Electricity Safety (Network Assets) Regulations 1997
i
Electricity Safety (Network Assets) Regulations
1997
S.R. No. 5/1997
TABLE OF PROVISIONS
Regulation Page
PART 1—PRELIMINARY 1
1. Objectives 1
2. Authorising provisions 1
3. Commencement 2
4. Revocation 2
5. Definitions 2
6. Application of Regulations 7
7. Application for exemptions 7
PART 2—GENERAL REQUIREMENTS 9
8. Duties of Network Operator 9
9. Incidents to be reported 9
10. Audit 12
11. Obligations on Network Operators concerning underground line 12
12. Obligations on distribution companies concerning underground
lines 14
PART 3—STANDARDISATION OF SUPPLY NETWORKS 15
13. Standard Networks 15
PART 4—NETWORK ASSETS (OBLIGATIONS OF NETWORK
OPERATORS) 16
14. Design, construction, operation and maintenance 16
15. Earthing and electrical protection 17
16. Earthing of low voltage electrical systems of supply 18
17. Electricity Safety (Network Assets) Code 1996 18
PART 5—NETWORK ASSETS (PUBLIC SAFETY) 19
18. Sporting activities 19
19. Aircraft 19
20. Entangled objects 19
-- 1 of 35 --
Regulation Page
ii
21. Blasting and fires 20
22. Protection of underground assets from damage 20
23. Excavating and altering levels 21
24. Clearances from structures and equipment 22
25. Placing materials 28
26. Transportation 28
27. Tree clearing 30
28. Damage and interference 30
29. Permits, conditions, revocation 31
═══════════════
NOTES 33
-- 2 of 35 --
1
STATUTORY RULES 1997
S.R. No. 5/1997
State Electricity Commission Act 1958
Electricity Safety (Network Assets) Regulations
1997
The Governor in Council makes the following Regulations:
Dated: 21 January 1997
Responsible Minister:
ALAN STOCKDALE
Treasurer
A. WILTSHIRE
Acting Clerk of the Executive Council
PART 1—PRELIMINARY
1. Objectives
The objectives of these Regulations are—
(a) to establish the minimum safety criteria for
the generation, transmission, distribution and
supply of electricity; and
(b) to generally protect people and property
from risk and damage associated with the
assets of the supply network.
2. Authorising provisions
These Regulations are made under sections 110
and 111 of the State Electricity Commission
Act 1958.
-- 3 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
2
3. Commencement
These Regulations come into operation on 29
January 1997.
4. Revocation
(1) The Electricity Supply and Construction
Regulations 1988 1 are revoked.
(2) The Electrical Works Protection Regulations
19882 are revoked.
5. Definitions
(1) In these Regulations—
"the Act" means the State Electricity
Commission Act 1958;
"active", in relation to conductors, means—
(a) a conductor of a supply network which
is maintained at a difference of
potential from—
(i) a neutral conductor; or
(ii) an earthed conductor; or
(b) if a supply network does not include a
neutral or earthed conductor—all of the
conductors of the network;
"aerial line" means any bare, covered or
insulated electric line placed above the
ground and in the open air but does not
include bus bars or any direct current
conductors used in a system of electric
traction;
"AS" means an Australian Standard, as published
and amended by Standards Australia on the
date these Regulations come into operation;
r. 3
-- 4 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
3
"assets" includes buildings (other than buildings
mainly used for administrative purposes),
machinery, and electric lines or any other
matter or thing required to generate,
transmit, distribute or supply electricity of
the electricity corporation or Network
Operator;
"chief electrical inspector" means the chief
electrical inspector appointed under Part 4 of
the Electricity Industry Act 1993;
"circuit" means a number of conductors
connected together for the purpose of
carrying electric current;
"the Code" means the Electricity Safety
(Network Assets) Code 1996;
"conductor" means a wire, cable or form of
metal designed for carrying electric current,
other than wires, cables or other forms of
metal directly used in converting electrical
energy into another form of energy;
"corporation" includes an incorporated
association;
"distribution company" has the same meaning
as in the Electricity Industry Act 1993;
"electric line" means a conductor used for the
purpose of transmitting, distributing or
supplying electricity and includes any
casing, coating, covering, tube, pipe, pole,
post, frame, bracket or insulator enclosing,
surrounding or supporting the conductor or
any part of the conductor or any apparatus
connected in conjunction with the conductor
for the purpose of transmitting, distributing
or supplying electricity;
r. 5
-- 5 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
4
"electrical installation" has the same meaning as
in section 46 of the Act;
"electricity corporation" has the same meaning
