Electricity Safety (Network Assets) (Amendment) Regulations 2005
i
Electricity Safety (Network Assets) (Amendment)
Regulations 2005
S.R. No. 158/2005
TABLE OF PROVISIONS
Regulation Page
1. Objective 1
2. Authorising provisions 1
3. Principal Regulations 1
4. Definitions 2
5. Minimum distances between aerial lines and the ground 2
6. Minimum distances between aerial lines and parts of buildings
and structures 2
7. Minimum distances between aerial lines and parts of railway
systems 3
8. Minimum distances between aerial lines and parts of tramway
systems 4
9. Minimum distances between conductors of aerial lines 4
10. Construction of underground lines 5
11. Mechanical protection of underground lines above the ground 5
12. Pole mounted substations 5
13. Earthing and electrical protection 5
14. Warning signs 5
15. Marking of network assets 6
16. Standard of upstream networks 6
17. Minimum distances between parts of buildings, structures,
scaffolding and posts and aerial lines of network operators 6
18. Minimum distances between materials and network assets 7
19. Minimum distances between vehicles, plant, machinery and
vessels and overhead network assets 7
20. Minimum distances between transported loads and overhead
network assets 7
21. Minimum distances between conductors of aerial lines and
network assets 8
22. Minimum distances between people and conductors of aerial
lines of network operators 8
23. Placing of materials 8
24. Exemption for existing aerial lines 8
═══════════════
ENDNOTES 10
-- 1 of 11 --
1
STATUTORY RULES 2005
S.R. No. 158/2005
Electricity Safety Act 1998
Electricity Safety (Network Assets) (Amendment)
Regulations 2005
The Lieutenant-Governor as the Governor's Deputy with the
advice of the Executive Council makes the following
Regulations:
Dated: 7 December 2005
Responsible Minister:
THEO THEOPHANOUS
Minister for Energy Industries
RUTH LEACH
Clerk of the Executive Council
1. Objective
The objective of these Regulations is to make
miscellaneous amendments to improve the
operation of the Electricity Safety (Network
Assets) Regulations 1999.
2. Authorising provisions
These Regulations are made under sections 149,
151 and 157 of the Electricity Safety Act 1998.
3. Principal Regulations
In these Regulations, the Electricity Safety
(Network Assets) Regulations 19991 are called the
Principal Regulations.
-- 2 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
2
4. Definitions
In regulation 5(1) of the Principal Regulations—
(a) after the definition of "live" insert—
' "load" in relation to a vehicle, means
goods, livestock or people;';
(b) for the definition of "minimum depth"
substitute—
' "minimum depth" in relation to a part of
an underground line that is below the
surface of the ground, means the
minimum depth of that part of the line
from the uppermost surface of the line
or the conduit and pipe enclosing the
line;'.
5. Minimum distances between aerial lines and the
ground
In Table 13.2 of the Principal Regulations, in the
first column, for "Alternating current bare or
covered" substitute "Bare or covered (other than
d.c. traction conductors)".
6. Minimum distances between aerial lines and parts
of buildings and structures
(1) In regulation 14(1) of the Principal Regulations,
for "carrying alternating current" substitute
"(other than a d.c. traction conductor)".
(2) In regulation 14(2) of the Principal Regulations,
for "An aerial line carrying direct current"
substitute "A d.c. traction conductor".
(3) In Table 14.1 of the Principal Regulations—
(a) in the heading omit "carrying alternating
current";
r. 4
-- 3 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
3
(b) in the first column, for "Alternating current
aerial line" (wherever occurring) substitute
"Aerial line (other than a d.c. traction
conductor)";
(c) in the column headed "132kV < U < 275kV",
for "4600mm" substitute "4500mm".
(4) In Table 14.2 of the Principal Regulations—
(a) in the heading, for "aerial lines carrying
direct current" substitute "d.c. traction
conductors";
(b) in the first column, for "Direct current aerial
line" substitute "d.c. traction conductor".
7. Minimum distances between aerial lines and parts
of railway systems
(1) In regulation 16 of the Principal Regulations
insert the following heading—
"Minimum distances between aerial lines and
parts of railway systems".
