Electricity Safety (Management) Regulations 1999
i
Electricity Safety (Management) Regulations 1999
S.R. No. 140/1999
TABLE OF PROVISIONS
Regulation Page
PART 1—PRELIMINARY 1
1. Objective 1
2. Authorising provisions 1
3. Commencement 1
4. Definitions 1
PART 2—ELECTRICITY SAFETY MANAGERS 3
5. Applications for acceptance 3
6. Details of manager's systems and procedures 3
7. Application fee 4
8. Bond 4
9. Directions of the Office for information 5
10. Change of details 5
11. Records 5
12. Accounts 6
13. Application for exemption 7
PART 3—ELECTRICITY SAFETY MANAGEMENT SCHEMES 8
14. Specified persons 8
15. Scheme description 8
16. Safety assessment 9
17. Exemptions to be specified 10
18. Electrical incidents 11
19. Safety management system 11
20. Electrical work and design, construction, operation and
maintenance of upstream network 12
21. Equipment 13
22. Permit to work system 14
23. Emergency preparedness 15
24. Communications systems 15
25. Internal monitoring, auditing and reviewing 16
26. Training 16
27. Published technical standards to be used 17
28. Records 17
-- 1 of 22 --
Regulation Page
ii
29. Application fee 18
30. Acceptance fee 18
31. Annual administration fee 18
32. Rebate of fees 19
33. Application for exemption 19
__________________
SCHEDULE—Maximum amount of bank guarantee 20
═══════════════
-- 2 of 22 --
1
STATUTORY RULES 1999
S.R. No. 140/1999
Electricity Safety Act 1998
Electricity Safety (Management) Regulations 1999
The Governor in Council makes the following Regulations:
Dated: 14 December 1999
Responsible Minister:
STEVE BRACKS
Treasurer
HELEN DOYE
Clerk of the Executive Council
PART 1—PRELIMINARY
1. Objective
The objective of these Regulations is to provide
for the requirements, procedures, fees and other
matters relating to the acceptance of electricity
safety managers and electricity safety
management schemes.
2. Authorising provisions
These Regulations are made under sections 149A,
150 and 157 of the Electricity Safety Act 1998.
3. Commencement
These Regulations come into operation on
31 December 1999.
4. Definitions
-- 3 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
2
In these Regulations—
"employer operator" means a scheme operator
referred to in section 107(1)(a) of the Act;
"function" means a relevant function for which
acceptance as an electricity safety manager is
sought;
"network operator" means a scheme operator
referred to in section 107(1)(b) of the Act;
"published technical standard" means a
document giving technical information,
guidance or advice published by—
(a) Standards Australia; or
(b) Standards New Zealand; or
(c) the British Standards Institute; or
(d) the International Organisation for
Standardisation (IOS); or
(e) the International Electrotechnical
Commission; or
(f) any similar standards organisation
within or outside Australia approved
by the Office; or
(g) the Office;
"the Act" means the Electricity Safety Act
1998.
_______________
-- 4 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
3
PART 2—ELECTRICITY SAFETY MANAGERS
5. Applications for acceptance
An application for acceptance as an electricity
safety manager must specify—
(a) the name, position, business address and
telephone number of—
(i) the applicant; and
(ii) the person substantially responsible for
the preparation and submission of the
application or any part of the
application; and
(iii) the person who will have management
or control of the exercise of the
functions; and
(b) the name, position, business address and
telephone number and duties of any person
who will be responsible for the exercise of
the functions; and
(c) the particulars of the systems and procedures
referred to in regulation 6 to be followed for
the proper exercise of the functions.
6. Details of manager's systems and procedures
(1) The electricity safety manager's systems must
specify—
(a) the means by which the electricity safety
manager will ensure that the exercise of the
functions is in accordance with the Act and
the regulations under the Act; and
(b) the key performance indicators to be used to
determine the electricity safety manager's
level of compliance with the Act and the
regulations under the Act; and
r. 5
-- 5 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
4
(c) the work systems and staffing systems to be
used in the exercise of the functions to
ensure, as far as practicable, that—
(i) each area of work in relation to the
exercise of a function is assessed to
identify the minimum qualifications,
proficiency and experience
requirements for a person assigned to
carry out that work; and
(ii) only persons with the qualifications,
proficiency and experience appropriate
to a function to be exercised are
assigned to carry out that work; and
(iii) any training necessary for persons
assigned to carry out that work is
provided.