as in the Electricity Industry Act 1993;
"high voltage", in relation to an electric line or
electrical equipment, means the use of the
electric line or electrical equipment in
connection with electricity at voltages
exceeding 1000 Volts alternating current or
1500 Volts direct current;
"HV" means high voltage;
"insulated" means contained within a material or
medium (including air) in order to limit the
flow of electric current between conductors
at different potentials;
"insulated conductor" means a conductor which
is wholly covered with insulating material in
accordance with the Electricity Safety
(Network Assets) Code 1996;
"live" means the condition of having a difference
of electrical potential to earth and includes
all metal connected to the neutral conductor
of the supply network except earthing
conductors;
"low voltage" means voltage exceeding 32 Volts
alternating current or 115 Volts direct
current but not exceeding 1000 Volts
alternating current or 1500 Volts direct
current;
"LV" means low voltage;
"maximum design temperature" means the
maximum temperature which a specific
conductor may reach under the influence of
load current (excluding fault current), the
r. 5
-- 6 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
5
ambient temperature of the air and solar
radiation;
"multiple earthed neutral system" means a
system of earthing in which the parts of an
electrical installation required by the State
Electricity Commission Wiring
Regulations 1992 to be earthed—
(a) are connected to the general mass of
earth; and
(b) are connected within the installation to
the neutral conductor of the system of
supply;
"Network Operator" means any person who
owns, constructs or operates any electric
line, plant or equipment for the purposes of
the generation, transmission, distribution or
supply of electricity;
"neutral conductor" means a conductor in a
circuit of a system of supply which is
maintained at an intermediate and
approximate uniform electrical potential in
respect of the other conductors of the circuit,
or the conductor of a two-wire system which
is earthed at its origin;
"premises" means any house, building or
structure including any associated land;
"protective equipment" means equipment which
is intended to isolate the active conductors of
a circuit if an electrical fault occurs;
"road" means any way ordinarily used by
vehicular traffic;
"service line" means the part of a Network
Operator’s supply network that forms the
terminating span of an electric line—
r. 5
-- 7 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
6
(a) constructed or designed or ordinarily
used for the supply of electricity at low
voltage; and
(b) through which electricity is, or is
intended to be, supplied by a Network
Operator to a consumer either from a
main or directly from the premises or
structure of the Network Operator;
"substation" means any premises or place in
which high voltage supply is converted,
controlled or transformed;
"supply" means supply of electricity;
"supply network" means a network comprised in
whole or part of electric lines, generators,
substations and any other matter or thing
required for the purposes of the generation,
transmission, distribution or supply of
electricity;
"system of supply" means a system of mains for
receiving electricity from a generating
station, substation or transformer and
conveying it for distribution to consumers at
the same nominal voltage throughout
between active and neutral conductors;
"U" means the nominal voltage of an electric
line;
"underground line" means an electric line which
is placed under the ground, and includes any
part of the line that is above the ground.
(2) A reference to "its" in these Regulations is to be
read as including a reference to "his or hers",
unless the context otherwise requires.
r. 5
-- 8 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
7
6. Application of Regulations
(1) These Regulations apply to all electric lines, plant
and equipment of a Network Operator, except
electric lines, plant and equipment—
(a) that are contained within a mine and for use
within the mine; or
(b) that form part of an electrical installation
which is located on land, other than public
land (as defined in section 58 of the Act),
where the person responsible for the
electrical installation owns or leases the land,
or has rights over the land pursuant to an
easement under section 12(2) of the
Subdivision Act 1988, for the purposes of
the supply of electricity to a subdivision.
(2) Sub-regulation (1) is not intended to restrict the
application of regulation 9.
(3) In this regulation—
"mine" means any part of the land on which
mining is being carried out under a mining
licence issued under the Mineral Resources
Development Act 1990.