(2) In regulations 16(1) and 16(2) of the Principal
Regulations, for "d.c. train traction conductor"
(wherever occurring) substitute "train d.c.
traction conductor".
(3) In regulations 16(2) and 16(3) and in the heading
to Table 16 of the Principal Regulations omit
"carrying alternating current".
(4) In Table 16 of the Principal Regulations—
(a) in the first column, for "Alternating current
aerial line" substitute "Aerial line (other
than d.c. traction conductors)";
(b) for "U < 1kV" substitute "U < 1kV".
r. 7
-- 4 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
4
8. Minimum distances between aerial lines and parts
of tramway systems
(1) In regulation 17 of the Principal Regulations—
(a) insert the following heading—
"Minimum distances between aerial lines
and parts of tramway systems";
(b) for "carrying alternating current" substitute
"(other than a d.c. traction conductor)".
(2) In Table 17 of the Principal Regulations—
(a) in the heading omit "carrying alternating
current";
(b) in the first column, for "Alternating current
aerial line" substitute "Aerial line (other
than a d.c. traction conductor)".
9. Minimum distances between conductors of aerial
lines
In Table 18 of the Principal Regulations—
(a) in row 2, for "900mm" substitute "600mm";
(b) in rows 6 and 7, for "U < 11kV" substitute
"U < 11kV";
(c) in rows 8 and 9, for "U < 33kV" substitute
"U < 33kV"; and
(d) in rows 10 and 11, for "U < 66kV"
substitute "U < 66kV".
r. 8
-- 5 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
5
10. Construction of underground lines
In the Principal Regulations—
(a) in regulation 20(4)(a) omit "rigid,";
(b) in Table 20, insert the following row at the
foot of the Table—
" Direct current
66kV < U < 500kV 1000mm 1000mm 1000mm".
11. Mechanical protection of underground lines above
the ground
In regulation 21(3) of the Principal Regulations
omit "rigid".
12. Pole mounted substations
In regulation 22(3)(b) of the Principal
Regulations, for "and is less than 200 millimetres"
substitute "and is 200 millimetres or less".
13. Earthing and electrical protection
In regulation 23(6)(c) of the Principal
Regulations, for "aerial service line is" substitute
"aerial service line was".
14. Warning signs
In regulation 24(3) of the Principal Regulations—
(a) after "If an aerial line crosses water" insert
"at a point where the water is navigable";
(b) in paragraph (c), for "20 metres" substitute
"at a point that is between 20 and
100 metres".
r. 10
-- 6 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
6
15. Marking of network assets
For regulation 26(2) of the Principal Regulations
substitute—
"(2) Underground lines, other than extra low
voltage lines, buried in any part of a road or
footpath must be identified by an orange
marker tape in accordance with
AS/NZS 2648.1 at least 150 millimetres
above the uppermost surface of the line or
the conduit or pipe enclosing the line.
(3) Sub-regulation (2) does not apply to an
underground line that is installed by the
process of boring.".
16. Standard of upstream networks
In regulation 29 of the Principal Regulations, for
"AS 2926" substitute "AS/NZS 60038".
17. Minimum distances between parts of buildings,
structures, scaffolding and posts and aerial lines of
network operators
In Table 38 of the Principal Regulations—
(a) for "Alternating current aerial lines"
(wherever occurring) substitute "All other
aerial lines";
(b) for "d.c. street" (wherever occurring)
substitute "tram d.c.";
(c) for "d.c. train" (wherever occurring)
substitute "train d.c.";
(d) in the third row, for "In any direction from
those parts a building," substitute "In any
direction (other than vertical) from those
parts of a building,";
(e) in the fourth row, after "In any direction"
insert "(other than vertical)".
r. 15
-- 7 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
7
18. Minimum distances between materials and network
assets
(1) In regulation 39(a) of the Principal Regulations,
after "switch yard" insert "of a network operator".