(2) The electricity safety manager's procedures must
specify—
(a) the processes to be used by the electricity
safety manager for monitoring, auditing and
reviewing the procedures, systems and
standards specified in the electricity safety
manager's application; and
(b) the methods by which any deficiencies in the
processes referred to in paragraph (a) will be
regularly and systematically identified; and
(c) the methods by which the processes referred
to in paragraph (a) will be regularly and
systematically improved.
7. Application fee
The fee for an application under section
98(2)(c)(ii) of the Act is $1000.
8. Bond
r. 7
-- 6 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
5
(1) The Office may require an accepted electricity
safety manager to pay, in respect of a function
specified in column 1 of the Table in the
Schedule, a bond in the form of a bank guarantee
of an amount not exceeding that specified in
column 2 of the Table opposite that function.
(2) If an electricity safety manager does not—
(a) comply with any condition to which his or
her acceptance is subject; or
(b) perform the functions in accordance with the
Act or the regulations under the Act; or
(c) comply with a direction under section 104 or
105 of the Act—
the Office is entitled to the bond or part of the
bond as compensation for any loss or damage
suffered by the Office because of the non-
compliance or non-performance.
9. Directions of the Office for information
An accepted electricity safety manager must
provide information required by the Office in
accordance with a direction under section 104(2)
of the Act within 10 business days after the date
the direction was given.
10. Change of details
It is a prescribed condition of an acceptance of an
electricity safety manager that the accepted
electricity safety manager notify the Office of any
change to the positions or persons specified in
regulation 5(a)(iii) and (b) within 10 business
days after the change occurs.
11. Records
r. 11
-- 7 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
6
(1) An accepted electricity safety manager must keep
the following records—
(a) written applications, documents
accompanying applications, additional
information in respect of any application and
correspondence received by the electricity
safety manager in the exercise of his or her
functions;
(b) details of licences, registrations, approvals
and certifications that have been granted,
given, refused or withdrawn by the
electricity safety manager in the exercise of
his or her functions;
(c) reports setting out the electricity safety
manager's level of compliance with the Act
and the regulations under the Act as
determined by the key performance
indicators;
(d) reports of the results of monitoring, auditing
and reviewing the procedures, systems and
standards referred to in regulation 6(2)(a);
(e) reports setting out the deficiencies in the
processes identified by the methods referred
to in regulation 6(2)(b) and the
improvements made to those processes.
(2) The records must be kept for a period of 7 years
after the creation of the record.
12. Accounts
An accepted electricity safety manager must
keep—
(a) proper accounts and records of the
transactions and affairs of the electricity
safety manager; and
-- 8 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
7
(b) any other working papers that are necessary
to explain the methods and calculations by
which the accounts are made up; and
(c) any other records that sufficiently explain the
financial operations and financial position of
the electricity safety manager.
13. Application for exemption
(1) The Office may, on the application of an accepted
electricity safety manager, exempt the electricity
safety manager from any of the requirements of
these Regulations.
(2) An application must be in writing and state—
(a) the name, address and telephone number of
the applicant; and
(b) the exemption requested; and
(c) the reasons for applying for the exemption.
_______________
r. 13
-- 9 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
8
PART 3—ELECTRICITY SAFETY MANAGEMENT
SCHEMES
14. Specified persons
An electricity safety management scheme must
specify—
(a) the name, address and telephone number of
the scheme operator; and
(b) in the case of an employer operator—
(i) the names and qualifications of persons
nominated to carry out the electrical
work under the scheme; and
(ii) the name, position, business address
and telephone number of the person
who has management or control of the
electrical installation or electrical
equipment on which the electrical work
is required to be carried out;
(c) in the case of a network operator, the name,
position, business address and telephone
number of the person who has management
or control of the upstream network.
