Building Amendment (Bushfire Construction) Further Interim Regulations 2009
i
Building Amendment (Bushfire Construction)
Further Interim Regulations 2009
S.R. No. 105/2009
TABLE OF PROVISIONS
Regulation Page
1 Objective 1
2 Authorising provisions 1
3 Commencement 1
4 Prescribed reporting authorities and prescribed matters 2
5 New regulation 309A inserted 2
309A Requirements for permits involving bushfire safety
matters 2
6 New regulations 808 and 809 inserted 3
808 Water supply for fire fighting purposes 3
809 Access for emergency vehicles 5
7 New Part 1A of Schedule 4 inserted 7
PART 1A—PRESCRIBED MATTERS REPORTED ON BY
CHIEF OFFICER 7
8 Prescribed reporting authorities and prescribed matters 8
9 Revocation of regulation 114 8
10 Revocation of inserted regulations 8
11 Expiry 8
═══════════════
ENDNOTES 9
-- 1 of 10 --
1
STATUTORY RULES 2009
S.R. No. 105/2009
Building Act 1993
Building Amendment (Bushfire Construction)
Further Interim Regulations 2009
The Governor in Council makes the following Regulations:
Dated: 1 September 2009
Responsible Minister:
JUSTIN MADDEN
Minister for Planning
TOBY HALLIGAN
Clerk of the Executive Council
1 Objective
The objective of these Regulations is to amend the
Building Regulations 2006 in relation to the
reconstruction of Class 1a buildings that were
destroyed in bushfires between 1 January 2009
and 31 March 2009 (inclusive).
2 Authorising provisions
These Regulations are made under sections 7, 261
and 262 of, and Part 1 of Schedule 1 to, the
Building Act 1993.
3 Commencement
(1) These Regulations (except regulations 8, 9
and 10) come into operation on 1 September 2009.
(2) Regulation 9 comes into operation on 9 March
2010.
-- 2 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
2
(3) Regulations 8 and 10 come into operation on
30 August 2010.
4 Prescribed reporting authorities and prescribed
matters
In regulation 308(2)(a) of the Building
Regulations 2006 1 after the words "Part 1" insert
the words "or Part 1A".
5 New regulation 309A inserted
After regulation 309 of the Building Regulations
2006 insert—
"309A Requirements for permits involving
bushfire safety matters
(1) The report and consent of the chief officer
must be obtained to an application for a
building permit—
(a) if the permit involves the provision of a
static water supply or access to
emergency vehicles for a Class 1a
building destroyed in bushfires between
1 January 2009 and 31 March 2009
(inclusive); and
(b) if the allotment on which the building is
located is in a Wildfire Management
Overlay under the relevant planning
scheme approved under the Planning
and Environment Act 1987—
if those matters do not comply with the
requirements of regulation 808 or 809 (as the
case requires).
(2) In a report under subregulation (1), the chief
officer may consent to a variation of the
requirements of regulation 808 or 809 if the
chief officer is satisfied that a satisfactory
degree of bushfire safety is achieved.".
r. 4
-- 3 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
3
6 New regulations 808 and 809 inserted
After regulation 807 of the Building Regulations
2006 insert—
"808 Water supply for fire fighting purposes
(1) Subject to subregulation (7), if the
construction of a Class 1a building is
proposed on the same allotment as a Class 1a
building that was destroyed in bushfires
between 1 January 2009 and 31 March 2009
(inclusive) and that allotment is in a Wildfire
Management Overlay under the relevant
planning scheme approved under the
Planning and Environment Act 1987, a
static water supply, such as a water tank,
must be provided on the allotment in
accordance with this regulation.
(2) The static water supply must be—
(a) used solely for fire fighting purposes;
and
(b) able to hold 10 000 litres in onsite static
storage located on the allotment; and
(c) located within 60 m of the building;
and
(d) situated so as to enable emergency
services vehicles access to within 4 m
of the water supply outlet.
(3) If the static water supply is not able to be
readily seen from the building or access
driveway a sign in or to the like effect of the
sign illustrated in the diagram at the foot of
this regulation must be located on the
allotment so that it is—
(a) easily seen by persons operating
emergency vehicles; and
r. 6
-- 4 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
4
(b) pointing in the direction of the water
supply.
Diagram—Sign indicating static water supply location
(4) All below-ground water pipelines relating to
the static water supply must be installed to
the depths of—
(a) 300 mm if subject to vehicle traffic; or
(b) 75 mm if under a house or concrete
slab, or
(c) 225 mm in all other locations.
(5) All fixed above-ground water pipelines and
fittings relating to the static water supply,
including the water supply, must be
constructed of non-corrosive and non-
combustible materials, or be protected from
the effects of radiant heat and flame.
