Building Amendment (Private Bushfire Shelter Construction) Interim Regulations 2010
i
Building Amendment (Private Bushfire Shelter
Construction) Interim Regulations 2010
S.R. No. 32/2010
TABLE OF PROVISIONS
Regulation Page
1 Objective 1
2 Authorising provisions 1
3 Commencement 1
4 Principal Regulations 2
5 Revocation 2
6 New regulation 115 substituted 2
115 Private bushfire shelter construction requirements 2
7 New Division 3 of Part 12 substituted 8
Division 3—Private bushfire shelter maintenance and
operation 8
1221 Application of this Division 8
1222 Private bushfire shelter maintenance and operation 8
8 Revocation of regulations 8
9 Revocation of definition 9
10 Expiry 9
═══════════════
ENDNOTES 10
-- 1 of 12 --
1
STATUTORY RULES 2010
S.R. No. 32/2010
Building Act 1993
Building Amendment (Private Bushfire Shelter
Construction) Interim Regulations 2010
The Lieutenant-Governor as the Governor's deputy with the
advice of the Executive Council makes the following
Regulations:
Dated: 25 May 2010
Responsible Minister:
JUSTIN MADDEN
Minister for Planning
TOBY HALLIGAN
Clerk of the Executive Council
1 Objective
The objective of these Regulations is to amend the
Building Regulations 2006 in relation to the
construction of private bushfire shelters that may,
as a last resort, be used for protection during a
bushfire event.
2 Authorising provisions
These Regulations are made under sections 7,
9 and 262 of, and Part 1 of Schedule 1 to, the
Building Act 1993.
3 Commencement
(1) These Regulations (except regulations 8 and 9)
come into operation on 28 May 2010.
-- 2 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
2
(2) Regulations 8 and 9 come into operation on
26 May 2011.
4 Principal Regulations
In these Regulations, the Building Regulations
2006 1 are called the Principal Regulations.
5 Revocation
The Building Amendment (Private Bushfire
Shelter Construction) Interim Regulations 2009 2
are revoked.
6 New regulation 115 substituted
For regulation 115 of the Principal Regulations
substitute—
'115 Private bushfire shelter construction
requirements
(1) Volume One of the BCA applies as if—
(a) in clause A1.1, after the definition of
"Primary building element" there
were inserted—
"Private bushfire shelter means a
building that may as a last resort
provide shelter for occupants from
the immediate life threatening
effects of a bushfire event.";
(b) in clause A3.2, after the paragraph
relating to Class 10b, there were
inserted—
"(c) Class 10c — a building being a
private bushfire shelter.".
(2) Volume Two of the BCA applies as if—
(a) in clause 1.1.1—
r. 4
-- 3 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
3
(i) after the definition of "Breaking
surf" the following definition
were inserted—
"Bushfire event has the same
meaning as in clause 1.8 of
the ABCB Performance
Standard for Private Bushfire
Shelters 2010 Part 1.";
(ii) after the definition of
"Performance Requirement" the
following definition were
inserted—
"Private bushfire shelter means
a building that may as a last
resort provide shelter for
occupants from the
immediate life threatening
effects of a bushfire event.";
(b) in clause 1.3.2, after the paragraph
relating to Class 10b, there were
inserted—
"(c) Class 10c — a building being a
private bushfire shelter.";
(c) in clause 1.3.3—
(i) in paragraphs (a) and (b), for
"10a and 10b" there were
substituted "10a, 10b and 10c";
(ii) after paragraph (c) there were
inserted—
"(d) paragraph (c) does not apply
if the minor use relates to a
Class 10c part of a Class 1
building or a Class 10a
building.";
r. 6
-- 4 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
4
(d) In Table 1.4.1 in clause 1.4.1, after the
reference to "ABCB 2006 Protocol for
House Energy Rating Software,
Version 2006.1" there were inserted—
"ABCB 2010 Performance Standard for
Private Bushfire Shelters 2010 Part 1";
(e) for clause O2.3(c) there were
substituted—
"(c) protect a building from the effects
of a bushfire; and
(d) reduce the likelihood of fatalities
arising from occupants of Class 1
buildings not evacuating those
buildings prior to exposure from a
bushfire event.".
