Building Amendment (Bushfire Safety) Regulations 2010
i
Building Amendment (Bushfire Safety) Regulations
2010
S.R. No. 82/2010
TABLE OF PROVISIONS
Regulation Page
1 Objective 1
2 Authorising provisions 1
3 Commencement 1
4 New regulation 309A inserted 2
309A Requirements for permits involving bushfire safety
matters 2
5 New regulations 808 and 809 inserted 3
808 Water supply for fire fighting purposes 3
809 Access for emergency vehicles 5
6 Part 1 of Schedule 4 amended 8
═══════════════
ENDNOTES 9
-- 1 of 10 --
1
STATUTORY RULES 2010
S.R. No. 82/2010
Building Act 1993
Building Amendment (Bushfire Safety) Regulations
2010
The Governor in Council makes the following Regulations:
Dated: 24 August 2010
Responsible Minister:
JUSTIN MADDEN
Minister for Planning
MATTHEW McBEATH
Assistant Clerk of the Executive Council
1 Objective
The objective of these Regulations is to amend the
Building Regulations 2006 in relation to the
reconstruction of Class 1a buildings that were
destroyed in bushfires between 1 January 2009
and 31 March 2009 (inclusive).
2 Authorising provisions
These Regulations are made under sections 7, 261
and 262 of, and Part 1 of Schedule 1 to, the
Building Act 1993.
3 Commencement
These Regulations come into operation on
30 August 2010.
-- 2 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
2
4 New regulation 309A inserted
After regulation 309 of the Building Regulations
2006 1 insert—
"309A Requirements for permits involving
bushfire safety matters
(1) The report and consent of the chief officer
must be obtained to an application for a
building permit if—
(a) the permit involves the provision of a
static water supply or access to
emergency vehicles for a Class 1a
building destroyed in bushfires between
1 January 2009 and 31 March 2009
(inclusive); and
(b) the allotment on which the building is
located is subject to a Wildfire
Management Overlay under the
planning scheme approved under the
Planning and Environment Act 1987
as in force from time to time applying
to that allotment; and
(c) a permit is not required under the
planning scheme for the construction of
the building; and
(d) the static water supply and access for
emergency vehicles do not comply with
the requirements of regulation 808
or 809 (as the case requires).
(2) In a report under subregulation (1), the chief
officer may consent to a variation of the
requirements of regulation 808 or 809 if the
chief officer is satisfied that a satisfactory
degree of bushfire safety is achieved.".
r. 4
-- 3 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
3
5 New regulations 808 and 809 inserted
After regulation 807 of the Building
Regulations 2006 insert—
"808 Water supply for fire fighting purposes
(1) This regulation applies if—
(a) construction of a Class 1a building is
proposed on the same allotment as a
Class 1a building that was destroyed in
bushfires between 1 January 2009 and
31 March 2009 (inclusive); and
(b) the allotment is subject to a Wildfire
Management Overlay under the
planning scheme approved under the
Planning and Environment Act 1987
as in force from time to time applying
to that allotment; and
(c) a permit is not required under the
planning scheme for the construction of
the building.
(2) A static water supply for fire fighting
purposes must be provided on an allotment
to which this regulation applies in
accordance with this regulation.
(3) The static water supply must be—
(a) used solely for fire fighting purposes;
and
(b) able to hold 10 000 litres in onsite static
storage located on the allotment; and
(c) located within 60m of the building; and
(d) situated so as to enable emergency
services vehicles access to within 4m of
the water supply outlet.
r. 5
-- 4 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
4
(4) If the static water supply is not able to be
readily seen from the building or access
driveway, a sign in or to the like effect of the
sign illustrated in the diagram at the foot of
this regulation must be located on the
allotment so that it is—
(a) easily seen by persons operating
emergency vehicles; and
(b) pointing in the direction of the water
supply.
Diagram—Sign indicating static water supply location
(5) All below-ground water pipelines relating to
the static water supply must be installed to
the depths of—
(a) 300mm if subject to vehicle traffic; or
(b) 75mm if under a house or concrete
slab; or
(c) 225mm in all other locations.
(6) All fixed above-ground water pipelines and
fittings relating to the static water supply,
including the water supply, must be
constructed of non-corrosive and
r. 5
-- 5 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
5
non-combustible materials, or be protected
from the effects of radiant heat and flame.
