lines > 33 kV Not permitted Not permitted Not permitted
Notes relating to Table 3
1 Any combination of circuits not shown in Table 3 are not permitted.
2 For the purpose of Table 3:
(a) no wind refers to:
(i) undercrossing conductors at 15°C with no wind blowing; and
(ii) overcrossing conductors at maximum design temperature with no
wind blowing; and
(b) wind refers to:
(i) undercrossing conductors at 15°C, and displaced by a 500 Pa
horizontal wind at right angles to the undercrossing conductors; and
(ii) overcrossing conductors at maximum design temperature and not
displaced by wind.
-- 140 of 149 --
Schedule 4 Proximity to powerlines
Electrical Safety Regulations 2024 131
Table 4 Proximity limits between circuits on different supporting
structures crossings)
Nominal System Voltage (U) Proximity limits
(in any direction in metres)
OTHER CABLE SYSTEM OR
INSULATED CONDUCTOR U < 1 KV 0.1
bare conductor U < 1 kV 0.6
Insulated conductor 1 kV < U < 33 kV 0.6
bare conductor 1 kV < U < 33 kV 1.2
33 KV < U < 66 KV 1.8
66 kV < U < 132 kV 2.4
132 kV < U < 275 kV 2.8
275 kV < U < 330 kV 3.8
330 kV < U < 500 kV 5.2
Table 5 Proximity limits distance between load being transported
and aerial lines
Nominal System Voltage (U) Proximity limits (in metres)
Vertical distance Horizontal distance
Other cable system or
insulated conductor U < 1 kV 0.33 0.33
1 kV < U < 132 kV 2.4 1.5
132 kV < U < 275 kV 3.2 4.6
275 kV < U < 330 kV 3.7 4.6
330 kV < U < 500 kV 4.7 5.5
-- 141 of 149 --
Schedule 5 Fees and refunds
Electrical Safety Regulations 2024 132
Schedule 5 Fees and refunds
Part 1 Fees
regulation 195(1)
Item Fee
application for an electrical work
licence (unrestricted)
350 revenue units
application for an electrical work
licence (restricted)
350 revenue units
application to renew an electrical
work licence (unrestricted)
350 revenue units
application to renew an electrical
work licence (restricted)
350 revenue units
application for an electrical
contractor licence
1 year licence – 350 revenue units
2 year licence – 600 revenue units
3 year licence – 785 revenue units
application to renew an electrical
contractor licence
1 year licence – 350 revenue units
2 year licence – 600 revenue units
3 year licence – 785 revenue units
registration of an apprentice 50 revenue units
application for a trainee permit 50 revenue units
copy of licence or trainee permit 50 revenue units
-- 142 of 149 --
Schedule 5 Fees and refunds
Electrical Safety Regulations 2024 133
Part 2 Refunds
regulation 195(3)
Item Refund
application to issue, renew or
reinstate electrical work licence
(unrestricted)
280 revenue units
application to issue, renew or
reinstate electrical work licence
(restricted)
280 revenue units
application to issue, renew or
reinstate electrical contractor
licence
1 year licence – 280 revenue units
2 year licence – 480 revenue units
3 year licence – 640 revenue units
-- 143 of 149 --
Schedule 6 Infringement notice penalties
Electrical Safety Regulations 2024 134
Schedule 6 Infringement notice penalties
regulation 201
Item Provision Infringement
amount
Electricity Safety Act 2022
1 section 45(1) 64 penalty units for an
individual, other than as a
person conducting a business
or undertaking or as an officer
of a person conducting a
business or undertaking
130 penalty units for an
individual as a person
conducting a business or
undertaking or as an officer of
a person conducting a
business or undertaking
640 penalty units for a body
corporate
2 section 47(1) and (2) 20 penalty units
3 section 48(1) 10 penalty units
4 section 48(2) 20 penalty units
5 section 60(2) 80 penalty units
6 sections 65(1), 66(1) and
67(1) and (3)
100 penalty units
7 sections 68(1) and (2), 71(2)
and (5), 73(2) and 74(2)
10 penalty units
8 sections 75(2) and 76(2) 20 penalty units
9 section 76(3) 10 penalty units
10 section 82(1), (2) and (3) 400 penalty units for a body
corporate
11 section 84(2) and (3) 20 penalty units
-- 144 of 149 --
Schedule 6 Infringement notice penalties
Electrical Safety Regulations 2024 135
Item Provision Infringement
amount
12 section 85(1) 40 penalty units
13 section 85(2) and (3) 20 penalty units
14 section 86(1) 40 penalty units
15 section 86(3) 10 penalty units
