Electricity Safety (Installations) (Amendment) Regulations 2001
i
Electricity Safety (Installations) (Amendment)
Regulations 2001
S.R. No. 3/2001
TABLE OF PROVISIONS
Regulation Page
1. Objectives 1
2. Authorising provisions 2
3. Commencement 2
4. Principal Regulations 2
5. Amendment of authorising provisions 2
6. Amendment of objectives 2
7. Definitions 2
8. Electrician's licence 5
9. Supervised worker's licence 6
10. Wiring methods 6
11. Private electric lines 11
12. Testing 12
13. Regulation 406 substituted 12
14. Certificates of compliance 14
15. Reporting of incidents 14
16. Exemptions 14
17. New Part 4A inserted 15
PART 4A—WIRING AND SAFETY REQUIREMENTS 15
Division 1—Duties of owners and operators of high voltage
electrical installations and supply networks of small gauge
railway or tramway systems 15
417. General requirements—high voltage electrical
installations 15
418. General requirements—small gauge railway or tramway
systems 17
419. Minimum distances between aerial lines and the ground
or water 18
420. Aerial lines and the façade of buildings 19
421. Minimum distances between aerial lines and buildings or
structures 21
422. Minimum distances between aerial lines and parts of
small gauge railway systems 25
423. Minimum distances between aerial lines and parts of
small gauge tramway systems 26
-- 1 of 53 --
Regulation Page
ii
424. Minimum distances between aerial lines 27
425. Substations 28
426. Poles and towers 29
427. Marking of electric lines 29
Division 2—Duties of the public 29
428. Application 29
429. Sporting activities 30
430. Aircraft, kites etc. 30
431. Entangled objects 31
432. Blasting and fires 31
433. Protection of underground electrical installations from
damage 31
434. Excavating 32
435. Altering levels 33
436. Minimum distances between parts of buildings,
structures, scaffolding and posts and aerial lines 34
437. Minimum distances between materials and certain aerial
lines 36
438. Minimum distances between parts of vehicles, plant,
machinery and aerial lines 37
439. Minimum distances between transported loads and aerial
lines 38
440. Minimum distances between aerial lines 38
441. Minimum distances between persons and aerial lines 40
442. Tree clearing 40
443. Damage and interference 41
444. Placing of materials 42
Division 3—Exclusions and exemptions 42
445. Exclusions 43
446. Exemptions 43
18. Examinations for registration 44
19. Examinations for licensing 44
20. New regulation 703 inserted 44
703 Transitional exemption for existing aerial lines 45
21. New Fees 45
22. New Schedule 4 substituted 45
═══════════════
ENDNOTES 49
-- 2 of 53 --
1
STATUTORY RULES 2001
S.R. No. 3/2001
Electricity Safety Act 1998
Electricity Safety (Installations) (Amendment)
Regulations 2001
The Governor in Council makes the following Regulations:
Dated: 30 January 2001
Responsible Minister:
CANDY BROAD
Minister for Energy and Resources
HELEN DOYE
Clerk of the Executive Council
1. Objectives
The objectives of these Regulations are to—
(a) make further provision for—
(i) the methods to be followed in carrying
out electrical installation work;
(ii) the quality of materials, fittings and
apparatus to be used in connection with
electrical installations;
(iii) fees, penalties and other matters
authorised by the Electricity Safety
Act 1998;
(b) prescribe standards for the design,
construction, operation and maintenance of
electrical installations;
-- 3 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
2
(c) provide for the protection of persons from
risk, and property from damage, associated
with the transmission and distribution of
electricity.
2. Authorising provisions
These Regulations are made under sections 149,
152, 156 and 157 of the Electricity Safety Act
1998.
3. Commencement
These Regulations come into operation on
1 February 2001.
4. Principal Regulations
In these Regulations, the Electricity Safety
(Installations) Regulations 19991 are called the
Principal Regulations.
5. Amendment of authorising provisions
In regulation 101 of the Principal Regulations,
after "sections" insert "149,".
6. Amendment of objectives
In regulation 102 of the Principal Regulations,
after paragraph (g) insert—
"(h) prescribe standards for the design,
construction, operation and maintenance of
electrical installations;
(i) provide for the protection of persons from
risk, and property from damage, associated
with the transmission and distribution of
electricity.".
7. Definitions
r. 2
-- 4 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
3
In regulation 105 of the Principal Regulations—
(a) insert the following definitions—
' "aerial line" has the same meaning as
"aerial conductor" in the
Australian/New Zealand Wiring Rules;
"AS" means an Australian Standard issued
by Standards Australia, as published or
amended from time to time;
"AS/NZS" means an Australian/New
Zealand Standard issued jointly by
Standards Australia and Standards New
Zealand, as published or amended from
time to time;
"Australian/New Zealand Wiring Rules"
means the Australian/New Zealand
Standard Electrical Installations
(known as the Australian/New Zealand
Wiring Rules), AS/NZS 3000 published
jointly by Standards Australia and
Standards New Zealand as published or
amended from time to time;
"conductor" has the same meaning as it has
in the Australian/New Zealand Wiring
Rules;
"d.c. traction conductor" means an
overhead tram trolley wire, a train
contact wire or a tram or train catenary
or traction feeder that operates on direct
current but does not include tram and
train negative conductors;
-- 5 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
4
"negative conductor" means a conductor in
a circuit of a small gauge railway or
tramway system that is—
(a) maintained at approximately the
same electrical potential as the
railway or tramway track; and
(b) insulated from earth;
"other cable system" means—
(a) telecommunication and control
cables; or
(b) aerial earthed cables;
"pole line" means an aerial line connected
by two or more poles;
"relevant installation" means—
(a) a low voltage electrical
installation operating on
alternating current on public land;
or
(b) a high voltage electrical
installation; or
(c) the supply network of a small
gauge railway or tramway system;
"small gauge railway or tramway system"
means a small gauge railway system or
a small gauge tramway system;
"small gauge railway system" means a
system by which vehicles designed to
transport passengers or goods are
guided by means of a railway track—
(a) with a gauge less than
600 millimetres; or
(b) in an amusement park;
r. 7
-- 6 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
5
"small gauge tramway system" means a
system by which vehicles designed to
transport passengers or goods are
guided by means of a tramway track—
(a) with a gauge less than
600 millimetres; or
(b) in an amusement park;
"substation" has the same meaning as it has
in the Australian/New Zealand Wiring
Rules;
"The Blue Book" means the Code of
Practice on Electrical Safety For Work
On Or Near High Voltage Electrical
Apparatus 1999 published by the Office
of the Chief Electrical Inspector, as
amended from time to time;';
(b) for the definition of "consumers mains",
substitute—
' "consumers mains" means those
conductors between the point of supply
and the main switchboard;';
(c) in the definition of "low voltage", for "SAA
Wiring Rules" substitute "Australian/New
Zealand Wiring Rules";
(d) the definition of "SAA Wiring Rules" is
revoked.