(f) after clause F2.3.4 there were
inserted—
"F2.3.4A Private bushfire shelter
A Class 10c building must provide
shelter to occupants from direct
and indirect actions of a
bushfire.";
(g) after performance requirement P2.3.4
there were inserted—
"P2.3.4A Private bushfire shelter
A Class 10c building associated
with a Class 1 building must be
designed and constructed to
provide a tenable environment for
occupants during the passage of
untenable conditions arising from
a bushfire event, appropriate to the
following—
r. 6
-- 5 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
5
(a) location of the Class 10c
building relative to fire
hazards including—
(i) predominant
vegetation;
(ii) adjacent buildings and
structures;
(iii) allotment boundaries;
(iv) other combustible
materials;
(b) occupancy of the Class 10c
building;
(c) bushfire intensity having
regard for the bushfire attack
level;
(d) fire intensity from adjacent
buildings and structures,
allotment boundaries and
other combustible materials;
(e) ready access to the Class 10c
building from the associated
Class 1 building and
occupant egress after the
fire;
(f) tenability within the Class
10c building for the
estimated maximum period
of occupancy;
(g) generation of smoke, heat
and toxic gases from
materials used to construct
the Class 10c building;
r. 6 r. 6
-- 6 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
6
(h) structural and fire loads
and actions to which the
Class 10c building may
reasonably be subjected
having regard to—
(i) the topography between
the Class 10c building
and the predominant
vegetation or other fire
hazards;
(ii) the distance between
the Class 10c building
and the predominant
vegetation or other fire
hazards;
(iii) the size of the potential
fire source and fire
intensity;
(iv) wind loading;
(v) potential impact from
debris such as falling
tree limbs;
(i) degree of external signage
identifying the location of
the Class 10c building;
(j) degree of internal signage in
the Class 10c building
identifying the design
capacity and maximum
period of occupancy;
(k) degree of occupant
awareness of outside
environmental conditions;
r. 6
-- 7 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
7
(l) degree of essential
maintenance of the Class 10c
building.
Terms used in this performance
requirement that are not defined in
Volume 2 of the BCA have the
same meaning as in ABCB
Performance Standard for Private
Bushfire Shelters 2010 Part 1.".
(h) before
"
B. Acceptable construction
practice
"
there were inserted—
"
AB. Acceptable design and
construction manual for Class 10c
buildings
3.7.4.0A
Performance requirement P2.3.4A
is satisfied for a Class 10c
building associated with a Class 1
building if it—
(a) is designed and constructed
in accordance with ABCB
Performance Standard for
Private Bushfire Shelters
2010 Part 1; and
(b) does not form part of, or is
not attached to, a Class 1
building or a Class 10a
building.".'.
r. 6
-- 8 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
8
7 New Division 3 of Part 12 substituted
For Division 3 of Part 12 of the Principal
Regulations substitute—
"Division 3—Private bushfire shelter
maintenance and operation
1221 Application of this Division
This Division applies to a Class 10c building
associated with a Class 1 building.
1222 Private bushfire shelter maintenance and
operation
(1) The occupier of an allotment containing a
Class 10c building associated with a Class 1
building must ensure that the Class 10c
building is maintained in a state that enables
the Class 10c building to fulfil its purpose.
Penalty: 20 penalty units.
(2) The occupier of an allotment containing a
Class 10c building associated with a Class 1
building must ensure that any paths of travel
from the Class 1 building to the Class 10c
building are maintained in an efficient
condition and kept readily accessible,
functional and clear of obstruction so that
access to the Class 10c building is
maintained.
Penalty: 20 penalty units.".
8 Revocation of regulations
Regulations 113A and 115 and Division 3 of
Part 12 of the Principal Regulations are revoked.
r. 7
-- 9 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
9
9 Revocation of definition
In regulation 105 of the Principal Regulations, the
definition of bushfire performance requirement
is revoked.
10 Expiry
These Regulations expire on 27 May 2011.
═══════════════
r. 9
-- 10 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
10
ENDNOTES
1 Reg. 4: S.R. No. 68/2006. Reprint No. 1 incorporating amendments as at
1 September 2009. Reprinted to S.R. No. 105/2009 and subsequently
amended by S.R. Nos 25/2009, 105/2009, 139/2009 and 15/2010.
2 Reg. 5: S.R. No. 139/2009.
——
Table of Applied, Adopted or Incorporated Matter Required by the
Subordinate Legislation Regulations 2004
Note that the following table of applied, adopted or incorporated matter is
included in accordance with the requirements of regulation 5 of the Subordinate
Legislation Regulations 2004.
In this table—
BCA means the Building Code of Australia published by the Australian
Building Codes Board—
(a) as amended or remade from time to time; and
(b) as amended by the Victoria Appendix to that Code published
by that Board as that Appendix is amended or remade from
time to time.
Statutory Rule
Provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 6 which
inserts the definition
of bushfire
performance
requirement into the
Building Regulations
2006
Volume Two of the BCA Performance
Requirement
P2.3.4A
Endnotes
-- 11 of 12 --
S.R. No. 32/2010
Building Amendment (Private Bushfire Shelter Construction) Interim
Regulations 2010
11
Statutory Rule
Provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 8 which
inserts regulation 115
into the Building
Regulations 2006
Volume One of the BCA
Volume Two of the BCA
ABCB Performance Standard
for Private Bushfire Shelters
2010 Part 1, published by the
Australian Building Codes
Board on 30 April 2010 as
incorporated by the BCA
Clauses A1.1
and A.3.2
Clauses 1.0.10,
1.1.1, 1.3.2,
1.3.3, 1.4.1,
Table 1.4.1,
O2.3(c) and (d),
F2.3.4A,
3.7.4.0A and
Performance
Requirement
P2.3.4A
The whole
-- 12 of 12 --