16 section 86(4) 20 penalty units
17 sections 87(2) and 88(2) 40 penalty units
18 sections 89(6) and 91(4) 20 penalty units
19 section 94(1) 10 penalty units
20 section 94(4) 5 penalty units
21 section 100(1) 10 penalty units
22 sections 161(6), 168(4)
and (7) and 169(5)
20 penalty units
23 section 171(4) 10 penalty units
24 sections 180(1) and 181 20 penalty units
25 sections 182(1) and (2) and
183(1)
40 penalty units
26 section 187(2) 20 penalty units
27 section 190(2) 50 penalty units
28 section 197(2) 100 penalty units
29 section 198(6) 200 penalty units
30 sections 201(2) and 202(2) 100 penalty units
31 section 203(3) 10 penalty units
32 section 205(3) 100 penalty units
33 section 211(3) 10 penalty units
34 section 211(5) 20 penalty units
-- 145 of 149 --
Schedule 6 Infringement notice penalties
Electrical Safety Regulations 2024 136
Item Provision Infringement
amount
Electrical Safety Regulations 2024
35 regulations 12(5), 13(2), 41(4)
and 46(3)
10 penalty units
36 regulation 49(2) 1 penalty unit
37 regulation 50(3) 4 penalty units
38 regulations 58(1) and 63(2) 10 penalty units
39 regulation 64(3) 4 penalty units
40 regulations 67(2) and 68(2) 10 penalty units
41 regulation 69(5) 3 penalty units
42 regulations 70(6), 71(2), 73(3),
74(2), 75(2), 76(3), 77(5),
78(2), 79(2), 80(5), 81(3),
85(2), 86(3), 87(2), 90(2),
91(2), 92(5), 93(2), 94(5),
95(2), 96(2) and 98(3)
10 penalty units
43 regulation 99(3) 20 penalty units
44 regulations 100(3), 101(3),
102(2), 103(3), 104(3), 105(2),
106(2) and 108(3)
10 penalty units
45 regulations 109(2), 110(7),
111(4), 112(6), 113(5) and
115(3)
3 penalty units
46 regulation 116(6) 10 penalty units
47 regulations 117(6) and 118(5) 3 penalty units
48 regulations 119(2), 120(7),
121(2), 122(5), 123(2), 124(3),
125(2), 127(2) and 129(1)
10 penalty units
49 regulations 130(2) and 131(2) 3 penalty units
50 regulation 132(2) 10 penalty units
-- 146 of 149 --
Schedule 6 Infringement notice penalties
Electrical Safety Regulations 2024 137
Item Provision Infringement
amount
51 regulation 133(2) 4 penalty units
52 regulations 134(2), 135(3),
136(3), 137(4), 138(5), 139(2)
and 140(2)
10 penalty units
53 regulation 141(4) 1 penalty unit
54 regulations 142(2), 143(4),
144(7) and 145(6)
10 penalty units
55 regulations 146(2), 147(6),
148(2) and 149(3)
1 penalty unit
56 regulations 150(4), 151(3) and
152(6)
10 penalty units
57 regulation 153(5) 1 penalty unit
58 regulation 154(5) 10 penalty units
59 regulation 155(4) 5 penalty units
60 regulations 156(4), 157(3),
158(2) and 159(3)
10 penalty units
61 regulation 160(2) 8 penalty units
62 regulations 162(4), 164(6),
166(4), 167(2), 168(2), 169(2),
170(2) and 171(2)
10 penalty units
63 regulation 172(3) 5 penalty units
64 regulations 173(3) and 175(2) 10 penalty units
65 regulation 176(2) 5 penalty units
66 regulation 178(4) 10 penalty units
67 regulation 182(2) 20 penalty units
68 regulation 191(3) 10 penalty units
-- 147 of 149 --
Schedule 6 Infringement notice penalties
Electrical Safety Regulations 2024 138
Item Provision Infringement
amount
69 regulation 196(2) and (5) 5 penalty units
70 regulations 198(1) and 200(5) 10 penalty units
-- 148 of 149 --
ENDNOTES
Electrical Safety Regulations 2024 139
ENDNOTES
1 KEY Key to abbreviations
amd = amended od = order
app = appendix om = omitted
bl = by-law pt = Part
ch = Chapter r = regulation/rule
cl = clause rem = remainder
div = Division renum = renumbered
exp = expires/expired rep = repealed
f = forms s = section
Gaz = Gazette sch = Schedule
hdg = heading sdiv = Subdivision
ins = inserted SL = Subordinate Legislation
lt = long title sub = substituted
nc = not commenced
2 LIST OF LEGISLATION
Electrical Safety Regulations 2024 (SL No. 14, 2024)
Date made 27 June 2024
Commenced 1 July 2024 (r 2 and s 2(2) Electrical Safety Act 2022 (Act
No. 3, 2022)
Electrical Safety Amendment Regulations 2026 (SL No. 13, 2026)
Date made 27 May 2026
Commenced 28 May 2026 (r 2)
3 LIST OF AMENDMENTS
r 3 amd No. 13, 2026, r 4
pt 8 hdg sub No. 13, 2026, r 5
pt 8
div 1 hdg rep No. 13, 2026, r 5
rr 184 – 185 rep No. 13, 2026, r 5
pt 8
div 2 hdg rep No. 13, 2026, r 5
rr 186 – 190 rep No. 13, 2026, r 5
r 191 sub No. 13, 2026, r 5
sch 6 sub No. 13, 2026, r 6
-- 149 of 149 --