8. Electrician's licence
In regulation 302(a)(ii) of the Principal
Regulations for "Electrical (Electrician)"
substitute "Electrotechnology Systems
Electrician".
r. 8
-- 7 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
6
9. Supervised worker's licence
In regulation 303 of the Principal Regulations—
(a) in paragraph (a)(i) omit "that included at
least 12 months electrical installation work";
(b) in paragraph (b)(ii) for "Electrical
(Electrician)" substitute "Electrotechnology
Systems Electrician".
10. Wiring methods
(1) In regulation 401 of the Principal Regulations, for
sub-regulation (1) substitute—
'(1) A person must not install, alter, repair or
maintain an electrical installation or a
portion of an electrical installation unless the
installation or the installed, altered, repaired
or maintained portion of the installation
complies with the Australian/New Zealand
Wiring Rules as modified by the following
provisions—
(a) for clause 1.4.13 substitute—
"1.4.13 Authority, regulatory
The Office of the Chief Electrical
Inspector established under Part 2 of
the Electricity Safety Act 1998.";
(b) in clause 1.4.14, for "licensed electrical
contractor or electrician" substitute—
"registered electrical contractor or
licensed electrician";
(c) after clause 1.4.27 insert—
"1.4.27A Company Assets Company
assets within the meaning of the
Electricity Safety Act 1998.";
r. 9
-- 8 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
7
(d) for clause 1.4.42 substitute—
"1.4.42 Electrical equipment
Appliances, wires, fittings, cables,
conduits or apparatus that generate, use,
convey or control electricity or that are
intended to generate, use, convey or
control electricity.";
(e) for clause 1.4.43 substitute—
"1.4.43 Electrical installation
An electrical installation within the
meaning of the Electricity Safety Act
1998.";
(f) after clause 1.4.55 insert—
'1.4.55A Hazardous bushfire risk
area
An area—
(a) that a fire control authority has
assigned a fire hazard rating of
"high" or "very high" under
section 80 of the Electricity
Safety Act 1998; or
(b) other than an urban area within
the meaning of section 3 of that
Act unless a fire control authority
has assigned to that area a fire
hazard rating other than "high" or
"very high" under section 80 of
that Act.';
(g) after clause 1.4.58 insert—
"1.4.58A Licensed electrician
Electrical installation worker holding
an electrician's licence under regulation
302 of the Electricity Safety
(Installations) Regulations 1999.";
r. 10
-- 9 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
8
(h) after clause 1.4.59 insert—
'1.4.59A Low bushfire risk area
An area—
(a) that a fire control authority has
assigned a fire hazard rating other
than "high" or "very high" under
section 80 of the Electricity
Safety Act 1998; or
(b) an urban area within the meaning
of section 3 of that Act unless a
fire control authority has assigned
to that area a fire hazard rating of
"high" or "very high" under
section 80 of that Act.';
(i) for clause 1.4.71 substitute—
"1.4.71 Point of supply
Point of supply within the meaning of
the Electricity Safety Act 1998.";
(j) after clause 1.4.72 insert—
"1.4.72A Registered Electrical
Contractor
A person who is registered as an
electrical contractor under regulation
201 of the Electricity Safety
(Installations) Regulations 1999.";
(k) in clause 1.6, after "suitable" insert "by
the regulatory authority";
(l) in clause 2.4.1(c) omit "or the
electricity distributor";
r. 10
-- 10 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
9
(m) in the NOTE to clause 3.11.4 for
"Regulatory authorities, such as water
and gas suppliers" substitute "Water,
gas, telecommunications";
(n) in clause 3.11.5.1 for "electricity
distributor" substitute "regulatory
authority";
(o) after the Heading "3.12 AERIAL
WIRING SYSTEMS", insert—
'3.12.0 General
3.12.0.1 Hazardous bushfire risk
areas
Aerial wiring systems must not be
constructed or substantially
reconstructed in hazardous bushfire risk
areas.
3.12.0.2 Low bushfire risk areas
Aerial wiring systems constructed or
substantially reconstructed in low
bushfire risk areas must comply with
the requirements of Clauses 3.12.1 to
3.12.7.3.
3.12.0.3 Substantially reconstructed
In this clause, "substantially
reconstructed" means reconductoring
of more than 30% of the wiring or
replacement of more than 30% of the
number of poles in a line supporting
wiring.';
(p) in clause 3.12.2.1, paragraph (c) and
the NOTE are revoked;
r. 10
-- 11 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
10
(q) after the Heading "3.13 CABLES
SUPPORTED BY A CATENARY"
insert—
'3.13.0 Outdoor cables
3.13.0.1 Hazardous bushfire risk
areas
Outdoor cables supported by means of
a catenary must not be constructed or
substantially reconstructed in hazardous
bushfire risk areas.
3.13.0.2 Low bushfire risk areas
Outdoor cables supported by means of
a catenary constructed or substantially
reconstructed in low bushfire risk areas
must comply with the requirements of
clauses 3.13.1 and 3.13.2.
3.13.0.3 Substantially reconstructed
In this clause, "substantially
reconstructed" means reconductoring
of more than 30% of the cable
supported by a catenary or catenaries or
replacement of more than 30% of the
number of supports for the catenary or
catenaries supporting a cable.';
(r) in clause 5.6.3.1(c) for "electricity
distributor" (where secondly occurring)
substitute "regulatory authority";
(s) in clause 7.8.11.4(c), after "appropriate
means" insert "considered suitable by
the regulatory authority";
r. 10
-- 12 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
11
(t) for clause 7.11.12 substitute—
"7.11.12 Construction and demolition
sites.
Installations on construction and
demolition sites must comply with
AS/NZS 3012.".'.
(2) In regulation 401(5) of the Principal Regulations,
for "SAA Wiring Rules" substitute
"Australian/New Zealand Wiring Rules".
(3) After regulation 401(5) of the Principal
Regulations insert—
"(6) The minimum depth of underground cables
set out in Clause 7.8.11.3 of the
Australian/New Zealand Wiring Rules does
not apply to the first 2000 millimetres of a
high voltage underground cable from the
point where the underground cable enters the
ground if that initial portion of the line is
selected, installed and protected in
accordance with clause 3.3.7 of the
Australian/New Zealand Wiring Rules.".
11. Private electric lines
(1) In regulation 403(2) of the Principal Regulations,
for "constructed or substantially reconstructed"
substitute "installed, altered, repaired or
maintained".
(2) In regulation 403(3) of the Principal Regulations,
for paragraph (b) substitute—
'(b) "low bushfire risk area" means—
(i) an area that a fire control authority has
assigned a fire hazard rating other than
"high" or "very high" under section 80
of the Act; or
r. 11
-- 13 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
12
(ii) an urban area within the meaning of
section 3 of the Act unless a fire control
authority has assigned to that area a fire
hazard rating of "high" or "very high"
under section 80 of the Act.'.
