Victorian Energy Efficiency Target Amendment (Ductwork and Standby Power Controllers) Regulations 2011
Authorised by the Chief Parliamentary Counsel
Authorised Version
i
Victorian Energy Efficiency Target Amendment
(Ductwork and Standby Power Controllers)
Regulations 2011
S.R. No. 56/2011
TABLE OF PROVISIONS
Regulation Page
1 Objective 1
2 Authorising provision 1
3 Principal Regulations 1
4 Definitions 2
5 Prescribed activities 3
6 New Schedules 28 to 29 inserted 3
SCHEDULE 28—Replacement of Gas Heating Ductwork 3
PART A—CRITERIA 3
PART B—CALCULATION OF CARBON DIOXIDE
EQUIVALENTS OF GREENHOUSE GASES 4
PART C—TIME AT WHICH ACTIVITY UNDERTAKEN 5
SCHEDULE 29—Installation of Standby Power Controller 7
PART A—CRITERIA 7
PART B—CALCULATION OF CARBON DIOXIDE
EQUIVALENTS OF GREENHOUSE GASES 10
PART C—TIME AT WHICH ACTIVITY UNDERTAKEN 13
═══════════════
ENDNOTES 14
-- 1 of 15 --
Authorised by the Chief Parliamentary Counsel
Authorised Version
1
STATUTORY RULES 2011
S.R. No. 56/2011
Victorian Energy Efficiency Target Act 2007
Victorian Energy Efficiency Target Amendment
(Ductwork and Standby Power Controllers)
Regulations 2011
The Governor in Council makes the following Regulations:
Dated: 5 July 2011
Responsible Minister:
MICHAEL O'BRIEN
Minister for Energy and Resources
MATTHEW McBEATH
Clerk of the Executive Council
1 Objective
The objective of these Regulations is to amend the
Victorian Energy Efficiency Target Regulations
2008 to provide for new prescribed activities.
2 Authorising provision
These Regulations are made under section 75 of
the Victorian Energy Efficiency Target Act
2007.
3 Principal Regulations
In these Regulations, the Victorian Energy
Efficiency Target Regulations 20081 are called the
Principal Regulations.
-- 2 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
2
Authorised by the Chief Parliamentary Counsel
4 Definitions
In regulation 4 of the Principal Regulations insert
the following definitions—
"Active State, in relation to a computer, means a
state in which the computer is carrying out
useful work in response to prior or
concurrent—
(a) user input; or
(b) instruction over a network;
approved laboratory means a laboratory that is
accredited by the National Association of
Testing Authorities or registered by an
authority recognised by the National
Association of Testing Authorities under a
mutual recognition agreement;
mains power switching device means a relay or
other device that switches the power to the
controlled appliances on or off;
master/slave arrangement, in relation to a
standby power controller, means an
arrangement where the standby power
controller is connected to an uncontrolled
master appliance, whose current or power is
solely used to control the electrical input to
controlled appliances connected to the
standby power controller;
Off Mode, in relation to a computer, means the
lowest power state, of the computer when the
computer is switched off by the user, but
does not include Sleep Mode;
Sleep Mode, in relation to a computer, means a
low power state that the computer is capable
of entering automatically after a period of
inactivity or by manual selection;".
r. 4
-- 3 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
3
Authorised by the Chief Parliamentary Counsel
5 Prescribed activities
(1) In regulation 6(z) of the Principal Regulations for
"26." substitute "26;".
(2) After regulation 6(z) of the Principal Regulations,
insert—
"(za) decommissioning existing gas heating
ductwork that is connected to a ducted gas
heater and installing in its place a product
that complies with the criteria specified in
Part A of Schedule 28;
(zb) installing a standby power controller being a
product that complies with the criteria
specified in Part A of Schedule 29." .
6 New Schedules 28 to 29 inserted
After Schedule 27 of the Principal Regulations
insert—
"__________________
SCHEDULE 28
Regulation 6(za)
REPLACEMENT OF GAS HEATING DUCTWORK
Prescribed activity under regulation 6(za): decommissioning existing gas
heating ductwork that is connected to a ducted gas heater and installing in its
place a product that complies with the criteria specified in Part A of
Schedule 28.