7. Application for exemptions 3
(1) The chief electrical inspector may, on application
made to him or her in writing, exempt a Network
Operator from any provision of these Regulations,
with or without conditions.
(2) Every application must be accompanied by—
(a) a detailed statement of the reasons the
exemption is sought; and
(b) a statement from the Network Operator that
granting the exemption would not lead to a
significant decrease in electrical safety.
r. 6
-- 9 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
8
(3) A Network Operator must comply with any
conditions of an exemption granted under sub-
regulation (1).
Penalty: 10 penalty units.
_______________
r. 7
-- 10 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
9
PART 2—GENERAL REQUIREMENTS
8. Duties of Network Operator
A Network Operator must—
(a) take reasonable care to ensure that every part
of its circuits function in a manner that
avoids injury to any person or damage to any
property; and
(b) ensure that each active conductor of any of
its—
(i) high voltage electric lines; or
(ii) other high voltage equipment—
is protected by an automatic disconnecting
device; and
(c) ensure that all its supply networks are
earthed; and
(d) ensure that the point at which each of its
supply networks is earthed is located so as to
permit the connection of devices for
protecting the network against earth faults;
and
(e) maintain all its electrical equipment in a
condition that is not likely to cause death or
injury to any person or damage to any
property.
Penalty: 75 penalty units.
9. Incidents to be reported
(1) If as a result of any incident of an electrical
nature—
(a) any person—
r. 8
-- 11 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
10
(i) is killed; or
(ii) is injured; or
(iii) receives medical attention; or
(iv) appears likely to require the immediate
attention of a medical practitioner; or
(v) receives an electric shock as a result of
contact with any live high voltage line,
equipment or apparatus used for the
generation, transmission, distribution or
supply of electricity; or
(b) serious property damage or a serious
reduction in the level of public safety has
occurred or is likely to occur—
a person to whom this sub-regulation applies must
immediately report all of the details within their
knowledge regarding the incident to the chief
electrical inspector.
Penalty: 50 penalty units.
(2) Sub-regulation (1) applies to—
(a) the Network Operator within whose area of
generation, transmission, distribution or
supply the incident occurs; and
(b) the Network Operator who owns the assets
involved in the incident; and
(c) any fire control authority attending the
incident.
(3) If any person—
(a) makes accidental contact with any live high
voltage line, equipment or apparatus used for
the generation, transmission, distribution or
supply of electricity; or
r. 9
-- 12 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
11
(b) receives an electric shock as a result of direct
or indirect contact with any of the assets of a
Network Operator or an electrical
installation—
a person to whom this sub-regulation applies must
report all of the details within their knowledge
regarding the incident to the chief electrical
inspector within one month of the incident.
Penalty: 50 penalty units.
(4) Sub-regulation (3) applies to—
(a) the Network Operator within whose area of
generation, transmission, distribution or
supply the incident occurs; and
(b) the Network Operator who owns the assets
involved in the incident.
(5) A fire control authority investigating any fire of
an electrical nature must report all of the details
within the knowledge of the fire control authority
to the chief electrical inspector within one month
of the end of the investigation.
Penalty: 50 penalty units.
(6) In this regulation—
"fire control authority" means—
(a) the Metropolitan Fire Brigades Board,
if within a metropolitan fire district;
(b) the Secretary of the Department of
Natural Resources and Environment, if
within a national park, state forest or
protected public land;
r. 9
-- 13 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
12
(c) the Country Fire Authority if the area is
within the country area of Victoria
within the meaning of the Country
Fire Authority Act 1958.
10. Audit
(1) A Network Operator must have a plan which
incorporates a requirement to test, inspect and
maintain the Network Operator's assets to ensure
that the requirements of these Regulations are
met.
Penalty: 75 penalty units.
(2) A Network Operator must give to the chief
electrical inspector any information that the chief
electrical inspector requests in writing concerning
the Network Operator's testing, inspection and
maintenance procedures and the results of those
procedures and must comply with the request
within 14 business days of the request.
Penalty: 75 penalty units.
(3) The chief electrical inspector may undertake
independent audits of the procedures used and
information provided to monitor compliance with
these Regulations and to assess electrical safety
performance.
11. Obligations on Network Operators concerning
underground line
(1) A Network Operator must maintain a record of all
underground lines under the control of the
Network Operator.