15. Scheme description
(1) An electricity safety management scheme
submitted by an employer operator must contain a
description of the electrical work to which the
scheme relates and the electrical installation or
electrical equipment requiring that work.
(2) An electricity safety management scheme
submitted by a network operator must contain a
description of the design, construction, operation
and maintenance of the upstream network to
which the scheme relates.
r. 14
-- 10 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
9
(3) The description must provide sufficient
information to enable the Office to identify the
location, extent and scope of the electrical
installation or electrical equipment requiring that
work or the network operator's upstream network
and to assess the risks associated with the safety
of the electrical installation, electrical equipment
or the upstream network.
(4) An electricity safety management scheme must set
out a system for notifying the Office of any
change to the positions or persons specified in the
electricity safety management scheme within
10 business days after the change occurs.
16. Safety assessment
An electricity safety management scheme must
contain a safety assessment relating to the
carrying out of electrical work for the employer
operator or to the network operator's upstream
network that—
(a) specifies the name, qualifications, position,
business address and telephone number of
the person responsible for making the safety
assessment; and
(b) describes the methodology used and
investigations undertaken for the safety
assessment; and
(c) assesses and records systematically and in
detail the hazards and risks associated with
the electrical installation, electrical
equipment or the upstream network,
including the likelihood and consequences
of—
(i) any serious electrical incident; and
(ii) any incident in which a person makes
accidental contact involving electricity
r. 16
-- 11 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
10
with the electrical installation or
equipment or with the upstream
network or receives an electric shock as
the result of direct or indirect contact
with the electrical installation or
equipment or with the upstream
network; and
(d) describes the measures taken or to be taken
to, as far as practicable—
(i) prevent those hazards; and
(ii) reduce those risks; and
(iii) maintain the level of safety required
under the Act and the regulations under
the Act; and
(e) specifies the extent to which the
communication systems need to operate in
emergencies.
17. Exemptions to be specified
An electricity safety management scheme must
specify—
(a) all provisions of the regulations relating to
the installation and operation of electrical
installations or supply networks from which
the scheme operator seeks to be exempted;
and
(b) all provisions of the regulations relating to
the carrying out of a class or type of
electrical work and the provisions of the Act
referred to in section 113(2) of the Act from
which the scheme operator proposes that any
person authorised under the scheme to carry
out that class or type of electrical work will
be exempted.
r. 17
-- 12 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
11
18. Electrical incidents
(1) The electricity safety management scheme must
specify the standards to be used for recording and
investigating—
(a) any serious electrical incident involving the
electrical installation or electrical equipment
of an employer operator or a network
operator's upstream network to which the
scheme relates; and
(b) any incident in which a person has made
accidental contact involving electricity with
the electrical installation or equipment or
with the upstream network or has received
an electric shock as the result of direct or
indirect contact with the electrical
installation or equipment or with the
upstream network.
(2) The electricity safety management scheme must
specify the management systems to be used for
reviewing and taking action on the information
recorded or the results of the investigations
referred to in sub-regulation (1).
19. Safety management system
(1) An electricity safety management scheme must
specify a safety management system in relation to
the safety of—
(a) the electrical work to be carried out by the
persons nominated by the employer operator;
or
(b) the design, construction, operation and
maintenance of the upstream network of the
network operator.
r. 18
-- 13 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
12
(2) The safety management system must contain a
safety policy and the methods and procedures
required by regulations 20, 21, 22, 23, 24, 25, 26
and 27 by which the policy is to be implemented.
(3) The safety management system must specify the
following details—
(a) the name, position, business address and
telephone number of—
(i) each person responsible for determining
the safety policy; and
(ii) each person responsible for the
implementation of the safety policy and
his or her duties; and
(b) the means by which the safety policy is
communicated to all persons required to
implement the policy; and
(c) the key performance indicators used to
determine the scheme operator's level of
compliance with the electricity safety
management scheme, the relevant provisions
of the Act and of the regulations under the
Act.