12. Testing
In regulation 405 of the Principal Regulations, for
sub-regulation (1) substitute—
"(1) For the purposes of section 44(1)(b) of the
Act, electrical installation work must be
tested after it is completed and before
inspection or certification under the Act to
verify that the installation work complies
with regulation 401.".
13. Regulation 406 substituted
For regulation 406 of the Principal Regulations
substitute—
'406. Prescribed electrical installation work
(1) For the purposes of section 45 of the Act,
"prescribed electrical installation work"
means work on all or part of any of the
following electrical installations if they are
ordinarily operated at low voltage or a
voltage exceeding low voltage—
(a) consumers mains, main earthing
systems, consumers terminals
connection devices and those parts of
main switchboards that are related to
the control of installations and the
protection against the spread of fire;
(b) sub-mains, earthing systems and any
distribution boards related to the
control of individual occupiers' portions
of multiple installations unless the
occupier has immediate and unimpeded
r. 12
-- 14 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
13
access to the main switch or switches
controlling the whole of the multiple
installation;
(c) electrical equipment installed in a
hazardous area described in clause
7.9.2.2 of the Australian/New Zealand
Wiring Rules and electrical equipment
associated with the protection of such a
hazardous area but not installed within
the hazardous area;
(d) high voltage installations except high
voltage electrical equipment that is—
(i) associated with an electric
discharge lighting system; or
(ii) associated with X-ray equipment;
or
(iii) associated with high frequency
equipment; or
(iv) within self contained equipment
supplied at low voltage;
(e) wiring systems, switchgear, controlgear
and accessories installed to provide
control and protection of standby
generation or co-generation electricity
supply systems;
(f) electric fences used for security
purposes but not including electric
fences intended primarily for the
control or containment of animals;
(g) wiring systems, switchgear, controlgear
and accessories installed to provide
control and protection of stand alone
power systems;
r. 13
-- 15 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
14
(h) fixed electrical equipment installed in
body-protected or cardiac-protected
electrical areas of hospitals and medical
and dental practices.
(2) For the purposes of section 45 of the Act,
"prescribed electrical installation work"
does not include—
(a) the repair or maintenance of a single
component part of an electrical
installation; or
(b) the replacement of a single component
part of an electrical installation by an
equivalent component part at the same
location.'.
14. Certificates of compliance
In regulation 410(3) of the Principal
Regulations—
(a) in paragraph (j), after "work" insert "if the
work has increased the maximum demand";
(b) in paragraph (k), after "installation" insert
"if the work has increased the maximum
demand of the installation".
15. Reporting of incidents
In regulation 414(3) of the Principal Regulations
omit "operated at low voltage".
16. Exemptions
After regulation 416(2) of the Principal
Regulations insert—
"(3) The Office may revoke an exemption.".
r. 14
-- 16 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
15
17. New Part 4A inserted
After Part 4 of the Principal Regulations insert—
'PART 4A—WIRING AND SAFETY
REQUIREMENTS
Division 1—Duties of owners and operators of
high voltage electrical installations and supply
networks of small gauge railway or tramway
systems
417. General requirements—high voltage
electrical installations
(1) A person who owns or operates a high
voltage electrical installation, must ensure
that—
(a) the installation or the installed, altered,
repaired or maintained portion of the
installation complies with the
Australian/New Zealand Wiring Rules
as modified by regulation 401(1); and
(b) all parts of the installation are designed,
installed, altered, repaired and
maintained in accordance with the
requirements of this Division.
Penalty: 20 penalty units.
(2) If there is an inconsistency relating to high
voltage electrical installations between a
provision of the Australian/New Zealand
Wiring Rules and a provision of this
Division, the provision of this Division
prevails to the extent of the inconsistency.
r. 17
-- 17 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
16
(3) A person who owns or operates a high
voltage electrical installation must ensure
that—
(a) any person operating the electrical
installation has a standard of
qualifications, proficiency and
experience that enables that person to
safely perform their function; and
(b) any person operating or maintaining the
electrical installation has written
operating and maintenance procedures
that describe the methods of operation,
maintenance, earthing, isolation,
energisation and de-energisation of the
electrical installation; and
(c) any person operating or maintaining
any part of the electrical installation is
trained, authorised and instructed to
perform the work on the electrical
installation in accordance with the
owner or operator's operating and
maintenance procedures; and
(d) any person under the control of the
owner or operator who is working on or
near the electrical installation—
(i) is appropriately trained in
accordance with Clause 3 of The
Blue Book and aware of the
requirements of The Blue Book;
and
(ii) complies with the provisions of
The Blue Book that apply to the
work that the person is carrying
out; and
r. 17
-- 18 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
17
(e) an Electrical Access Permit for work on
the electrical installation as required in
Clause 8 of The Blue Book is used by
any person under the control of the
owner or operator who is working on or
near the electrical installation.
Penalty: 20 penalty units.
418. General requirements—small gauge
railway or tramway systems
(1) A person who owns or operates the supply
network of a small gauge railway or tramway
system must ensure that all parts of the
supply network of the system are designed,
installed, altered, repaired and maintained in
accordance with the requirements of this
Division.
Penalty: 20 penalty units.
(2) A person who owns or operates the supply
network of a small gauge railway or tramway
system must ensure that—
(a) any person operating the supply
network of the system has a standard of
qualifications, proficiency and
experience that enables that person to
safely perform their function; and
(b) any person operating or maintaining the
supply network of the system has
written operating and maintenance
procedures that describe the methods of
operation, maintenance, earthing,
isolation, energisation and de-
energisation of the supply network of
the system; and
r. 17
-- 19 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
18
(c) any person operating or maintaining
any part of the supply network of the
system is trained, authorised and
instructed to perform the work on the
supply network of the system in
accordance with the owner's or
operator's operating and maintenance
procedures; and
(d) any person under the control of the
owner or operator who is working on or
near the supply network of the
system—
(i) is appropriately trained in
accordance with Clause 3 of The
Blue Book and aware of the
requirements of The Blue Book;
and
(ii) complies with the provisions of
The Blue Book that apply to the
work that the person is carrying
out; and
(e) an Electrical Access Permit for work on
the supply network of the system as
required in Clause 8 of The Blue Book
is used by any person under the control
of the owner or operator who is
working on or near the supply network
of the system.
Penalty: 20 penalty units.
419. Minimum distances between aerial lines
and the ground or water
(1) An aerial line must not, at any time, be
closer to the ground or the surface of any
water not accessible to boats with masts than
r. 17
-- 20 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
19
the relevant minimum distance specified in
Table 419.
(2) An aerial line must not, at any time, be
closer than 13 500 millimetres to the surface
of any water accessible to boats with masts.
(3) The minimum distances in Table 419 do not
apply to a part of an aerial line that is within
a substation.