Penalty: 75 penalty units.
(2) A Network Operator (other than the Public
Transport Corporation) who owns an underground
line within a distribution area must, before
energising the line or within 2 business days of
r. 10
-- 14 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
13
relocating the line, give the responsible person
sufficient information to enable every cable of the
line to be located and identified.
Penalty: 75 penalty units.
(3) The responsible person must issue to the Network
Operator, on receipt of information under sub-
regulation (2), confirmation of the receipt of the
information.
(4) In the case of an underground line that is
energised at the time that these Regulations come
into operation, the Network Operator who owns
the line must give the responsible person the
records required under sub-regulation (1) within 6
months of the date on which these Regulations
come into operation.
Penalty: 75 penalty units.
(5) Sub-regulation (4) does not apply to the Public
Transport Corporation.
(6) The Public Transport Corporation must keep a
register containing details sufficient to enable
every cable of all underground lines that are under
the control of the Corporation to be located and
identified.
(7) The Public Transport Corporation must ensure
that the information recorded under sub-regulation
(6) is available to the public during normal
business hours.
(8) In this regulation and in regulation 12—
"distribution area" means the area defined under
a distribution company's distribution licence
issued under the Electricity Industry Act
1993;
r. 11
-- 15 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
14
"responsible person" means—
(a) the asset recording service specified in
relation to a distribution area, or part of
a distribution area, by the chief
electrical inspector; or
(b) if no service has been specified, the
distribution company in whose area the
line is situated.
12. Obligations on distribution companies concerning
underground lines
(1) A distribution company must keep a register
containing details sufficient to enable every cable
of all underground lines that are under its control
within its distribution area to be located and
identified.
Penalty: 75 penalty units.
(2) The distribution company must also record in the
register any information that is given to it under
regulation 11(2) within 7 business days of
receiving that information.
Penalty: 50 penalty units.
(3) The distribution company must ensure that the
information received under regulation 11(2) and
recorded under sub-regulation (1) is available to
the public during normal business hours.
Penalty: 50 penalty units.
_______________
r. 12 r. 12
-- 16 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
15
PART 3—STANDARDISATION OF SUPPLY NETWORKS
13. Standard Networks
(1) A Network Operator (other than the Public
Transport Corporation) must ensure that all supply
networks coming into operation after the date of
the commencement of these Regulations are
designed and constructed to provide electricity
consumers with a standard network for the supply
of electricity.
Penalty: 50 penalty units.
(2) In this regulation—
"standard network" means a network that
complies with AS 2926-1987 with regard to
the operating characteristics of that network.
_______________
r. 13
-- 17 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
16
PART 4—NETWORK ASSETS (OBLIGATIONS OF
NETWORK OPERATORS)
14. Design, construction, operation and maintenance
(1) A Network Operator of any supply network
comprised of—
(a) aerial lines; or
(b) service lines; or
(c) underground lines; or
(d) underground service lines; or
(e) substations (including generators); or
(f) equipment and metering—
must design, construct, operate and maintain the
supply network with reasonable care to avoid
injury to any person or damage to any property.
Penalty: 75 penalty units.
(2) Without intending to limit sub-regulation (1), the
Network Operator must ensure that—
(a) the safety clearances set out for—
(i) aerial lines and service lines in section
1.2.9(1), (2), (3), (4) and (7) of the
Code; and
(ii) underground lines and service lines in
sections 2.3.2 and 2.3.3 of the Code;
and
(iii) substations in sections 3.2.5(3), 3.2.6(3)
and 3.2.7(c) and (d) of the Code—
are maintained at all times with respect to the
supply network; and
r. 14
-- 18 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
17
(b) that all precautions necessary are taken to
prevent unauthorised access to the network;
and
(c) that warning notices prohibiting the entry of
unauthorised people are located at all
entrances to substation buildings and
compounds of the network; and
(d) that the assets of the network do not cause
fire.
Penalty: 75 penalty units.
15. Earthing and electrical protection
(1) A Network Operator of any supply network must
ensure that the earthing and protection systems of
the network, including the network's conductors,
fittings and equipment are designed, installed,
operated and maintained with reasonable care to
avoid injury to any person or damage to any
property.