PART A—CRITERIA
Item
28A Ductwork that—
(a) is tested and certified by an approved laboratory as
complying with AS 4254–2002; and
r. 5
-- 4 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
4
Authorised by the Chief Parliamentary Counsel
(b) is insulated using bulk insulation that is certified by
an accredited body or approved laboratory as
complying with AS/NZS 4859.1:2002 and achieves
a minimum R-value of R1.5 when measured in
accordance with AS/NZS 4859.1:2002; and
(c) is longitudinally labelled at intervals of not more
than 1·5 meters, in characters that are clearly legible
and at least 18mm high stating—
(i) the duct manufacturer's or duct assembler's
name; and
(ii) the diameter of the duct core; and
(iii) the R-value of the bulk insulation; and
(iv) whether the ductwork complies with
AS 4254–2002; and
(d) is installed and supported in accordance with the
requirements set out in AS 4254–2002; and
(e) uses fittings that achieve at least the R-value
specified by Table 3.12.5.2 of the Building Code.
PART B—CALCULATION OF CARBON DIOXIDE
EQUIVALENTS OF GREENHOUSE GASES
The method and variables to be used to calculate in tonnes the
carbon dioxide equivalent of greenhouse gases to be reduced by
the decommissioning of existing gas heating ductwork and the
installation of ductwork referred to in an item in Part A is
determined by multiplying the abatement factor for that item by
the regional factor applying to the place where the ductwork is
installed.
r. 6
-- 5 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
5
Authorised by the Chief Parliamentary Counsel
The following are the abatement factors and regional factors for
each item in Part A:
Item
28A Abatement factor:
(a) if the ductwork is connected to a heater
that has a rated output heating capacity of
not less than 10 and not more than 18kW: 12·13;
(b) if the ductwork is connected to a heater
that has a rated output heating capacity of
more than 18 and not more than 28kW: 15·40;
(c) if the ductwork is connected to a heater
that has a rated output heating capacity of
more than 28kW: 18·86;
(d) if the ductwork is installed but the output
heating capacity of the heater is not known: 12·13.
28A Regional factor:
(a) If the product is installed in metropolitan
Victoria: 1·00;
(b) If the product is installed in regional
Victoria—climatic region Mild: 1·00;
(c) If the product is installed in regional
Victoria—climatic region Cold: 1·61;
(d) If the product is installed in regional
Victoria—climatic region Hot: 0·71.
PART C—TIME AT WHICH ACTIVITY UNDERTAKEN
Item
28A At the beginning of whichever of the following days is
later—
(a) the day on which the installation of the product is
completed; or
r. 6
-- 6 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
6
Authorised by the Chief Parliamentary Counsel
(b) the day on which a ducted gas heater connected to
the product is first able to produce and deliver
ducted gas heating.
__________________
r. 6
-- 7 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
7
Authorised by the Chief Parliamentary Counsel
SCHEDULE 29
Regulation 6(zb)
INSTALLATION OF STANDBY POWER CONTROLLER
Prescribed activity under regulation 6(zb): Installing a standby power
controller being a product that complies with the criteria specified in Part A
of Schedule 29.
PART A—CRITERIA
Item
29A A product that when installed in an information
technology environment is able to automatically reduce
the standby energy consumption of home information
technology equipment connected to it, and—
(a) when tested by an approved laboratory in
accordance with a laboratory test approved by the
ESC, is determined to be suitable for use in an
information technology environment and, in
particular, is demonstrated to—
(i) be suitable for use with desktop and
notebook computers that are not more than
2 years old; and
(ii) be capable of controlling the power of at
least 4 appliances (whether directly or
indirectly); and
(iii) be fitted with a mains power switching
device that is rated to a minimum of
50 000 switching cycles; and
(iv) have an electric power consumption of not
more than 1 watt when tested in accordance
with the laboratory test; and
(v) automatically disconnect mains power from
controlled appliances when the master
computer is switched to Off Mode; and
r. 6
-- 8 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
8
Authorised by the Chief Parliamentary Counsel
(vi) automatically reconnect mains power to the
controlled appliances when the master
computer enters Active State; and
(vii) not be reliant on a universal serial bus
connection to determine the operating mode
of the computer; and
(viii) be able, at the time of installation, to
disconnect mains power from or reconnect
mains power to controlled appliances
without having to be set up to have those
functions assigned to the operation of an
existing appliance remote control; and
(ix) not require manual setting of a current or
power threshold; and
(b) is connected to at least 2 controlled appliances at the
time of installation.