TABLE 419—Minimum distances to the ground from aerial lines
Minimum distance
Type of aerial line
Nominal voltage ('U')
Carriageway
of roads
Ground
traversable
by vehicles
Other ground or
the surface of
any water not
accessible to
boats with masts
U < 1500V d.c. traction
conductor
5000mm 5000mm 4500mm
Alternating current
insulated with earthed
screen U > 1kV
5500mm 5500mm 4500mm
Alternating current
insulated without an
earthed screen U > 1kV
6000mm 5500mm 4500mm
Alternating current
Bare or covered
1kV < U < 33kV 6700mm 5500mm 5000mm
33kV < U < 132kV 6700mm 6700mm 5500mm
132kV < U < 275kV 8700mm 6700mm 6700mm
275kV < U < 330kV 9700mm 6700mm 6700mm
330kV < U < 500kV 11400mm 10700m
m
10700mm
420. Aerial lines and the façade of buildings
(1) An aerial line other than a low voltage
insulated conductor must not, at any time, be
attached to the façade of any building.
r. 17
-- 21 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
20
(2) A low voltage insulated conductor must not,
at any time, be closer to a part of a building
or structure specified in Table 420 (and
partially illustrated in Figures 420.1, 420.2
and 420.3) than the relevant minimum
distance specified in the Table.
(3) Figures 420.1, 420.2 and 420.3 are for
illustrative purposes only and are not
intended to be a comprehensive depiction of
the situations they illustrate.
TABLE 420—Minimum distances to parts of buildings or structures from
low voltage insulated conductors supported along the façade of the building
or structure
Low voltage
insulated conductor Minimum distance
A Vertically from ground 2500mm
B Above windows and doors 300mm
C Each side of and below windows 500mm
D Each side of doors and balconies 1000mm
E From metallic parts of buildings or
structures
50mm
r. 17
-- 22 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
21
421. Minimum distances between aerial lines
and buildings or structures
(1) An aerial line carrying alternating current
must not, at any time, be closer to a building
or structure or part of a building or structure
specified in Table 421.1 (and partially
illustrated in Figures 421.1 and 421.2) than
the relevant minimum distance specified in
that Table.
(2) An aerial line carrying direct current must
not, at any time, be closer to a building or
structure or part of a building or structure
specified in Table 421.2 (and partially
illustrated in Figures 421.1 and 421.2) than
the relevant minimum distance specified in
that Table.
(3) The minimum distances in rows A, B, C and
D of Tables 421.1 and 421.2 do not apply to
the connection of an aerial line to a pole,
tower or substation.
(4) The minimum distances in rows B, C and D
of Tables 421.1 and 421.2 do not apply to
r. 17
-- 23 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
22
that part of an aerial line close to a building
or structure for the purposes of supplying
electricity to the building or structure.
(5) Figures 421.1 and 421.2 are for illustrative
purposes only and are not intended to be a
comprehensive depiction of the situations
they illustrate.
TABLE 421.1—Minimum distances to parts of buildings or structures from
aerial lines carrying alternating current
Minimum distance for type of aerial line and nominal voltage ('U')
U>1kV
1kV < U <
33kV
33kV < U <
132kV
132kV <
U <
275kV
275kV <
U <
330kV
330kV <
U <
500kV
Alternating
current
aerial line
Insulated
with
earthed
screen
Insulated
without
earthed
screen
Bare or
covered Bare Bare Bare Bare
A
Vertically above
those parts of a
building or
structure normally
accessible to
persons
2700mm 3700mm 4500mm 5000mm 6800mm 8000m
m
9800m
m
B
Vertically above
those parts of a
building or
structure not
normally
accessible to
persons but on
which a person
can stand
100mm 2700mm 3700mm 4500mm 6000mm 7000m
m
8000m
m
C
-- 24 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
23
In any direction,
other than
vertically above,
from those parts
of a building or
structure normally
accessible to
persons, or from
any part not
normally
accessible to
persons but on
which a person
can stand
100mm 1500mm 2100mm 3000mm 4600mm 5500m
m
6400m
m
D
In any direction
from those parts
of a building or
structure not
normally
accessible to
persons
100mm 600mm 1500mm 2500mm 3700mm 4700m
m
6400m
m
TABLE 421.2—Minimum distances to parts of buildings or structures
from aerial lines carrying direct current
Minimum distance for type of aerial line and
nominal voltage ('U')
U< 600V
600V < U<
1500V
Direct current aerial line Insulated Bare Bare or insulated
A
Vertically above those parts
of a building or structure
normally accessible to
persons
2700mm 3700mm 4500mm
B
Vertically above those parts
of a building or structure not
normally accessible to
persons but on which a person
can stand
100mm 2700mm 3700mm
C
r. 17
-- 25 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
24
In any direction, other than
vertically above, from those
parts of a building or structure
normally accessible to
persons or vertically below as
described in row E, or from
any part not normally
accessible to persons but on
which a person can stand
100mm 1500mm 2100mm
D
In any direction, other than
vertically below as described
in row E, from those parts of
a building or structure not
normally accessible to
persons
100mm 600mm 1500mm
E
Vertically below those parts
of a building or structure
erected over a small gauge
railway or tramway system
100mm 300mm 300mm
-- 26 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
25
422. Minimum distances between aerial lines
and parts of small gauge railway systems
(1) A high voltage aerial line carrying
alternating current above a direct current
catenary wire or supervisory cable for a d.c.
traction conductor for a small gauge railway
system must not, at any time, be closer than
900 millimetres above a straight line joining
the higher of the supporting points for the
span of the catenary wire or supervisory
cable.
r. 17 r. 17
-- 27 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
26
(2) An aerial line carrying alternating current
must not, at any time, be closer to a part of a
small gauge railway system specified in
Table 422 than the relevant minimum
distance specified in that Table.
TABLE 422—Minimum distances to parts of small gauge railway systems
from aerial lines carrying alternating current
Minimum distance from part of a small gauge railway
system
Alternating current
aerial line Nominal
voltage ('U') Above track
From d.c. traction
conductors
From d.c. traction
conductor
wire/cable supports
U < 1kV 6700mm Not permitted 2700mm
1kV < U< 22kV 7600mm 1200mm 3700mm
22kV < U< 66kV 7600mm 1800mm 4600mm
66kV < U< 132kV 7900mm 2100mm 4600mm
132kV < U< 275kV 9000mm 3000mm 5500mm
275kV < U< 330kV 9800mm 4000mm 6400mm
330kV < U< 500kV 11300mm 5500mm 7900mm
423. Minimum distances between aerial lines
and parts of small gauge tramway systems
An aerial line carrying alternating current
must not, at any time, be closer to a part of a
small gauge tramway system specified in
Table 423 than the relevant minimum
distance specified in that Table.
r. 17
-- 28 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
27
TABLE 423—Minimum distances to parts of small gauge tramway systems
from aerial lines carrying alternating current
Minimum distance from part of a small gauge tramway
system
Alternating current
aerial line Nominal
voltage ('U') Above track
From d.c. traction
conductors
From d.c. traction
conductor
wire/cable supports
U < 1kV 7000mm 600mm 2700mm
1kV < U< 22kV 8200mm 1200mm 3700mm
22kV < U< 66kV 8200mm 1800mm 4600mm
66kV < U< 132kV 8200mm 2100mm 4600mm
132kV < U< 220kV 9000mm 3000mm 5500mm
220kV < U< 330kV 9800mm 4000mm 6400mm
330kV < U< 500kV 11300mm 5500mm 7900mm
424. Minimum distances between aerial lines
(1) An aerial line that forms part of—
(a) a high voltage electrical installation; or
(b) the supply network of a small gauge
railway or tramway system—
must not, at any time, be closer to another
aerial line than the relevant minimum
distance specified in Table 424.