20. Electrical work and design, construction, operation
and maintenance of upstream network
(1) The safety management system must specify the
means by which an employer operator will ensure
that electrical work—
(a) is adequate for the safe operation of the
electrical installation or electrical equipment;
and
(b) takes into account the results of the safety
assessment for the scheme; and
r. 20
-- 14 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
13
(c) meets any published technical standards
specified in the safety management system;
and
(d) is carried out by the persons nominated to
carry out the work.
(2) The safety management system must specify the
means by which a network operator will ensure
that the design, construction, installation,
operation and maintenance of the upstream
network and any modification of the upstream
network—
(a) are adequate to ensure the safe operation and
structure of the upstream network; and
(b) take into account the results of the safety
assessment for the upstream network; and
(c) meet any published technical standards
specified in the safety management system;
and
(d) provide adequate means of automatically
isolating the upstream network or any part of
the network in the event of an emergency;
and
(e) provide adequate means of providing access
for servicing and maintenance of the
upstream network and associated equipment;
and
(f) provide adequate means of maintaining the
structure and operation of the upstream
network; and
(g) provide adequate means of preventing
unauthorised access by the public to the
upstream network.
21. Equipment
The safety management system must specify—
r. 21
-- 15 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
14
(a) the equipment that is essential to ensure the
safety of the electrical installation, electrical
equipment or the upstream network to which
the scheme relates; and
(b) the systems in place to ensure that the
equipment referred to in paragraph (a)—
(i) operates in normal conditions and, to
the extent it is intended to function, in
an emergency; and
(ii) is tested and maintained.
22. Permit to work system
(1) The safety management system must specify all
work that may affect the safety of the electrical
installation, electrical equipment or upstream
network to which the scheme relates.
(2) If work is specified under sub-regulation (1), a
permit to work system must be established and
maintained as part of the electricity safety
management scheme.
(3) A permit to work system must—
(a) prohibit any person who does not have a
written permit to work issued by a person
authorised by the scheme operator from—
(i) having access to the electrical
installation or equipment or the
upstream network or parts of the
electrical installation or equipment or
upstream network to which the scheme
relates; and
(ii) performing work specified under sub-
regulation (1); and
(b) specify the position of the person who is
authorised by the scheme operator to issue
permits to work; and
r. 22
-- 16 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
15
(c) make provision to ensure that persons
issuing permits to work and persons
requiring permits to work are competent and
are provided with appropriate training,
procedures, tools, equipment and emergency
support.
23. Emergency preparedness
The safety management system must specify—
(a) a response plan that addresses all reasonably
foreseeable emergencies arising from the
hazards and risks that have been identified as
a result of the safety assessment; and
(b) in the case of an employer operator, the
means by which the operator will ensure the
continued safety of electrical work being
carried out on electrical installations and
electrical equipment; and
(c) in the case of a network operator, the means
by which the operator will ensure the
continued safe operation and structure of the
upstream network.
24. Communications systems
(1) The safety management system must specify
communications systems—
(a) within the organisation of the scheme
operator; and
(b) between the scheme operator and—
(i) any other person who may be affected
by an emergency; and
(ii) the relevant fire control authorities and
other emergency service authorities;
and
r. 23
-- 17 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
16
(iii) the Office.
(2) The safety management system must provide for
communications systems that are—
(a) adequate to handle—
(i) a reasonably foreseeable emergency
relating to the electrical installation or
electrical equipment or upstream
network; and
(ii) the normal operational requirements of
the electrical installation or electrical
equipment or upstream network; and
(b) protected so as to be capable of operation in
an emergency to the extent specified by the
safety assessment.
25. Internal monitoring, auditing and reviewing
The safety management system must specify—
(a) the processes by which the scheme operator
will monitor, audit and review—
(i) the recording and investigation of
electrical incidents required by
regulation 18(1); and
(ii) the implementation of the safety policy
required by regulation 19(2); and
(b) the methods by which any deficiencies in the
processes referred to in paragraph (a) will be
regularly and systematically identified; and
(c) the methods by which the processes referred
to in paragraph (a) will be regularly and
systematically improved.