(2) Without intending to limit sub-regulation (1), the
Network Operator must have adequate measures
in place for—
(a) the isolation of abnormal electrical
conditions likely to cause damage or risk to
people, property or assets; and
(b) the management of step and touch voltages
near assets associated with the circuit in
accordance with section 4.2.7 of the Code;
and
(c) the isolation of abnormal electrical
conditions likely to cause damage to low
voltage overhead and underground services
in accordance with sections 4.2.6 (1), (2) and
(3) of the Code.
Penalty: 75 penalty units.
r. 15
-- 19 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
18
16. Earthing of low voltage electrical systems of supply
A Network Operator of any low voltage system of
supply must ensure that the system is earthed by
means of—
(a) a multiple earthed neutral system installed
and maintained in accordance with section
4.2.4(2) of the Code; or
(b) a method approved by the chief electrical
inspector.
Penalty: 75 penalty units.
17. Electricity Safety (Network Assets) Code 1996
The Electricity Safety (Network Assets) Code
1996 may be used as a guide by a court in
determining whether a person is in breach of a
provision of these Regulations.
_______________
r. 16
-- 20 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
19
PART 5—NETWORK ASSETS (PUBLIC SAFETY)
18. Sporting activities
A person must not throw, hit, kick, launch,
discharge, fire or project, or cause to be thrown,
hit, kicked, launched, discharged, fired or
projected, any object—
(a) with intent to strike; or
(b) if there is significant risk that the object will
strike—
any exposed equipment which is necessary or
incidental to the generation, transmission or
distribution of electricity or any electric light or
electric line.
Penalty: 10 penalty units.
19. Aircraft
A person must not, without the written permission
of the Network Operator, fly, launch or release
any kite, aeroplane, glider, balloon, parachute,
model aeroplane or model glider, so that it will, in
the course of its intended flight, or in any
circumstances which could reasonably be
predicted or anticipated, come within 45 metres of
any overhead electric line or other exposed
electrical equipment of a Network Operator.
Penalty: 10 penalty units.
20. Entangled objects
A person must not, without the written permission
of the Network Operator, pull or interfere with
any kite, string, appendage, wire or similar object
resting on or entangled in any electric line or
electrical equipment unless the action is
reasonably necessary to prevent or reduce injury
to a person or damage to property.
r. 18
-- 21 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
20
Penalty: 10 penalty units.
21. Blasting and fires
A person must not, without the written permission
of the Network Operator—
(a) blast or cause blasting to be done; or
(b) light or cause to be lit or allow to remain
alight any fire; or
(c) install equipment or operate processes likely
to create an explosive atmosphere—
in the vicinity of any assets of the Network
Operator in such a manner that the assets are
likely to be damaged or an explosion is likely to
occur.
Penalty: 50 penalty units.
22. Protection of underground assets from damage
A person must not, without the written permission
of the Network Operator—
(a) place or maintain, or cause to be placed or
maintained, any corrosive, abrasive, heavy or
deleterious material or substance above any
underground line of a Network Operator so
as to cause damage or be likely to cause
damage to the underground line; or
(b) make any opening in the ground, road,
footpath or other such surface so as to
endanger any underground line of the
Network Operator.
Penalty: if the person is a corporation, 100
penalty units;
in any other case, 50 penalty units.
r. 21
-- 22 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
21
23. Excavating and altering levels
A person must not, without the written permission
of the Network Operator—
(a) cut away, excavate or remove or cause to be
cut away, excavated or removed, any earth
or material supporting assets of a Network
Operator so as to endanger the stability of
the assets; or
(b) make any excavation deeper than 900mm
within 15000mm of, or deeper than 300mm
within 1500mm of, any tower or tower
structure supporting any electric line or
equipment of a Network Operator; or
(c) make an excavation deeper than 1800mm
within 3000mm of, or deeper than 900mm
within 1500mm of—
(i) any other pole, structure or standard
supporting any electric line or
equipment of a Network Operator; or
(ii) any pole or bed log to which is affixed
a staywire used for the support of the
electric line or equipment; or
(d) make an excavation deeper than 300mm
within 600mm of any wall, fence or
foundation of a substation; or
(e) place any soil, stone, rock or filling or
construct any artificial surface above ground
level below a Network Operator's electric
line or within the vertical projection of any
points to which any conductor of the line
may sway, in a manner to alter the level of
the ground at any place so as to infringe any
permissible clearance in these Regulations
for that line; or
r. 23
-- 23 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
22
(f) place any soil, stone, rock or filling or
construct any artificial surface above ground
level adjacent to a Network Operator's assets
in a manner to alter the level of the ground at
any place so as to infringe any permissible
clearance in these Regulations.