(2) The nominal voltage of the lower circuit of
an aerial line must not be greater than the
nominal voltage of the upper circuit of an
aerial line.
(3) A d.c. traction conductor for a small gauge
tramway system must not, at any time, cross
an electrolysis drainage cable, unless the
conductor and the cable are attached to a
common pole or support.
r. 17
-- 29 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
28
TABLE 424—Minimum distances between aerial lines
Type and nominal voltage ('U') Minimum distance
Upper circuit Lower circuit
Between the aerial
line spans.
Circuits on the
same pole line
Between the
points where the
aerial lines are
attached to a
common pole or
support
Between the aerial
line spans. Circuits
crossing not on
same pole line
Low voltage
alternating
current aerial
line
d.c. traction
conductor
U≤ 1500V
1000mm 1000mm 1000mm
d.c. traction
conductor
U≤ 1500V
Electrolysis
drainage cable
1000mm 1000mm Not permitted
d.c. traction
conductor
U≤ 1500V
Other cable
system
1000mm 1000mm 1000mm
Alternating
current aerial
line
U > 1kV
U < 33kV
Alternating
current aerial
line
U < 33kV
1200mm 1200mm 750mm
Alternating
current aerial
line
U > 33kV
U < 66kV
Alternating
current aerial
line
U < 66kV
1800mm 1800mm 1200mm
425. Substations
Any part of the supporting platform and
equipment (except conductors) for a pole
mounted substation that is mounted on or
attached to the pole or crossarms of the pole
and that is—
(a) more than 500 millimetres from the
vertical projection of the kerb line in
the direction away from a vehicular
carriageway and that is more than 200
millimetres from the surface of the pole
must be no lower than 3600 millimetres
from the ground; and
r. 17
-- 30 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
29
(b) more than 500 millimetres from the
vertical projection of the kerb line in
the direction away from a vehicular
carriageway and that is 200 millimetres
or less from the surface of the pole
must be no lower than 2400 millimetres
from the ground; and
(c) in any other situation not covered by (a)
or (b) must be no lower than 4600
millimetres from the ground.
426. Poles and towers
Poles, towers and other structures supporting
aerial lines must—
(a) be as vertical as is practicable; and
(b) not lean over the kerb line in the
direction of a vehicular carriageway
more than 5 degrees from the
perpendicular; and
(c) elsewhere not lean more than 10
degrees from the perpendicular.
427. Marking of electric lines
If aerial lines are within one kilometre of an
airport or airfield, the lines must be marked
to indicate their position and direction in
accordance with AS 3891.1 and AS 3891.2.
Division 2—Duties of the public
428. Application
A person may do any thing that is otherwise
prohibited by regulations 429 to 442 if the
person—
(a) does that thing when the relevant
installation is isolated and earthed by
r. 17
-- 31 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
30
the owner or operator of the
installation; and
(b) does that thing with the written
permission of the owner or operator of
the relevant installation; and
(c) complies with any conditions imposed
by the owner or operator in giving the
permission.
429. Sporting activities
A person must not throw, hit, kick, launch,
discharge, fire or project, or cause to be
thrown, hit, kicked, launched, discharged,
fired or projected, any object—
(a) with intent to strike; or
(b) if there is significant risk that the object
will strike—
any part of a relevant installation.
Penalty: 10 penalty units.
430. Aircraft, kites etc.
(1) A person must not launch, release, operate,
fly or land any aircraft, glider, hang glider,
hot air balloon, parachute, mechanically
propelled model aircraft, model glider or kite
within 45 metres of a relevant installation
that is above the ground.
Penalty: 10 penalty units.
(2) Sub-regulation (1) does not apply to a person
who lands an aircraft, glider, hang glider, hot
air balloon or parachute if the particular
circumstances reasonably necessitated the
landing by the person.
r. 17
-- 32 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
31
431. Entangled objects
A person must not pull or interfere with any
object resting on or entangled in any relevant
installation unless the action is reasonably
necessary to prevent or reduce injury to a
person or damage to property.
Penalty: 10 penalty units.
432. Blasting and fires
A person must not—
(a) carry out blasting or cause blasting to
be done; or
(b) light or cause to be lit or allow to
remain alight any fire; or
(c) install equipment or operate processes
likely to create an explosive
atmosphere—
in the vicinity of a relevant installation in
such a manner that the relevant installation is
likely to be damaged or an explosion is
likely to occur.
Penalty: 20 penalty units.
433. Protection of underground electrical
installations from damage
A person must not place or allow to remain,
or cause to be placed or allowed to remain
above or in the vicinity of—
(a) an underground high voltage electrical
installation; or
r. 17
-- 33 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
32
(b) a low voltage electrical installation
operating on alternating current that is
under public land—
the existence and location of which should
reasonably have been known to the person,
any corrosive, abrasive, heavy or deleterious
material or substance that damages or is
likely to damage an underground electrical
installation.
Penalty: 20 penalty units.
434. Excavating
(1) A person must not make an excavation
deeper than 300 millimetres on private land
where the person should reasonably have
known that an underground line was located
unless the person has inspected any record of
the route of underground lines under
regulation 404 and located any underground
lines in the vicinity of the excavation.
Penalty: 20 penalty units.
(2) A person must not cut away, excavate or
remove, or cause to be cut away, excavated
or removed, any earth or material supporting
or covering a relevant installation so as to—
(a) endanger the stability of the relevant
installation; or
(b) in the case of a high voltage
underground electric line, reduce the
depth of the underground installation to
less than the minimum depth required
by clause 7.8.11.3 of the
Australian/New Zealand Wiring Rules;
and
(c) in the case of a low voltage relevant
electrical installation operating on
r. 17
-- 34 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
33
alternating current that is under public
land, reduce the depth of the
underground installation to less than the
minimum depth required by clause
3.11.1 of the Australian/New Zealand
Wiring Rules.
Penalty: 20 penalty units.
435. Altering levels
(1) A person must not place material above
ground level below a low voltage aerial line
operating on alternating current on public
land that forms part of a relevant installation
in a manner to alter the level of the ground
so as to reduce the distance between the
ground and the line to less than the minimum
distance required, by clause 3.12.3 of the
Australian/New Zealand Wiring Rules.
Penalty: 20 penalty units.