29B A product that when installed in an audio visual
environment is able to automatically reduce the standby
energy consumption of home audio visual equipment
connected to it, and—
(a) when tested by an approved laboratory in
accordance with a laboratory test approved by the
ESC, is determined to be suitable for use in an audio
visual environment and, in particular, is
demonstrated to—
(i) be capable of controlling the power of at
least 4 appliances (whether directly or
indirectly); and
(ii) be fitted with a mains power switching
device that is rated to a minimum of
50 000 switching cycles; and
(iii) have an electric power consumption of not
more than 1 watt when tested in accordance
with the laboratory test; and
r. 6
-- 9 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
9
Authorised by the Chief Parliamentary Counsel
(iv) automatically disconnect mains power from
controlled appliances—
(A) in the case of a product that relies on a
master/slave arrangement—when the
master appliance is turned off;
(B) in the case of a product that relies on
sensing infra-red signals from the
remote controls of controlled
appliances—after a period of time
specified in the laboratory test when the
product does not detect infra-red
signals from those remote controls that
are triggered by a user; and
(v) automatically reconnect mains power to the
controlled appliances only when—
(A) in the case of a product that relies on a
master/slave arrangement—when the
master appliance is turned on;
(B) in the case of a product that relies on
sensing infra-red signals from the
remote controls of controlled
appliances—when any of the controlled
appliances are operated by a user; and
(vi) be able, at the time of installation, to
disconnect mains power from or reconnect
mains power to controlled appliances
without having to be set up to have those
functions assigned to the operation of an
existing appliance remote control; and
(vii) not require manual setting of a current or
power threshold; and
(b) is connected to at least 2 controlled appliances at the
time of installation.
r. 6
-- 10 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
10
Authorised by the Chief Parliamentary Counsel
PART B—CALCULATION OF CARBON DIOXIDE
EQUIVALENTS OF GREENHOUSE GASES
The method and variables to be used to calculate in tonnes the
carbon dioxide equivalent of greenhouse gases to be reduced by
the installation of a product or products referred to in an item in
Part A is determined by the sum of the figures obtained by
multiplying the number (not exceeding 4) of products installed
in the premises under each item in Part A, by the abatement
factor for that item.
The following are the abatement factors and regional factors for
each item in Part A:
Item
29A Abatement Factor:
(a) A product that satisfies the minimum
eligibility criteria for an item in Part A: 1·0;
(b) A product that satisfies the minimum
eligibility criteria for item 29A in Part A and
is capable of automatically disconnecting
mains power to controlled appliances when
the master computer enters Sleep Mode, and
has been demonstrated, to the satisfaction of
the ESC, to be capable of achieving abatement
of at least 2·0 tonnes over a 10 year period
and has been subjected to a field trial
approved by the ESC: 2·0;
(c) A product that satisfies the minimum
eligibility criteria for item 29A in Part A
and is capable of automatically disconnecting
mains power to controlled appliances when
the master computer enters Sleep Mode, and
has been demonstrated, to the satisfaction of
the ESC, to be capable of achieving abatement
of at least 3·0 tonnes over a 10 year period and
has been subjected to a field trial approved
by the ESC: 3·0;
r. 6
-- 11 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
11
Authorised by the Chief Parliamentary Counsel
(d) A product that satisfies the minimum
eligibility criteria for item 29A in Part A and
is capable of automatically disconnecting
mains power to controlled appliances when
the master computer enters Sleep Mode, and
has been demonstrated, to the satisfaction of
the ESC, to be capable of achieving abatement
of at least 4·0 tonnes over a 10 year period and
has been subjected to a field trial approved
by the ESC: 4·0;
(e) A product that satisfies the minimum
eligibility criteria for item 29A in Part A and
is capable of automatically disconnecting
mains power to controlled appliances when
the master computer enters Sleep Mode, and
has been demonstrated, to the satisfaction of
the ESC, to be capable of achieving abatement
of at least 5·0 tonnes over a 10 year period and
has been subjected to a field trial approved
by the ESC: 5·0;
(f) A product that satisfies the minimum
eligibility criteria for item 29A in Part A and
is capable of automatically disconnecting
mains power to controlled appliances when
the master computer enters Sleep Mode, and
has been demonstrated, to the satisfaction of
the ESC, to be capable of achieving abatement
of at least 6·0 tonnes over a 10 year period and
has been subjected to a field trial approved
by the ESC: 6·0.