Penalty: 50 penalty units.
24. Clearances from structures and equipment
(1) In this regulation—
"other cable systems" means—
(a) telecommunication and control cables;
or
(b) aerial earthed cables; or
(c) electrolysis drainage cables—
attached to Network Operators' structures
carrying a supply network, or, that are in the
vicinity of a Network Operator's supply
network.
(2) A person must not, without the written permission
of the Network Operator—
(a) build, erect or maintain any structure
(including any scaffolding, building or post)
closer than the relevant distances in Table A
from any point to which an electric line,
service line or other cable system may swing
or sag; or
r. 24
-- 24 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
23
TABLE A
Buildings and
structures
Other cable
systems
service
lines and
U < 1kV
U>1kV
U
<33kV
U >33kV
U <
132kV
U >132kV
U <
220kV
U >
220kV
U <
330kV
U > 330kV
U < 500kV
mm mm mm mm mm mm
(i) Vertically
above those
parts of a
structure
normally
accessible to
pedestrians
3700 4600 4600 6800 8000 9800
(ii) Vertically
above those
parts of a
structure not
normally
accessible but
on which a
person can
stand
2700 3700 4600 6000 7000 8000
(iii) In any
direction from
those parts of a
structure not
normally
accessible to
pedestrians
600 2700 3000 3700 4700 6400
(iv) In any
direction from
those parts of a
structure
normally
accessible to
pedestrians,
windows
openings and
balconies
1500 2700 3000 4600 5500 6400
(v) In any
direction from a
footbridge
4600 4600 4600 6800 8000 9800
(b) place or maintain —
(i) any material within the relevant
distances in Table B of any point to
r. 24
-- 25 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
24
which a part of an electric line, service
line or other cable system may swing or
sag; or
(ii) any timber or inflammable material
within the relevant distances in Table B
of any point to which a part of an
electric line, service line or other cable
system may swing or sag; or
TABLE B Other
cable
systems,
service
lines and
U < 1kV
U >1kV
U < 33kV
U >33kV
U < 132kV
U > 132kV
U < 220kV
U > 220kV
U < 330kV
U > 330kV
U < 500kV
mm mm mm mm mm mm
(i) Any
material—
Horizontal
distances
1500 2100 3000 4600 5500 6400
Vertical
distances
3700 4600 4600 6800 8000 9800
(ii)
Inflammable
materials—
Horizontal
Distances
3000 3000 3000 4600 5500 6400
(c) operate a crane, backhoe, post hole digger,
excavator or other machine or vehicle
equipped with an elevating component or
shear legs or water borne vessel so that any
part of the vehicle or vessel or its load comes
within the distances in Table C of any point
to which a part of an electric line, service
line or other cable system may swing or sag;
or
TABLE C Other cable systems, service lines and
U < 66 000 volts U > 66 000 volts
mm mm
Vertical distances 2000 6000
r. 24
-- 26 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
25
Horizontal distances 2000 6000
(d) erect or maintain conductors of circuits, or
other cable systems, attached to the structure
of a Network Operator; or
(e) erect or maintain conductors of circuits, or
other cable system, which cross the circuit of
an electric line, or other cable systems,
belonging to a Network Operator unless
clearances in excess of those contained in
Table D can be maintained; or
TABLE D Between structures
Upper circuit Lower circuit
Attached to
a common
structure
No wind
condition Wind condition
mm mm mm
(i) LV aerial line Private electric
line (LV) and
other cable
systems
900 Not
permitted
Not permitted
(ii) LV aerial
line
LV aerial line 380 600 380
(iii) Aerial lines
U > 1kV
U < 11kV
Private electric
line (LV) and
other cable
systems
1800 Not
permitted
Not permitted
(iv) Aerial lines
U > 1kV
U < 11kV
LV aerial line or
aerial lines < 11kV
1200 1200 600
(v) Aerial lines
U > 11kV
U < 33kV
Private electric
line (LV) and
other cable
systems
1800 Not
permitted
Not permitted
(vi) Aerial lines
U > 11kV
U < 33kV
LV Aerial line or
aerial lines < 33kV
1200 1200 750
(vii) Aerial lines
U > 33kV
U < 66kV
Private electric
line (LV) and
other cable
systems
2400 Not
permitted
Not permitted
r. 24
-- 27 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
26
(viii) Aerial
lines
U > 33kV
U < 66kV
LV aerial line or
aerial lines < 66kV
1800 1800 1200
Notes relating to Table D—
(1) Any combination of circuits not shown in Table D is
not permitted.