(2) A person must not place material above
ground level below a high voltage aerial line
or aerial line of a small gauge railway or
tramway system that forms part of a relevant
installation in a manner to alter the level of
the ground so as to reduce the distance
between the ground and the line to less than
the minimum distance required by regulation
419.
Penalty: 20 penalty units.
(3) A person must not place any material above
ground level next to a low voltage electrical
installation operating on alternating current
on public land so as to reduce the distance
between the ground and the installation to
less than the minimum distance required by
r. 17
-- 35 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
34
clause 3.12.3 of the Australian/New Zealand
Wiring Rules.
Penalty: 20 penalty units.
(4) A person must not place any material above
ground level next to a high voltage electrical
installation or the supply network of a small
gauge railway or tramway system, so as to
reduce the distance between the ground and
the installation to less than the minimum
distance required by regulation 426.
Penalty: 20 penalty units.
436. Minimum distances between parts of
buildings, structures, scaffolding and posts
and aerial lines
A person must not build, erect or maintain a
building, structure, scaffolding or post or
part of a building, structure, scaffolding or
post specified in Table 436 so that, at any
time, the building, structure, scaffolding,
post or part is closer to an aerial line that
forms part of a relevant installation than the
relevant minimum distance specified in that
Table.
Penalty: 20 penalty units.
r. 17
-- 36 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
35
TABLE 436—Minimum distances from parts of buildings, structures, scaffolding or
posts to aerial lines of relevant installations
Minimum Distance Nominal Voltage
Alternating current aerial lines
Aerial lines
d.c. traction
conductors for
a small gauge
tramway
system
U < 600V
d.c. traction
conductors
for a small
gauge
railway
system
U < 1500V
Alternating
current
aerial lines
U < 1kV
1kV <
U <
33kV
33kV<
U < 132kV
132kV<
U <
275kV
275kV<
U <
330kV
330kV<
U < 500kV
Vertically above
those parts of a
building,
structure,
scaffolding or
post normally
accessible to
persons
3700mm 4600mm 3700mm 4600mm 5000mm 6800mm 8000mm 9800mm
Vertically above
those parts of a
building,
structure,
scaffolding or
post not normally
accessible but on
which a person
can stand
2700mm 3700mm 2700mm 3700mm 4600mm 6000mm 7000mm 8000mm
In any direction
from those parts
of a building,
structure,
scaffolding or
post not normally
accessible to
persons
600mm 2700mm 600mm 2700mm 3000mm 3700mm 4700mm 6400mm
In any direction
from windows,
openings and
balconies and
those parts of a
building,
structure,
scaffolding or
post normally
accessible to
persons
1500mm 2700mm 1500mm 2700mm 3000mm 4600mm 5500mm 6400mm
In any direction
from a footbridge
4600mm 4600mm 4600mm 4600mm 4600mm 6800mm 8000mm 9800mm
r. 17
-- 37 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
36
437. Minimum distances between materials and
certain aerial lines
A person must not—
(a) place or allow to remain any timber or
other flammable material closer than
3000 millimetres in any direction from
a wall or fence of any substation or
switch yard that forms part of a relevant
installation; or
(b) place or allow to remain any timber or
other flammable material vertically
below an aerial line that forms part of a
relevant installation; or
(c) place or allow to remain any timber or
other flammable material, so that, at
any time, the timber or other flammable
material is closer than the relevant
horizontal distance specified in Table
437 from any point of the vertical
projection below an aerial line that
forms part of a relevant installation; or
(d) place or allow to remain any material
so that, at any time, the material is
closer than the relevant horizontal
distance marked 'h' specified in Table
437 from any point of the vertical
projection below an aerial line that
forms part of a relevant installation
unless the material is no closer
vertically below the line than the
vertical distance marked 'v'.
Penalty: 20 penalty units.
r. 17
-- 38 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
37
TABLE 437—Minimum distances from materials to aerial lines
Alternating current aerial lines
Nominal voltage ('U')
Type of
material
U <
1500V d.c.
traction
conductor
1kV<
U < 33kV
33kV<
U < 132kV
132kV<
U < 275kV
275kV<
U < 330kV
330kV<
U < 500kV
Timber or
other
flammable
material
Horizontal
distance
3000mm 3000mm 3000mm 4600mm 5500mm 6400mm
Any other
material
'h'
'v'
1500mm
3700mm
2100mm
4600mm
3000mm
4600mm
4600mm
6800mm
5500mm
8000mm
6400mm
9800mm
438. Minimum distances between parts of
vehicles, plant, machinery and aerial lines
(1) A person must not operate a vehicle or fixed
or mobile plant or machinery so that any part
of the vehicle, plant, machinery or any fixed
or removable attachment of that vehicle,
plant or machinery comes closer to an aerial
line that forms part of a relevant installation
than the relevant minimum distance
specified in Table 438.
Penalty: 20 penalty units.
(2) This regulation does not apply to a person
transporting a load.
TABLE 438—Minimum distances from any part of a vehicle, plant or
machinery to aerial lines
Alternating current aerial lines
Norminal voltage ('U')
U < 1500V
d.c. traction
conductor U < 66kV U > 66kV
Minimum
distance in
all directions
2000mm 2000mm 6000mm
r. 17
-- 39 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
38
439. Minimum distances between transported
loads and aerial lines
A person must not transport a load so that
the load is closer to an aerial line that forms
part of a relevant installation than the
relevant minimum distance specified in
Table 439.
Penalty: 20 penalty units.
TABLE 439—Minimum distances from transported loads to aerial lines
Alternating current aerial lines
Nominal voltage ('U')
U < 1500V
d.c. traction
conductor
U < 1kV
insulated
conductor
1kV<
U <
66kV
66kV<
U <
132kV
132kV<
U <275kV
275kV<
U <
330kV
330kV<
U <
500kV
Minimum
distance in
all
directions
700mm 300mm 1000mm 1500mm 4600mm 5500mm 6400mm
440. Minimum distances between aerial lines
(1) A person who owns or operates an electrical
installation must not erect, maintain or allow
to remain or cause to be erected or
maintained an aerial line referred to in Table
440.1 so that, at any time, the aerial line is
closer to an aerial line that forms part of a
relevant installation specified in the Table
than the relevant minimum distance
specified in the Table.
Penalty: 20 penalty units.
(2) The nominal voltage of the lower circuit of
an aerial line must not be greater than the
nominal voltage of the upper circuit of an
aerial line.
r. 17
-- 40 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
39
(3) A person must not erect or maintain a circuit
or other cable system on a pole line so that,
at any time, the circuit or other cable system
is closer than the relevant minimum distance
specified in Table 440.3 to—
(a) a circuit or other cable system or pole
line of a relevant installation specified
in the Table; or
(b) any part of a relevant installation
specified in the Table not attached to
the pole line.
Penalty: 20 penalty units.