29B Abatement Factor:
(a) A product that satisfies the minimum
eligibility criteria for item 29B in Part A: 1·0;
(b) A product that satisfies the minimum
eligibility criteria for item 29B in Part A
and does not operate solely on the basis of a
master/slave arrangement, and has been
r. 6
-- 12 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
12
Authorised by the Chief Parliamentary Counsel
demonstrated, to the satisfaction of the ESC,
to be capable of achieving abatement of at least
2·0 tonnes over a 10 year period and has been
subjected to a field trial approved by the ESC: 2·0;
(c) A product that satisfies the minimum
eligibility criteria for item 29B in Part A
and does not operate solely on the basis of a
master/slave arrangement, and has been
demonstrated, to the satisfaction of the ESC,
to be capable of achieving abatement of at least
3·0 tonnes over a 10 year period and has been
subjected to a field trial approved by the ESC: 3·0;
(d) A product that satisfies the minimum
eligibility criteria for item 29B in Part A
and does not operate solely on the basis of a
master/slave arrangement, and has been
demonstrated, to the satisfaction of the ESC,
to be capable of achieving abatement of at least
4·0 tonnes over a 10 year period and has been
subjected to a field trial approved by the ESC: 4·0;
(e) A product that satisfies the minimum
eligibility criteria for item 29B in Part A
and does not operate solely on the basis of a
master/slave arrangement, and has been
demonstrated, to the satisfaction of the ESC,
to be capable of achieving abatement of at least
5·0 tonnes over a 10 year period and has been
subjected to a field trial approved by the ESC: 5·0;
(f) A product that satisfies the minimum
eligibility criteria for item 29B in Part A
and does not operate solely on the basis of a
master/slave arrangement, and has been
demonstrated, to the satisfaction of the ESC,
to be capable of achieving abatement of at least
6·0 tonnes over a 10 year period and has been
subjected to a field trial approved by the ESC: 6·0.
r. 6
-- 13 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
13
Authorised by the Chief Parliamentary Counsel
PART C—TIME AT WHICH ACTIVITY UNDERTAKEN
Item
29A–29B At the beginning of the day on which the installation
of the product or products is completed.".
═══════════════
r. 6
-- 14 of 15 --
S.R. No. 56/2011
Victorian Energy Efficiency Target Amendment (Ductwork and Standby
Power Controllers) Regulations 2011
14
Authorised by the Chief Parliamentary Counsel
ENDNOTES
1 Reg. 4: S.R. No. 158/2008 as amended by S.R. Nos 109/2010, 127/2010
and 31/2011.
——
Table of Applied, Adopted or Incorporated Matter
The following table of applied, adopted or incorporated matter is included in
accordance with the requirements of regulation 5 of the Subordinate Legislation
Regulations 2004.
In this table, Principal Regulations means the Victorian Energy Efficiency
Target Regulations 2008.
Statutory rule
provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 7
which inserts new
Schedule 28 in the
Principal Regulations
Australian Standard
"Ductwork for air-handling
systems in buildings"
AS 4254–2002 published by
Standards Australia on
5 April 2002 and reissued
incorporating Amendment
Nos 1 and 2 in October 2004.
Australian/New Zealand
Standard "Materials for the
thermal insulation of
buildings–Part 1:
General criteria and
technical provisions"
AS/NZS 4859.1:2002
published by Standards
Australia/Standards New
Zealand on 15 October 2002
and reissued incorporating
Amendment No. 1 in
December 2006.
Building Code of Australia
The whole
The whole
Table 3.12.5.2
Endnotes
-- 15 of 15 --