(2) For the purpose of Table D—
(a) no wind condition refers to—
(i) undercrossing conductors at 15 oC with
no wind blowing; or
(ii) overcrossing conductors at maximum
design temperature with no wind
blowing; and
(b) wind condition refers to—
(i) undercrossing conductors at 15 oC, and
displaced by a 500Pa horizontal wind at
right angles to the undercrossing
conductors; or
(ii) overcrossing conductors at maximum
design temperature and not displaced by
wind.
(f) erect a circuit or other cable system unless
the clearance in any direction from such
circuit or other cable system to a structure of
a Network Operator, not supporting the
circuit or other cables system is greater than
that shown in Table E.
Penalty: 50 penalty units
TABLE E— Clearance any direction
Other
cable
system
and
U < 1kV
insulated
conductor
U < 1kV
bare
conductor
U > 1kV
U < 33kV
insulated
conductor
U > 1kV
U < 33kV
bare
conductor
U>3kV
U<132kV
U>132kV
U<220kV
U>220kV
U<330kV
U>330kV
U<500kV
r. 24
-- 28 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
27
mm mm mm mm mm mm mm mm
100 1500 1500 2100 3000 4500 5000 6000
-- 29 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
28
25. Placing materials
A person must not, without the written permission
of the Network Operator—
(a) place or maintain any timber or inflammable
material within 3000mm in any direction of a
wall or fence of any substation, switch yard
or other assets of the Network Operator;
(b) place or maintain any material that will
impede access to any door, gate or entrance
of any substation or switch yard of the
Network Operator or interfere in any way
with the free flow of air through any
openings or fittings used for ventilation in
the walls of such substations or switch yards;
(c) place or maintain any material adjacent to a
wall or fence of any substation, switchyard
or other assets of the Network Operator so as
to enable unauthorised access to that
substation, switchyard or other assets.
Penalty: 50 penalty units.
26. Transportation
(1) A person who transports anything in the vicinity
of a Network Operator's electric line or overhead
assets must ensure that—
(a) at all times during the transportation the
distance between the load transported and
the Network Operator's electric lines and
overhead assets exceeds the minimum
distances prescribed in Table F;
r. 25
-- 30 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
29
TABLE F Other cable
system and
U < 1kV
insulated
conductor
U <132kV
except for
U < 1kV
insulated
conductors
U > 132kV
U < 220kV
U > 220kV
U < 330kV
U > 330kV
U < 500kV
mm mm mm mm mm
(i) vertical
distances
300 1500 3700 4700 6400
(ii) horizontal
distances
300 1500 4600 5500 6400
(b) arrangements satisfactory to the Network
Operator including, where necessary, the
provision of an escort, the de-energising of
electric lines and overhead assets and any
other action to ensure the safety of people,
property and assets have been made before,
and are observed during, the transportation. 4
Penalty: 50 penalty units.
(2) A person intending to rely on sub-regulation
(1)(b) must give to the Network Operator at least
7 days before the commencement of the
transportation a written notice of intention to
undertake the transportation that states—
(a) the nature of the vehicle and the load; and
(b) the height of the load; and
(c) the date and the time of the proposed
movement; and
(d) the starting point and finishing point of the
transportation; and
(e) the proposed route; and
(f) the name and contact address of the transport
operator; and
(g) any other particulars which the Network
Operator may in the circumstances require.