26. Training
The safety management system must specify the
work and staffing systems used in relation to the
r. 25
-- 18 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
17
electrical installation or electrical equipment of an
employer operator or the upstream network of a
network operator to ensure, as far as practicable,
that—
(a) only persons with the qualifications,
proficiency and experience appropriate to the
work that may affect the safety of the
electrical installation or electrical equipment
or the upstream network are assigned to
carry out that work; and
(b) any training necessary for persons assigned
to carry out that work is provided.
27. Published technical standards to be used
A safety management system must not specify
technical standards other than published technical
standards to be applied in connection with
electrical work to be carried out by the persons
nominated by an employer operator or in the
design, construction, operation and maintenance
of the upstream network of a network operator.
28. Records
(1) A scheme operator must keep the following
records relating to the electricity safety
management scheme—
(a) a report setting out the scheme operator's
level of compliance with the electricity
safety management scheme and the relevant
provisions of the Act and of the regulations
under the Act as determined by the key
performance indicators;
(b) the results of monitoring, auditing and
reviewing—
(i) the recording and investigation of
electrical incidents referred to in
regulation 25(a)(i); and
r. 27
-- 19 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
18
(ii) the implementation of the safety policy
referred to in regulation 25(a)(ii);
(c) a report setting out any deficiencies in the
processes identified by the methods referred
to in regulation 25(b) and the improvements
made to those processes.
Penalty: 20 penalty units.
(2) A scheme operator must make available to the
Office any record referred to in sub-regulation (1)
that is requested by the Office during the normal
business hours of the scheme operator.
(3) The records must be kept—
(a) at an address nominated by the scheme
operator in the electricity safety management
scheme; and
(b) in a manner that makes their retrieval
reasonably practicable; and
(c) in a secure manner; and
(d) for the period of 7 years after the creation of
the record.
29. Application fee
The fee for an application under section 107(2)(a)
of the Act is $1000.
30. Acceptance fee
The prescribed fee for acceptance of an electricity
safety management scheme is $1000.
31. Annual administration fee
(1) The prescribed annual administration fee for—
(a) an employer operator who has nominated—
(i) not more than 5 persons to carry out the
electrical work under the electricity
safety management scheme is $3500;
r. 29
-- 20 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
19
(ii) between 6 and 50 persons to carry out
the electrical work under the electricity
safety management scheme is $4500;
(iii) 51 or more persons to carry out the
electrical work under the electricity
safety management scheme is $6500;
(b) a network operator is $10 000.
(2) The annual administration fee must be paid to the
Office within 5 business days after the date of the
Order approving the electricity safety
management scheme and within 5 business days
before each anniversary of that date.
32. Rebate of fees
The Office may rebate the payment of an annual
administration fee if the compliance audits under
section 114 of the Act demonstrate compliance
with the accepted electricity safety management
scheme.
33. Application for exemption
(1) The Office may, on the application of the scheme
operator, exempt an electricity safety management
scheme from any of the requirements of these
Regulations.
(2) An application must be in writing and state—
(a) the name, address and telephone number of
the applicant; and
(b) the exemption requested; and
(c) the reasons for applying for the exemption.
__________________
r. 32
-- 21 of 22 --
S.R. No. 140/1999
Electricity Safety (Management) Regulations 1999
20
SCHEDULE
Column 1
Function
Column 2
Maximum amount of
bank guarantee
Registration and renewal of registration of
electrical contractors under section 31 of the
Act $400 000
Licensing of electrical workers and renewal of
licences under section 40 of the Act $1 000 000
Issuing certificates of compliance of electrical
equipment under section 55 of the Act $100 000
Issuing certificates of acceptance of electrical
equipment under section 56 of the Act $100 000
Approving electrical equipment under section
58 of the Act $300 000
Requiring modifications to be made to
approved electrical equipment under section
60 of the Act $100 000
Approving samples of prescribed electrical
equipment under section 61 of the Act $20 000
Withdrawing approval of electrical equipment
under section 62 of the Act $100 000
═══════════════
Sch.
-- 22 of 22 --