(6) If the static water supply is above ground,
the following additional requirements
apply—
(a) there must be at least one pipe fitting no
less than 64 mm, 3 thread/25 mm ×
50 mm nominal bore British Standard
Pipe (BSP) round male coupling;
r. 6
-- 5 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
5
(b) all pipe work and valving between the
water supply and the water supply
outlet must be no less than 50 mm
nominal bore;
(c) if the water supply is less than 20 m
from the building, each outlet must face
away from the building to allow access
during emergencies.
(7) Subregulation (1) does not apply if—
(a) the bushfire attack level of the
allotment is determined as LOW or
12·5 under clause 2.2 or Appendix B
(as the case requires) in accordance
with Section 2 of AS 3959—2009
Construction of buildings in bushfire-
prone areas, published 10 March 2009,
as published from time to time; and
(b) there is a fire hydrant connected to a
reticulated water supply within 120 m
of the rear of the building.
809 Access for emergency vehicles
(1) If the construction of a Class 1a building is
proposed on the same allotment as a Class 1a
building that was destroyed in bushfires
between 1 January 2009 and 31 March 2009
(inclusive) and that allotment is in a Wildfire
Management Overlay under a planning
scheme approved under the Planning and
Environment Act 1987, the driveway to the
building must be designed to allow an
emergency vehicle access in accordance with
this regulation.
(2) The driveway must be designed so that as a
minimum—
(a) any curves in the driveway have a
minimum inner radius of 10 m; and
r. 6
-- 6 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
6
(b) the average grade for the driveway be
no more than 1 in 7 (14⋅4%) (8⋅1o ) with
a maximum of no more than 1 in 5
(20%) (11⋅3 o
) for no more than 50 m;
and
(c) any dips in the driveway have no more
than a 1 in 8 (12⋅5%) (7⋅1o
) entry and
exit angle.
(3) If the driveway from the road to the building
or static water supply for fire fighting
purposes (within the meaning of
regulation 808), including gates, bridges and
culverts, is greater than 30 m in length, the
driveway must—
(a) be designed, constructed and
maintained for a load limit of at least
15 tonnes and be of all weather
construction; and
(b) provide a minimum trafficable width of
3⋅5 m, and be clear of encroachments
4 m vertically.
(4) If the driveway is longer than 100 m, a
turning area for emergency vehicles close to
the building must be provided for by either—
(a) a turning circle with a minimum radius
of 8 m; or
(b) the driveway encircling the building; or
(c) a T head or Y head with a minimum
forced surface of each leg being 8 m in
length measured from the centre point
of the head and 4 m trafficable width.
r. 6
-- 7 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
7
Note
The following diagrams illustrate aspects of
subregulation (4)(c).
Diagram—Y head Diagram—T head
(5) If the length of the driveway is greater than
200 m passing bays must be provided and
be—
(a) 20 m long; and
(b) provided every 200 m, with a
trafficable width of 6 m.".
7 New Part 1A of Schedule 4 inserted
After Part 1 of Schedule 4 to the Building
Regulations 2006 insert—
"PART 1A
PRESCRIBED MATTERS REPORTED ON BY
CHIEF OFFICER
Column 1 Column 2 Column 3
Item
Prescribed matters to be
reported on by chief officer
Regulation
reference
The following bushfire safety
matters if those matters do
not meet the requirements of
regulation 808 or 809—
309A(1)
r. 7
-- 8 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
8
Column 1 Column 2 Column 3
Item
Prescribed matters to be
reported on by chief officer
Regulation
reference
1 static water supply for fire
fighting purposes
2 emergency vehicle access
".
8 Prescribed reporting authorities and prescribed
matters
In regulation 308(2)(a) of the Building
Regulations 2006 after the words "Part 1" omit
the words "or Part 1A".
9 Revocation of regulation 114
Regulation 114 of the Building Regulations 2006
is revoked.
10 Revocation of inserted regulations
Regulations 309A, 808, 809 of, and Part 1A of
Schedule 4 to, the Building Regulations 2006 are
revoked.
11 Expiry
These Regulations expire on 31 August 2010.
═══════════════
r. 8
-- 9 of 10 --
S.R. No. 105/2009
Building Amendment (Bushfire Construction) Further Interim Regulations
2009
9
ENDNOTES
1 Reg. 4: S.R. No. 68/2006 as amended by S.R. Nos 136/2006, 115/2007,
126/2008, 25/2009 and 79/2009.
——
Table of Applied, Adopted or Incorporated Matter Required by the
Subordinate Legislation Regulations 2004
Note that the following table of applied, adopted or incorporated matter is
included in accordance with the requirements of regulation 5 of the Subordinate
Legislation Regulations 2004.
Statutory Rule
Provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 6 which
inserts regulation 808
into the Building
Regulations 2006
Australian Standard 3959—
2009 Construction of
buildings in bushfire-prone
areas, published by Standards
Australia on 10 March 2009
Section 2
clause 2.2
Appendix B