(7) If the static water supply is above ground,
the following additional requirements
apply—
(a) there must be at least one pipe fitting no
less than 64mm, 3 thread/25mm ×
50mm nominal bore British Standard
Pipe (BSP) round male coupling;
(b) all pipe work and valving between the
water supply and the water supply
outlet must be no less than 50mm
nominal bore;
(c) if the water supply is less than 20m
from the building, each outlet must face
away from the building to allow access
during emergencies.
(8) This regulation does not apply if—
(a) the bushfire attack level of the
allotment is determined as LOW or
12·5 in accordance with Clause 2.2 or
Appendix B (as the case requires) of
AS 3959 Construction of buildings in
bushfire-prone areas, as incorporated
for the time being by the BCA; and
(b) there is a fire hydrant connected to a
reticulated water supply within 120m of
the rear of the building.
809 Access for emergency vehicles
(1) This regulation applies if—
(a) construction of a Class 1a building is
proposed on the same allotment as a
Class 1a building that was destroyed in
bushfires between 1 January 2009 and
31 March 2009 (inclusive); and
r. 5
-- 6 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
6
(b) that allotment is subject to a Wildfire
Management Overlay under the
planning scheme approved under the
Planning and Environment Act 1987
as in force from time to time applying
to that allotment; and
(c) a permit is not required under the
planning scheme for the construction of
the building.
(2) The driveway to the building must be
designed to allow an emergency vehicle
access in accordance with this regulation.
(3) The driveway must be designed so that—
(a) any curves in the driveway have a
minimum inner radius of 10m; and
(b) the average grade for the driveway be
no more than 1 in 7 (14⋅4%) (8⋅1o ) with
a maximum of no more than 1 in 5
(20%) (11⋅3 o
) for no more than 50m;
and
(c) any dips in the driveway have no more
than a 1 in 8 (12⋅5%) (7⋅1o
) entry and
exit angle.
(4) If the driveway from the road to the building
or static water supply for fire fighting
purposes (within the meaning of
regulation 808), including gates, bridges and
culverts, is greater than 30m in length, the
driveway must—
(a) be designed, constructed and
maintained for a load limit of at least
15 tonnes and be of all weather
construction; and
r. 5
-- 7 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
7
(b) provide a minimum trafficable width of
3⋅5m, and be clear of encroachments
4m vertically.
(5) If the driveway is longer than 100m, a
turning area for emergency vehicles close to
the building must be provided for by either—
(a) a turning circle with a minimum radius
of 8m; or
(b) the driveway encircling the building; or
(c) a T head or Y head with a minimum
forced surface of each leg being 8m in
length measured from the centre point
of the head and 4m trafficable width.
Note
The following diagrams illustrate aspects of
subregulation (5)(c).
Diagram—Y head Diagram—T head
(6) If the driveway is longer than 200m, passing
bays must be provided every 200m and
must—
(a) be 20m long; and
(b) have a trafficable width of 6m.".
r. 5
8m 8m
4m
8m 8m
4m 4m
-- 8 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
8
6 Part 1 of Schedule 4 amended
In Part 1 of Schedule 4 to the Building
Regulations 2006 after item 11 insert—
"
The following bushfire safety
matters if those matters do not
meet the requirements of
regulation 808 or 809—
reg. 309A(1)
12 static water supply for fire
fighting purposes
13 emergency vehicle access
".
═══════════════
r. 6
-- 9 of 10 --
S.R. No. 82/2010
Building Amendment (Bushfire Safety) Regulations 2010
9
ENDNOTES
1 Reg. 4: S.R. No. 68/2006. Reprint No. 1 incorporating amendments as at
1 September 2009. Reprinted to S.R. No. 105/2009 and subsequently
amended by S.R. Nos 25/2009, 105/2009, 139/2009, 15/2010, 32/2010
and 50/2010.
——
Table of Applied, Adopted or Incorporated Matter Required by the
Subordinate Legislation Regulations 2004
Note that the following table of applied, adopted or incorporated matter is
included in accordance with the requirements of regulation 5 of the Subordinate
Legislation Regulations 2004.
In this table—
BCA means the Building Code of Australia published by the Australian
Building Codes Board—
(a) as amended or remade from time to time; and
(b) as amended by the Victorian Appendix to that Code published by
that Board as that Appendix is amended or remade from time to
time.
Statutory Rule
Provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 5 which
inserts regulation 808
into the Building
Regulations 2006
Australian Standard 3959—
2009 Construction of
buildings in bushfire-prone
areas, published by Standards
Australia on 10 March 2009,
as amended on 16 November
2009 as incorporated for the
time being by the BCA.
Clause 2.2
Appendix B
Endnotes