TABLE 440.1—Minimum distances between aerial lines
Type and nominal voltage ('U') Minimum distance
Upper circuit Lower circuit
Between the points
where the aerial lines
are attached to a
common pole or support
Between the aerial line
spans. Circuits on the
same pole line or
circuits crossing not on
same pole line
Low voltage alternating
current aerial line
d.c. traction conductor
U≤ 1500V
1000mm 1000mm
d.c. traction conductor
U≤ 1500V
Electrolysis drainage
cable
1000mm 1000mm
d.c. traction conductor
U≤ 1500V
Other cable system 1000mm 1000mm
TABLE 440.3—Minimum distances from circuits or other cable systems on pole lines
to circuits or other cable systems on pole lines of relevant installations and any part of
a relevant installation not attached to the pole line
Alternating current aerial lines
Nominal voltage ('U')
1500V
d.c.
traction
conductor
Other cable
systems and
U < 1kV
insulated
conductor
U < 1kV
bare
conductor
1kV<
U < 33kV
insulated
conductor
1kV<
U < 33kV
bare
conductor
33kV<
U<132kV
132kV<
U<275kV
U>275kV<
U<330kV
330kV<
U<500k
V
Minimum
distance
in any
direction
1500mm 100mm 1500mm 1500mm 2100mm 3000mm 4500mm 5000mm 6000mm
r. 17
-- 41 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
40
441. Minimum distances between persons and
aerial lines
(1) A person must not, at any time, come closer
to an aerial line that forms part of a relevant
installation than the relevant minimum
distance specified in Table 441.
Penalty: 20 penalty units.
(2) This regulation does not apply to—
(a) a licensed electrician; or
(b) a person engaged in tree clearing work
who holds a current certificate
specifying satisfactory completion of a
training course in tree clearing,
approved by the Office; or
(c) a person engaged by the owner or
operator of the aerial line who is
carrying out electrical installation work
on the line, under the effective
supervision of a licensed electrician, if
the person has—
(i) completed a contract of training as
an electric line worker that
involves electrical work on high
voltage aerial lines; and
(ii) the written permission of the
owner or operator of the line.
TABLE 441—Minimum distances from persons to aerial lines
Item number
Type of aerial line
Nominal voltage ('U') Minimum distance
1 Insulated low voltage conductors 100mm
2 Bare or covered low voltage conductors 1500mm
3 High voltage conductors U < 66kV 2000mm
4 High voltage conductors U > 66kV 4000mm
442. Tree clearing
r. 17
-- 42 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
41
(1) A person, other than an authorised person,
must not prune or clear the whole or any part
of a tree if the tree or any part of the tree that
is pruned or cleared will fall closer to a
relevant installation than—
(a) in the case of a low voltage electrical
installation operating on alternating
current on public land, 2 metres in all
directions; and
(b) in the case of a high voltage electrical
installation or aerial line of a small
gauge railway or tramway system, the
relevant minimum distance specified in
Table 442.
Penalty: 20 penalty units.
(2) In this regulation "authorised person"
means a person who holds a current
certificate specifying satisfactory completion
of a training course in tree clearing,
approved by the Office.
TABLE 442—Minimum distances from falling trees or parts of trees to high
voltage electrical installations and aerial lines of a small gauge railway or
tramway system
Nominal voltage ('U')
U < 66kV alternating
current or
U <1500V d.c. traction
conductor
U > 66kV alternating current
or
U > 1500V direct current
Minimum distance in
all directions
2000mm 6000mm
443. Damage and interference
r. 17
-- 43 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
42
(1) A person must not attach aerial lines or other
cable systems to a low voltage electrical
installation operating on alternating current
on public land.
Penalty: 20 penalty units.
(2) A person must not in a manner that would
cause or be likely to cause risk to persons or
damage to property—
(a) damage or interfere with a relevant
installation; or
(b) damage or interfere with a seal or lock
preventing entry or access to a relevant
installation; or
(c) deface a sign relating to electrical
safety on or near a relevant installation.
Penalty: 20 penalty units.
444. Placing of materials
A person must not place any material, or
allow any material to remain, in a manner
that will impede access to any switchboard
or door, gate or entrance to a substation,
switchroom or switchyard of an electrical
installation or interfere with the free flow of
air through any opening or fitting used for
ventilation in the walls of a substation,
switchroom or switchyard of an electrical
installation.
Penalty: 20 penalty units.
Division 3—Exclusions and exemptions
r. 17
-- 44 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
43
445. Exclusions
Division 2 does not apply in relation to a
relevant installation that—
(a) is upstream of the point of supply
except an electrical installation used for
the consumption of electricity by the
electricity supplier; or
(b) is used in mining under a licence issued
under the Mineral Resources
Development Act 1990; or
(c) comprises fixed electrical equipment
designed to be easily transportable that
is connected to the electricity supply by
the insertion of a plug into a socket
designed for the plug.
446. Exemptions
(1) The Office may, on the application of a
person, exempt the person from any
requirement of this Part subject to any
conditions specified by the Office.
(2) An application must—
(a) be in writing; and
(b) contain details of—
(i) the applicant's name, telephone
number, and business and postal
address; and
(ii) the exemption requested; and
(iii) the reasons for the exemption; and
(c) be accompanied by—
r. 17
-- 45 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
44
(i) any relevant technical
information; and
(ii) the written agreement to the
proposed exemption by the owner
or operator of the relevant
installation; and
(iii) the application fee set out in
Schedule 2.
(3) The Office may, at any time, revoke an
exemption.'.
18. Examinations for registration
For regulation 501(4) of the Principal Regulations
substitute—
"(4) If a person fails an examination of
competency or proficiency for registration as
an electrical contractor, the person is not
eligible to sit for a further examination for a
period of 3 months unless that person can
demonstrate to the Office that it will cause
unusual hardship.".
19. Examinations for licensing
For regulation 502(4) of the Principal Regulations
substitute—
"(4) If a person fails an examination of
competency or proficiency for a licence in a
prescribed class of electrical work, the
person is not eligible to sit for a further
examination for a period of 3 months unless
that person can demonstrate to the Office
that it will cause unusual hardship.".
20. New regulation 703 inserted
r. 18 r. 20
-- 46 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
45
After regulation 702 of the Principal Regulations
insert—
"703 Transitional exemption for existing aerial
lines
(1) Division 1 of Part 4A in relation to high
voltage electrical installations does not apply
to an aerial line that was in operation
immediately before the date this regulation
came into operation if—
(a) immediately before that date the aerial
line complied with the requirements of
Part 2 of the Electricity Safety
(Network Assets) Regulations 19972 as
in force immediately before they were
revoked; and
(b) on and after that date the aerial line
complies with the Electricity Safety
(Network Assets) Regulations 19973 as
in force immediately before they were
revoked.
(2) This regulation ceases to have any force or
effect on 31 December 2003.".
21. New Fees
In Schedule 2 to the Principal Regulations
insert—
"ELECTRICAL INSTALLATIONS
Application fee for exemption under
regulation 445 $70".