(2) In Table 39 of the Principal Regulations—
(a) for "Alternating current aerial lines"
substitute "All other aerial lines";
(b) in the column headed "132kV < U < 275kV",
for "4600mm" (wherever occurring)
substitute "4500mm".
19. Minimum distances between vehicles, plant,
machinery and vessels and overhead network assets
In Table 40 of the Principal Regulations, for
"Alternating current" substitute "All other".
20. Minimum distances between transported loads and
overhead network assets
(1) In regulation 41 of the Principal Regulations, after
"at any time," insert "any part of the vehicle or".
(2) For regulation 41(b) of the Principal Regulations
substitute—
"(b) the maximum height and width of the loaded
vehicle; and".
(3) In Table 41 of the Principal Regulations—
(a) omit "alternating current";
(b) for "U < 1500V d.c. traction conductor"
substitute "U < 1kV bare conductor and
U < 1500V d.c. traction conductor";
(c) for "U < 66kV" substitute "U ≤ 66kV";
(d) for "700mm" substitute "600mm";
(e) for "6400mm" substitute "6000mm".
r. 18
-- 8 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
8
21. Minimum distances between conductors of aerial
lines and network assets
(1) In Table 42.1 of the Principal Regulations—
(a) in rows 7 and 8, for "U < 11kV" substitute
"U < 11kV";
(b) in rows 9, 10 and 11, for "U < 33kV"
substitute "U < 33kV";
(c) in rows 12, 13 and 14, for "U < 66kV"
substitute "U < 66kV";
(d) in row 14, for "line < 66kV" substitute
"line < 66kV".
(2) In Table 42.2 of the Principal Regulations, for
"Alternating current" substitute "All other".
22. Minimum distances between people and conductors
of aerial lines of network operators
In the heading to column 2 of Table 43 of the
Principal Regulations omit "alternating current".
23. Placing of materials
In regulation 44 of the Principal Regulations, for
"substation or switchyard" (wherever occurring)
substitute "substation, switchroom or switchyard
of a network operator".
24. Exemption for existing aerial lines
(1) In regulation 47(1) of the Principal Regulations,
after "an aerial service line over a driveway"
insert "or land traversable by vehicles".
(2) For regulation 47(3) of the Principal Regulations
substitute—
'(3) On the replacement of an aerial service line
that fails to comply with the minimum
clearance specified by the Electricity Safety
(Network Assets) Regulations 1997, if a
r. 21
-- 9 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
9
network operator demonstrates to the Office
that it is not reasonably able to comply with
regulation 13, the service line may be
replaced in its existing position, and the
replacement may be maintained in that
position for up to 24 months after the
replacement occurs, if the network operator
advises the occupier in writing, within
5 business days after the replacement, of the
need for the network operator to ensure that
the aerial service line is made compliant with
the minimum clearance required by
Table 13.1 within 24 months after the service
line replacement.
(4) In this regulation, "occupier", in relation to
premises to which the aerial service line is
attached, means a person who is in actual
occupation of the premises or, if no-one is in
actual occupation of the premises, the owner
of the premises.'.
═══════════════
r. 24
-- 10 of 11 --
S.R. No. 158/2005
Electricity Safety (Network Assets) (Amendment) Regulations
2005
10
ENDNOTES
1 Reg. 3: S.R. No. 141/1999.
——
Table of Applied, Adopted or Incorporated Matter Required by the
Subordinate Legislation Regulations 2004
Note that the following table of applied, adopted or incorporated matter is
included in accordance with the requirements of regulation 5 of the Subordinate
Legislation Regulations 2004.
Statutory Rule
Provision
Title of applied, adopted or
incorporated document
Matter in
applied,
adopted or
incorporated
document
Regulation 15 AS/NZS 2648.1
Australian/New Zealand
Standard, "Underground
marking tape – Non-detectable
tape" published jointly by
Standards Australia and
Standards New Zealand as
amended from time to time.
The whole
Regulation 16 AS/NZS 60038
Australian/New Zealand
Standard, "Standard voltages"
published jointly by Standards
Australia and Standards New
Zealand as amended from time
to time.
The whole
Endnotes