Penalty: 50 penalty units.
r. 26
-- 31 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
30
27. Tree clearing
(1) A person, other than an authorised person, must
not, without written permission from the Network
Operator, cut or clear any tree or part of a tree or
any vegetation unless—
(a) the tree or part of the tree or the vegetation,
in falling, will be too short to encroach on
the clearances stated in regulation 24(2)(c);
or
(b) effective precautions have been taken to
prevent the tree or the part of the tree or the
vegetation from encroaching on the
clearances stated in regulation 24(2)(c).
Penalty: 10 penalty units.
(2) In this regulation—
"authorised person" means a person who holds a
current certificate certifying satisfactory
completion of a training course, approved by
the chief electrical inspector, relating to tree
clearing by non-electrical personnel.
28. Damage and interference
(1) A person must not, without the written permission
of the Network Operator, damage, deface or
interfere with—
(a) any assets of the Network Operator; or
(b) a seal or lock protecting or affixed to
apparatus or any other equipment of the
Network Operator; or
(c) a notice or sign erected by the Network
Operator—
so as to, or be likely to, result in injury to any
person or damage to any property.
Penalty: 50 penalty units.
r. 27
-- 32 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
31
(2) A person must not, without the written permission
of the Network Operator, place or cause to be
placed on any part of any assets of a Network
Operator any board or sign in a manner which
results in injury to any person or damage to any
property or is likely to result in injury to any
person or damage to any property.
Penalty: 10 penalty units.
29. Permits, conditions, revocation
(1) In granting a person permission under this Part, a
Network Operator may impose any conditions the
Network Operator thinks fit which are consistent
with the protection of people and property and the
protection of or prevention of any interference
with any operations, assets, stores or electric lines
of the Network Operator.
(2) A Network Operator may at any time revoke any
permission granted by it under this Part, but the
revocation does not affect the previous lawful
exercise of the permission.
Table of applied, incorporated or adopted matter
Statutory Rule
provision
Title of applied, adopted or
incorporated document
Matter in applied,
adopted or
incorporated
document
Regulation
13(2)
Australian Standard AS 2926
1987
whole document
Regulation
14(2)(a)(i)
Electricity Safety (Network
Assets) Code 1996
Sections 1.2.9(1),
(2), (3), (4), (6)
Regulation
14(2)(a)(ii)
Electricity Safety (Network
Assets) Code 1996
Australian Standard AS 3600
1994
Australian Standard AS 1012.9
1986
Sections 2.3.2 &
2.3.3
section 6.1.1.1
whole document
r. 29
-- 33 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
32
Statutory Rule
provision
Title of applied, adopted or
incorporated document
Matter in applied,
adopted or
incorporated
document
Regulation
14(2)(a)(iii)
Electricity Safety (Network
Assets) Code 1996
Building Code of Australia
Sections 3.2.5(3);
3.2.6(3); 3.2.7(c) &
(d)
Section C
Regulation
15(2)(b)
Electricity Safety (Network
Assets) Code 1996
ESAA Guidelines for the
Design and Maintenance of
Overhead Distribution and
Transmission Lines C(b)1 1991
Section 4.2.7
Clause 12
Regulation
15(2)(c)
Electricity Safety (Network
Assets) Code 1996
Australian/New Zealand
Standard AS/NZS 2053 (series)
1995
Australian Standard AS 1074
1989
Australian Standard AS 3116
1996
Australian Standard AS 3147
1992
Australian Standard AS 3198
1996
Section 4.2.6(1), (2)
& (3)
whole document
whole document
whole document
whole document
whole document
Regulation
16(1)
Electricity Safety (Network
Assets) Code 1996
Australian Standard AS 3000
1991
Section 4.2.4(2)
section 5
Regulation 17 Electricity Safety (Network
Assets) Code 1996
whole document
═══════════════
r. 29
-- 34 of 35 --
S.R. No. 5/1997
Electricity Safety (Network Assets) Regulations 1997
33
NOTES
1 S.R. No. 260/1988.
2 S.R. No. 242/1988.
3 Application for Exemption
Any such exemption granted applies only to the particular case for which
application is made unless indicated otherwise and it is not an indication
that any future application will be granted.
4 Transportation costs
The person undertaking the transportation may be liable for all costs
incurred by the Network Operator as a result of transportation.