22. New Schedule 4 substituted
r. 22
-- 47 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
46
For Schedule 4 to the Principal Regulations
substitute—
"SCHEDULE 4
PART A—PRESCRIBED CLASSES OF ELECTRICAL
INSPECTION WORK
Class Description
L Electrical equipment installed in installations comprising a
low voltage single phase, 2 wire supply comprising
consumers mains, main earthing systems, consumer
terminals connection devices or those parts of main
switchboards that are related to the control of installations
and the protection against the spread of fire.
G Any low voltage installations other than classes H, S, F, R
and M.
H
V
Electrical equipment installed in a hazardous area
described in clause 7.9.2.2 of the Australian/New Zealand
Wiring Rules and electrical equipment associated with the
protection of the hazardous area but not installed within
the hazardous area.
High voltage installations except high voltage electrical
equipment that is—
(i) associated with an electric discharge lighting
system; or
(ii) associated with X-ray equipment; or
(iii) associated with high frequency equipment; or
(iv) within self contained equipment supplied at low
voltage.
S Wiring systems, switchgear, controlgear and accessories
installed to provide control and protection of standby
generation or co-generation electricity supply systems.
F Electric fences used for security purposes but not
including electric fences intended primarily for the control
or containment of animals.
Class Description
R Wiring systems, switchgear, controlgear and accessories
-- 48 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
47
installed to provide control and protection of stand alone
power systems.
M Fixed electrical equipment installed in body-protected or
cardiac-protected electrical areas of hospitals and medical
and dental practices.
PART B—REQUIRED QUALIFICATIONS,
PROFICIENCY AND EXPERIENCE IN ELECTRICAL
INSPECTION WORK
Class Description
L 1. A detailed understanding of safety in electrical
installations.
2. Testing methods for electrical installations.
3. The requirements of these Regulations for consumers
mains, main earthing systems, main switchboards and
consumer terminals connection devices.
G 1. A detailed understanding of safety in electrical
installations.
2. Testing methods for electrical installations.
3. The requirements of these Regulations for low voltage
electrical installations.
H 1. A detailed understanding of safety in electrical
installations in hazardous areas.
2. Testing methods in hazardous areas and for electrical
equipment associated with the protection of hazardous
areas.
3. The requirements of these Regulations for electrical
installations in hazardous areas and electrical
equipment associated with the protection of hazardous
areas.
Class Description
V 1. A detailed understanding of safety in high voltage
electrical installations.
r. 22
-- 49 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
48
2. Testing methods for high voltage installations.
3. The requirements of these Regulations for high
voltage electrical installations.
S 1. A detailed understanding of safety in standby
generation and co-generation electrical installations.
2. Testing methods for standby generation and co-
generation installations.
3. The requirements of these Regulations for standby
generation and co-generation installations.
F 1. A detailed understanding of safety in security fences
that are electrical installations.
2. Testing methods for security fences that are electrical
installations.
3. The requirements of these Regulations for security
fences that are electrical installations.
R 1. A detailed understanding of safety of stand alone
power systems.
2. Testing methods for stand alone power systems.
3. The requirements of these Regulations for stand alone
power systems.
M 1. A detailed understanding of safety in fixed electrical
equipment installed in body-protected or cardiac-
protected electrical areas of hospitals and medical and
dental practices.
2. Testing methods for electrical installations in those
areas.
3. The requirements of these Regulations for those
areas.".
═══════════════
r. 22
-- 50 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
49
ENDNOTES
1 Reg. 4: S.R. No. 49/1999.
2 Reg. 20: S.R. No. 5/1997.
3 Reg. 20: See Note 2.
Table of Applied, Adopted or Incorporated Matter Required by
Subordinate Legislation Regulations 1994
Note that the following table of applied, adopted or incorporated matter is
included in accordance with the requirements of regulation 6 of the Subordinate
Legislation Regulations 1994.
Statutory Rule
Provision
Title of applied, adopted
or incorporated
document
Matter in applied,
adopted or incorporated
document
Regulation 7 AS/NZS 3000 Clauses 1.4.5, 1.4.28,
1.4.82 and paragraph (b) of
clause 1.4.90
Regulations 10
and 17
AS/NZS 3000 which
incorporates:
AS 1023.1
AS 1939
AS 2005.10
AS 2005.20
AS 2005.21
AS 2005.21.1
AS 2005.21.2
AS 2005.29
AS 2005.30
AS 2005.40
AS 2067
AS 2381.1
AS 2381.2
AS 2381.6
AS 2381.7
AS 2381.10
AS 2430.1
AS 2430.2
AS 2926
AS 3001
The whole as modified by
regulation 401 of the
Principal Regulations as
amended by regulation 10
of these Regulations
Endnotes
-- 51 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
50
ENDNOTES—continued
Statutory Rule
Provision
Title of applied, adopted
or incorporated
document
Matter in applied,
adopted or incorporated
document
AS 3002
AS 3004
AS 3491.1
AS 3439.2
AS 3439.3
AS 3439.4
AS/NZS 2053.1
AS/NZS 2053.2
AS/NZS 2293.1
AS/NZS 2293.2
AS/NZS 2293.3
AS/NZS 2430.3
AS/NZS 2648.1
AS/NZS 3003
AS/NZS 3008.1.1
AS/NZS 3012
AS/NZS 3013
AS/NZS 3100
AS/NZS 3108
AS/NZS 3832
Regulation
10(1)(t)
AS/NZS 3012 which
incorporates:
AS 3000
AS 2790
AS 3439.4
AS 1939.7
AS 2005.10
AS 2005.20
AS 2005.21
AS 2005.21.1
AS 2005.21.2
AS 2005.29
AS 2005.30
AS 2005.40
AS 2184
AS 1930
AS/NZS 3008.1.1
The whole
-- 52 of 53 --
S.R. No. 3/2001
Electricity Safety (Installations) (Amendment) Regulations 2001
51
ENDNOTES—continued
Statutory Rule
Provision
Title of applied, adopted
or incorporated
document
Matter in applied,
adopted or incorporated
document
AS/NZS 2293.1
AS/NZS 2293.2
AS/NZS 2293.3
AS 3001
AS 3760
Regulation 13 AS/NZS 3000 Clause 7.9.2.2
Regulation 17
inserting new
regulations 417
and 418 in the
Principal
Regulations
Code of Practice on
Electrical Safety For
Work On Or Near High
Voltage Electrical
Apparatus 1999 published
by the Office of the Chief
Electrical Inspector
The whole
Regulation 17
inserting new
regulation 427 in
the Principal
Regulations
AS 3891.1 which
incorporates AS 2700
AS 3891.2
The whole
The whole
Regulation 17
inserting new
regulation 434 in
the Principal
Regulations
AS/NZS 3000 Clauses 3.11.1 and 7.8.11.3
Regulation 17
inserting new
regulation 435 in
the Principal
Regulations
AS/NZS 3000 Clause 3.12.3
Regulation 22 AS/NZS 3000 Clause 7.9.2.2
-- 53 of 53 --